Page 21

part

SETUP

2

INPUT CONNECTION EXAMPLES 2.5.1. Thermocouple

The figure below shows the wiring hookup for any thermocouple type. For example, for Type K hookup, connect the yellow wire to the + (+S) Terminal and the red wire to the – (–S) Terminal. When configuring your controller, select Thermocouple and Thermocouple type in the Input Type menu (see part 3).

TYPE J K T E N R S B

Input Connector Jacket (external insulation) Terminal 1 (-) Terminal 2 (+) Extension Grade Red White dark-Brown Black Red Yellow dark-Brown Yellow Red Blue dark-Brown Blue Red Purple dark-Brown Purple Red Brown dark-Brown Brown Red Black Green Red Black Green Red Black Black

Figure 2.5.2 Thermocouple Wiring Hookup

13

Page 22

part

2

SETUP

2.5.2. Two/Three/Four-Wire RTD The figures below show the input connections and input connector jumpers

Figure 2.5.3

Two-Wire RTD Hookup 14 required to hookup a 2, 3 or 4-wire RTD. The two-wire connection is the simplest method, but does not compensate for leadwire temperature change and often requires calibration to cancel lead-wire resistance offset. The three-wire connection works best with RTD leads closely equal in resistance. The controller measures the RTD, plus upper and lower lead drop voltage and then subtracts twice the measured drop in the lower supply current lead producing excellent lead-resistance cancellation for balanced measurements. The four-wire RTD hookup is applicable to unbalanced lead resistance and enables the controller to measure and subtract the lead voltage which produces the best lead-resistance cancellation.When configuring your controller, select RTD type and RTD value in the Input Type Menu (see part 3).

Three-Wire RTD Hookup

Four-Wire RTD Hookup

Page 23

part

SETUP 2.5.3. Process Current

2

The figure shows the wiring hookup for Process Current 0 - 20 mA. When configuring your controller, select Process type in the Input Type menu (see part 3).

Figure 2.5.4 Process Current Wiring Hookup

2.5.4. Process Voltage The figure shows the wiring hookup for Process Voltage 0 - .1 V, 0 - 1 V, or 0 -10 V. When configuring your controller, select Process type in the Input Type menu (see part 3). Figure 2.5.5 Process Voltage Wiring Hookup 15

Page 24

part

3

OPERATION: CONFIGURATION MODE

3.1 Introduction The Controller has two different modes of operation. The first, Run Mode, is used to display values for the process variable, setpoint value and to display or clear peak and valley values. The other mode, Menu Configuration Mode, is used to navigate through the menu options and configure the controller. Part 3 of this manual will explain the Menu Configuration Mode. For your controller to operate properly, the user must first "program" or configure the menu options in the Menu Configuration Mode.

Turning Your Controller On for the First Time

16

The Controller becomes active as soon as it is connected to a power source. It has no On or Off button. The Controller will at first flash reset on the PV and software version number on the SV display, and then proceed to the Run Mode.

Page 25

part

OPERATION: CONFIGURATION MODE

3

Button

Function in Configuration Mode

MENU

To enter the Configuration Mode, the user must first press MENU. Use this button to advance/navigate to the next setting. The first menu to appear will be "ID Code", if enabled. The user can navigate through all the top level menus by pressing MENU. Selecting an ID of 0000 will allow you to bypass the ID Menu using the MENU button.

Press this button to scroll through "flashing" selections. When a numerical value is flashing, this button will increase the active digit from "0" to "9". After "9" the display starts at "0" again. The most significant digit may also show a "–" sign. In the Run Mode MAX causes the display to flash the PEAK press again to return to the PV value.

Press this button to go back to a previous Top Level Menu item. Press this button twice to reset the controller to the Run Mode. When a numerical value is flashing, this button will scroll through the digits from left to right digit allowing the user to select the desired digit to modify. In the Run Mode, MIN causes the display to flash the VALLEY - press again to return to the PV value.

ENTER

Press this button to access the submenus from a Top Level Menu item. Also, press this button to store a submenu selection or after entering a value, the display will flash a "stored" message to confirm your selection. To reset flashing PEAK or VALLEY press ENTER. In the Run Mode, press ENTER twice to enable Standby Mode with flashing "STBY".

NOTE:

Except for Setpoints and the Alarms, modifying any settings of the menu configuration will reset the controller prior to resuming Run Mode. 17

Page 26

part

3

OPERATION: CONFIGURATION MODE

3.2 Menu Configuration: Modifying set points will not reset the controller

Figure 3.1 Flowchart for ID and Set Point Menus 18

Page 27

part

OPERATION: CONFIGURATION MODE

ID Number (if enabled) Display

Action

Note ☞

3

It is recommended that you put the controller in the Standby Mode for any configuration change other than setpoints & alarms

Response

SEE ID OPTION SUBMENU IN THE BREAK LOOP ALARM SECTION FOR ENABLE/DISABLE ID OPTION

Id C0de

Press MENU Press ENTER

ID. C D ____

Press MAX & MIN Press ENTER

ENTERING OR CHANGING YOUR (NON-DEFAULT) ID NUMBER 1) Press MENU, if necessary, until "ID C 0DE" prompt appears. 2) Display advances to "ID CD", if non-default ID code. If default ID code, the menu will advance to CH.ID with default value i.e. 0000. If the ID code is the default value i.e. 0000, press MENU again and the menu will skip the Note ☞ ID code to Set Point Menu. 3) Press MAX to increase digit 0-9. Press MIN to activate next digit (flashing). Continue to use MAX and MIN to enter your 4-digit ID code. 4) If the correct ID code is entered, the menu will display CH.ID, otherwise an error message will be displayed and the controller will return to the Run Mode.

