MICRO-INFINITY ICN77000 Series Controller Operator's Manual, pages 11 to 20

Pages 11 to 20 of 108

The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Newport Electronics, Inc. ICN77530

Page 11

part

INTRODUCTION

1

TO DISABLE OUTPUTS Standby mode is useful during setup of the controller or when maintenance of the system is necessary. When the controller is in standby, it remains in the ready condition but all outputs are disabled. This allows the system to remain powered and ready to go.

When the controller is in "RUN" Mode, push ENTER twice to disable all outputs and alarms. It is now in "STANDBY" Mode. Push ENTER once more to resume "RUN" Mode.

PUSH ENTER TWICE to disable the system during an EMERGENCY.

3

Page 12

part

2

SETUP

2.1 Mounting the Controller Note ☞

If necessary, the rear connector assembly may be removed from the main case for wiring (see Figure 2.1a for Square Mount, Figure 2.1b for Round Mount).

R 0.06 [1.6]

4

Page 13

part

SETUP

Square Mount

2

Square Mount Micro Controller Mounting Instructions

Figure 2.1a, Mounting the Square Mount Controller 5

Page 14

part

2

SETUP

Round Mount

Round Mount Micro Controller Mounting Instructions 1.

Separate the display from the meter by squeezing the case (where shown) and then unplugging the cable from the meter.

2.

Slide the retainer over the rear of the case, but do not engage serrations on case.

3.

Pass the cable (from the display) thru a 1 3/4" diameter hole in the mounting panel and connect to the meter (take care to center the connector on the mating pins). While squeezing the case, press the display and meter squarely together until they connect.

4.

Check the display and gasket for proper alignment, then slide the retainer tight against the backside of the mounting panel.

Figure 2.1b, Mounting the Round Mount Controller 6

Page 15

part

SETUP

2

2.2. Front Panel View Front Panel Annunciators

Figure 2.2 Front Panel Display

SP1

OUT1/Setpoint 1 indicator.

SP2

OUT2/Setpoint 2 indicator.

AL1

Alarm 1 indicator.

AL2

Alarm 2 indicator.

°C

°C unit indicator.

°F

°F unit indicator.

PV

Upper display shows the Process Value

SV

Lower display shows the Setpoint Value

MENU

Changes display to Configuration Mode and advances thru menu items*

Used in program mode and peak recall*

Used in program mode and valley recall*

ENTER

Accesses submenus in Configuration Mode and stores selected values*

* See Part 3 Operation:Configuration Mode 7

Page 16

part

2

SETUP

2.3. Rear Panel View

Figure 2.3 Typical Rear Connector Label and Possible Labels of Different Models 8

Page 17

part

SETUP

2

Rear Panel Connector Labels POWER

AC Power Connector: All models

INPUT

Input Connector: All models TC, PR (Process) RTD

ALARM 1

ALARM 1 relay SPST, programmable: All models

OUTPUT 1

Control Output 1: Based on one of the following models. Relay SPDT Voltage and Current Solid State Relay Pulse

OUTPUT 2

Control Output 2: Based on one of the following models: Relay SPST Normally Open Solid State Relay Pulse

OPTION

Based on one of the following models: RS-232C Isolated Analog Out RS-485 Alarm 2 Relay SPST, programmable Remote Setpoint 9

Page 18

part

2

SETUP

2.4. Mechanical Installation The settings of the DIP switch must be verified or set to comply with your selection at the Input/Type menu (see Section 3.0 for Input/Type). The DIP switch is accessible through an opening on the side of the case or may be accessed by removing the controller from the case, see Section 2.1 for instructions. Locate the dip switch (see Figure 2.4) and set the switches according to the following tables.

Dip Switch Configuration

Unit installed in case.

Unit removed from case.

opening in case

Figure 2.4 Dip Switch Location, switch settings are shown in OFF position 10

Page 19 read from a scan by OCR; it may hold reading errors

SETUP M24

Dip Switch Settings Thermocouple RTD 100 RTD 500/1k ohm Process 20mA Process 100mV Process 1V Process 10V

11

Page 20

part

2

SETUP

For SSR wiring hook-up examples, refer to Specification Section.

2.5. Electrical Installation POWER CONNECTION EXAMPLES The figure below shows the power wiring hookup. Use copper conductors only for power connections The Protective Conductor terminal must be connected for safety reasons.

Figure 2.5.1 Power Wiring Hookup Note ☞

12

The Safety European Standard EN61010-1 for measurement, control, and laboratory equipment requires that fuses must be specified based on IEC127. This standard specifies for a Time-lag fuse, the letter code “T”. The above recommended fuses are of the type IEC127-2-sheet III. Be aware that there are significant differences between the requirements listed in the UL 248-14/CSA 248.14 and the IEC 127 fuse standards. As a result, no single fuse can carry all approval listings. A 1.0 Amp IEC fuse is approximately equivalent to a 1.4 Amp UL/CSA fuse. It is advised to consult the manufacturer’s data sheets for a cross-reference.

Fuse

Connector

Output Type

115 Vac

230 Vac

Fuse 1

Output 1

Relay

5 A(T)

3 A(T)

Fuse 2

Output 1

Relay

5 A(T)

3 A(T)

SSR

0.5 A(T)

0.5 A(T)

Fuse P

Power

N/A

100 mA(T)

100 mA(T)

Fuse A

Alarm 1/2

Relay

3 A(T)

3 A(T)

Note: Values shown are minimum recommendations for the protection of the controller. For a specific load, consult the respected electrical specifications to select a suitable fuse.