OPERATION: CONFIGURATION MoDE

MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MIN ¥ PRESS MAX & PRESS ENTER TC ENTER JJ KTEN® RSC "WHEN FLASHING" MAX FOR CHOICE ENTER j RTD 4392.2 392.3 392.4 385.2 385.3 385.4] input FENTER TYPE erd> RTD J 400crm, 500m = 10000hm VES VALUE lL ENTER I PROCESS } O-1V 0-1 0-10V 0-20mA |

Figure 3.2 Flowchart for Input Type

23

Page 32

part

3

OPERATION: CONFIGURATION MODE

Input Type (Thermocouple) Display

Action

Response

INPT TYPE

Press MENU Press ENTER

ENTER INPUT TYPE MENU: 1) Press MENU, if necessary, until "Inpt type" prompt appears. . ", or "proc" (RTD, Thermocouple, Process), if the 2) Display flashes "rtd", "tc displayed input type is Tc, press MENU to skip to step 5 (tc stops flashing).

INPT t. c

Press MAX Press ENTER Press ENTER

INPT J

Press MAX Press ENTER

Note ☞

THERMOCOUPLE SUBMENU: . " (flashing). 3) Press MAX to scroll to "tc . " stops flashing. 4) Display flashes "stored" message and "tc 5) Display flashes previous thermocouple type selection. ie. "J" (see below for types). 6) 7)

Scroll through the available thermocouple types to the selection of your choice. Display flashes "strd" message and advances to the next menu Reading Configuration.

Use the Input Type (Thermocouple) (RTD) or (Process) and verify your Dip Switch Setting (see section 2.4) and your Electrical Installation (see section 2.5). See the following pages for (RTD) and (Process) menus.

Thermocouple Types:

( J,

K,

T,

E,

N,

DIN J,

R,

S,

B,

C)

Display:

J CA

T

E

N

DNJ

R

S

B

C

24

Page 33

part

OPERATION: CONFIGURATION MODE

3

Input Type (RTD) Display

Action

Response

INPT TYPE

Press MENU Press ENTER

ENTER INPUT TYPE MENU: 1) Press MENU, if necessary, until "Inpt type" prompt appears. . ", or "proc" (RTD, Thermocouple, Process), if the 2) Display flashes "rtd", "tc displayed input type is RTD, press MENU to skip to step 5 (rtd stops flashing).

INPT RTD

Press MAX Press ENTER Press ENTER

INPT 392. 2

Press MAX Press ENTER

RTD Types:

385, 392, Two, Three and Four-wire

Display:

392.2 392.3 392.4 385.2 385.3 385.4 Note ☞

RTD SUBMENU: 3) Press MAX to scroll to "RTD" (flashing). 4) Display flashes "stored" message and "RTD" stops flashing 5) Display flashes previous RTD type selection ie. 392.2. (See below for RTD types.) 6) 7)

Scroll through the available RTD types to the selection of your choice: Display flashes "strd" message and advances to "rtd valU".

Last digit indicates: 2, 3 or 4-wire input. 25

Page 34

part

3

OPERATION: CONFIGURATION MODE

Input Type (RTD Value) Display

Action

Response

RTD VALU

Press ENTER

RTD VALUE SUBMENU: 8) Press ENTER at "rtd valU" prompt to enter your RTD Value. Display flashes previous RTD value selection ie. 100 _ (see below for RTD value selections)

RTD 100 _ STRD 100 _

Press MAX

9)

Press ENTER

10) Display flashes "stored" message and advances to "Reading Configuration".

RTD Values:

All RTD’s may be: 100 ohm 500 ohm

1000 ohm

Display:

26

100_

500_

Scroll through the available RTD Values to the selection of your choice:

1000

Page 35

part

OPERATION: CONFIGURATION MODE

3

Input Type (Process) Display

Action

Response

INPT TYPE

Press MENU Press ENTER

INPT PRoc

Press MAX Press ENTER Press ENTER

Proc 0-10

Press MAX Press ENTER

Note ☞

ENTER INPUT TYPE MENU: 1) Press MENU, if necessary, until "Inpt type" prompt appears. . ", or "proc" (RTD, Thermocouple, Process), if the 2) Display flashes "rtd", "tc displayed input type is Process, press MENU to skip to step 5 (proc stops flashing). PROCESS SUBMENU: 3) Press MAX to scroll to "Proc" (flashing). 4) Display flashes "stored" message and "Proc" stops flashing. 5) Display flashes previous Process type selection. ie. "0-10" (See below for types.) 6) 7)

Scroll through the available Process types to the selection of your choice. Display flashes "stored" message and advances to the next menu "Reading Configuration".