CK. I D 1234

Press MENU or Press MAX & MIN

5)

STRD 1234

Press ENTER

6)

Note ☞

To leave your ID code Unchanged, press MENU and advance to "SET PoNT" Menu. To Change your ID code use the MAX and MIN buttons to enter a new ID code. Display flashes "STRD" message and advances to the next menu "SET PoNT".

To prevent unauthorized tampering with the setup parameters, the controller provides protection by requiring the user to enter the ID code before allowing access to subsequent menus. If the ID code entered does not match the ID code stored, the controller responds with an error message and access to subsequent menus will be denied. Use numbers that are easy for you to remember. If the ID code is forgotten or lost, call customer service with your serial number to reset the default to "0000".

19

Page 28

part

3

OPERATION: CONFIGURATION MODE

Set Points (if ID Number Enabled) Display

Action

Response

SET PT

Press MENU Press ENTER

SETPOINT 1 1) Press MENU, if necessary, until "SET PT" prompt appears. 2) Display advances to "SP1", Setpoint 1.

SP1 100. 5

Press MAX Press MIN

STRD 100. 5

Press ENTER

SP2 210. 5 STRD 210. 5 20

DISPLAY SHOWS PREVIOUS VALUE. 1ST DIGIT FLASHING. 4) Press MAX to increase digit 0-9. 5) Press MIN to activate next digit (flashing). 6) Continue to use MAX and MIN to enter your 4-digit Setpoint 1 value. 7)

Display flashes "STRD" message only if a change is made, otherwise press MENU to advance to "SP2", Setpoint 2.

SETPOINT 2 : DISPLAY SHOWS PREVIOUS VALUE. 1ST DIGIT FLASHING. Press MAX & MIN

9)

Use MAX and MIN buttons to enter your 4-digit Setpoint 2 value.

Press ENTER

13) Display flashes "STRD" message and advances to “Swapping Setpoints” submenu.

Page 29

part

OPERATION: CONFIGURATION MODE

3

Setpoints cont. Display

Action

Response OUTPUT REDIRECTION: DISPLAY SHOWS “S1.o.1” AND CURRENT SETTING, “S1.o.1” OR “S1.o.2”

S1.o.1 S1.o.1

. ” is selected, Setpoint 1 (and OUT 1 configuration) direct the control output at When “S1.o1 label “Output 1” and Setpoint 2 (and OUT 2 configuration) direct the control output at label . ” is selected , Setpoint 1 (and OUT 1 configuration) direct the control “Output 2.” When “S1.o2 output at label “Output 2” and Setpoint 2 (and OUT 2 configuration) direct the control at label “Output 1.” Summary

Press MAX Press ENTER Note ☞

Setting S1.o.1

Setpoint/Out/LED Output Label 1 1 2 2 S1.o.2 1 1 2 2 14) Press MAX to select the output option. 15) Press ENTER to make the selection or MENU to advance to “Input Type”.

Always put unit in stand-by before redirecting the outputs, and always perform a reset afterward to ensure proper operation. With Analog Proportional output option, the following issues need to be considered when redirecting the output: 1) Current (4-20 mA) output is disabled; 2) %Hi/Lo and SELF setting is moved to Out 2 configuration menu; 3) Control Type and Cycle Time appear in Out 1 and is associated with time proportional control at Output 2; 4) Control Type and Cycle Time setting in Out 2 is disregarded by Analog Proportional output. 21

Page 30

part

3

OPERATION: CONFIGURATION MODE

Set Points (if ID Number Disabled - default) Display

125. 5 100. 5

Action

Press MENU (1 time) Press MAX Press MIN Press ENTER

125. 5 210. 5

Press MENU (2 times)

125. 5 S1.o.1

Press MENU (3 times) Press MAX Press ENTER

22

Response With ID number disabled and in Run Mode, pressing MENU one time advances the controller to Setpoint 1 setting directly. SET POINT 1 1) Press MENU once from Run Mode. 2) Display flashes the first digit of Setpoint 1. 3) Press MAX to set the digit, 0-9. 4) Press MIN to activate the next digit (flashing). 5) Repeat step 3 and 4 until all digits are set. 6) Controller stores new setting and returns to Run Mode. SET POINT 2 1) Press MENU twice from Run Mode. 2) Display flashes the first digit of Setpoint 2. 3) Follow step 3 to 6 of Setpoint 1 to complete the setting.

OUTPUT REDIRECTION 1) Press MENU 3 times from Run Mode. 2) Display flashes “S1.o.1” in the SV window. (See previous page for more details.) 3) Press MAX to select the output option. 4) Press ENTER to make the selection or MENU to advance to “Input Type”.