Use the Input Type (Thermocouple) (RTD) or (Process) and verify your Dip Switch Setting (see section 2.4) and your Electrical Installation (see section 2.5). See the previous pages for (RTD) and (Process) menus.

Process Types:

100mV

1V

10V

Display: Natural Gain Max Display

0-0.1

0-1.0

0-10

0-20

100 cts/mv 9999 @100 mv

10 cts/1mV 9999 @ 1V

1 ct/mV 9999 @ 10V

500 cts/mA 9999 @ 20 mA

Note ☞

0-20 mA

For 4-20 mA Input select 0-20 mA and adjust the Input Scale & Offset accordingly. To adjust 4-20 mA input. (See example under INPUT Scale & Offset.)

27

Page 36 read from a scan by OCR; it may hold reading errors

OPERATION: CONFIGURATION MoDE

MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MINV PRESS MAX & PRESS ENTER FFFF. FFF.F DECIMAL ves FF.FF POINT PROCESS F.FFF TEMP J c UNIT 1 F READING CONFIG FILTER 1 2 4 8 16 32 64 128 PROCESS IN1 YES INPUT RD1 SC & OFF IN2 RD2

Figure 3.3 Flowchart for Reading Configuration

28

Page 37

part

OPERATION: CONFIGURATION MODE

3

Reading Configuration Display

Action

RDG CNFG

Press MENU Press ENTER

DEC. PT DC. P T FFF. F

Response 1) 2)

DECIMAL POINT SUBMENU: Press ENTER

3)

Display flashes previous selection for decimal location.

Press MAX

4)

Press ENTER

5)

Scroll though the available selections and choose decimal location: FFFF. or FFF.F (also F.FFF and FF.FF, if "Process" type was selected in the "Input Type" menu). Display flashes "strd" message and advances to "Temperature Unit".

Note ☞

TEMP UNIT teMp %F

Press MENU, if necessary, until "Reading Configuration" prompt appears. Display advances to "deC. pt" (Decimal Point).

Decimal point for Process input type is passive.

TEMPERATURE UNIT SUBMENU: Press ENTER

6)

Display flashes previous Temperature Unit selection.

Press MAX

7)

Scroll though the available selections to the temperature unit of your choice: °F or °C.

Press ENTER

8)

Display flashes "strd" message and advances to "Filter Constant". 29

Page 38

part

3

OPERATION: CONFIGURATION MODE

Reading Configuration cont. Display fltr Cnst

Action

Response FILTER CONSTANT SUBMENU:

Press ENTER

9) Display flashes previous selection for filter constant.

Press MAX

10) Scroll though the available selections: 0001, 0002, 0004, 0008, 0016, 0032, 0064, 0128. - Default is 0004

FLTR 0001

Press ENTER

11) Display flashes "stored" message only if change was made. Note ☞

For PID control select filter value 0001-0004. A filter value of 2 is approximately equal to 1 sec. RC low pass time constant. If Process was selected in the "Input Type" menu the display will advance to "Input SC & OFF", otherwise the display advances to the "Alarm 1" menu.

Note ☞

30

The Filter Constant submenu allows the user to specify the number of readings stored in the digital averaging filter.

Page 39

part

OPERATION: CONFIGURATION MODE

3

Reading Configuration cont. (If process was selected) Display

INPT SC. 0 F

Action

Response INPUT SCALE & OFFSET SUBMENU:

Press ENTER

. F" prompt. Display flashes 1st digit in submenu "IN 1" 12) Press enter at the "INPT SC0

Press MAX & MIN

RD 1 0000.

Press ENTER

IN 2 9999.

Press MAX & MIN Press ENTER

13) Use MAX and MIN buttons to enter "IN 1" value. The "IN 1" value = min. input value * the natural gain. Example: 4(mA) x 500 = 2000 14) Display advances to "RD 1" submenu. 15) Use MAX and MIN buttons to enter "RD 1" value. IN 1” in terms of some meaningful engineering units This value responds to “I 16) Display advances to "IN 2" submenu. The "IN 2" value = max. input value * the natural gain. Example: 20(mA) x 500 = 10000 (9999) 17) Use MAX and MIN buttons to enter "IN 2" value. 18) Display advances to "RD 2" submenu.

Press MAX & MIN Press ENTER

19) Use MAX and MIN buttons to enter "RD 2" value. 20) Display flashes "stored" message and advances to "Alar 1" menu.

IN 1 2000.

RD 2 0100.

Press ENTER Press MAX & MIN

Note ☞

This submenu allows the user to scale the meter when in Process Mode and the above display value is an example for 4-20 mA input (4 to 20 mA = 0000 to 0100%). 31

Page 40

part

3

OPERATION: CONFIGURATION MODE Modifying Alarm settings will not reset the controller

Figure 3.4 Flowchart for Alarm 1 and Alarm 2 32