Page 51

part

OPERATION: CONFIGURATION MODE

3

Output 1 cont. Display

Action

Response MAXIMUM/PERCENT HIGH SUBMENU Specify in percent, the maximum value (0099) for control output. If the output is analog, then the maximum voltage or current, in percent, is specified. If the output is time proportional, then the maximum duty-cycle, in percent, is specified.

% % XI

0099

Press MIN & MAX Press ENTER

10) Display shows “% % xi ” and flashes the 10s digit of the current Percent Low setting. 11) Use MAX & MIN buttons to enter a new value for Percent Low. 12) Press ENTER to store the current setting and to advance to *Control Type submenu.

Example: On an analog output of 0~10 Vdc, a setting of %LO = 10 and %HI = 90, cause the minimum on the control output to be 1 V and the maximum on the control output to be 9 V. The same setting on a time proportional output, will cause 10% duty cycle for the minimum control output and 90% duty cycle for the maximum control output. To disable %LO/HI, set LO to 00 and HI to 99. If %LO/HI is at other values than the default (%LO = 00, %H I= 99), “Soak” is disabled.

CTRL TYPE CTRL PID

Press ENTER Press MAX Press ENTER Note ☞

*CONTROL TYPE SUBMENU: (Relay, SSR or Pulse Option) 13) Display flashes "0n . 0f" or "Pid". 14) Scroll through the available selections: ON/OFF or PID. 15) Display flashes "strd" message and advances to "Action Type" submenu.

The ON/OFF control is a coarse way of controlling the process. The "Dead Band" improves the cycling associated with the On/Off control. The PID control is best for processes where the setpoint is continuously changing and/or a tight control of the process variable is required. PID control requires tuning and adjustment of the "Proportional", "Integral or Reset" and "Derivative or Rate" terms by a trial-and-error method. The Controller provides an "Auto Tuning" feature making the tuning process automatic, possibly optimum. 43

Page 52

part

3

OPERATION: CONFIGURATION MODE

Output 1 cont. Display

4-20 CURR

Action

*If Current/Voltage is your analog control output 1, this menu i.e. ctrL type will not appear, instead 4-20/Curr will be displayed. Select "Enbl" for a 4-20 mA (2-10 V) output or "dsbl" for a 0-20 mA (0-10 V) output. If 4-20 mA is enabled, %HI/LO setting will have no effect. Note ☞

ACTN TYPE ACTN DRCT Note ☞

44

Response

Both Current and Voltage control outputs are active simultaneously.

Press ENTER Press MAX Press ENTER

ACTION TYPE SUBMENU: 16) Display flashes "drCt" or "rvrs". 17) Scroll through the available selections: Direct or Reverse. 18) Display flashes "strd" message and advances to "Auto PID" submenu. If "ON/OFF" was selected in the Control Type, the display skips to the "Dead Band" submenu.

The error that results from the measurement of the process variable may be positive or negative since it may be greater or smaller than the set point. If a positive error should cause the controller output to increase (i.e. cooling), it would be called Direct Acting. If a negative error should cause the output to increase (i.e. heating), it would be called Reverse Acting.

Page 53

part

OPERATION: CONFIGURATION MODE

3

Output 1 cont. Display

Action

Response

AUTO PID

Press ENTER Press MAX

AUTO PID SUBMENU: 19) Display flashes "enbl" or "dsbl". 20) Scroll through the available selections: Enable or Disable. If "Enabled", the controller can determine, by enabling Start PID, the optimum values for the three adjustments, Proportional, Reset and Rate corresponding to P, I, and D. These values may be changed once the auto tuning is complete. If "Disabled" is selected, the user will manually enter these three adjustment values. If you want the controller to do the auto PID and the P, PI or PID, first select auto disable and enter 0000 for the unwanted parameter. e.g. for PI enter 0000 for the rate.

AUTO ENBL

Press ENTER

ADPT C TRL

Press ENTER Press MAX

21) Display flashes "stored" message and advances to "Adaptive Control" submenu. *ADAPTIVE CONTROL SUBMENU: * (NOT INSTALLED) 22) Display flashes "enbl" or "dsbl". 23) Scroll through the available selections: Enable or Disable. If "Enabled", the Adaptive Tuning dynamically changes and updates the P, I, and D parameters for optimum control. The adaptive tuning is useful when the load continuously changes thereby requiring new values for P, I, and D.

ADPT ENBL Press ENTER

24) Display flashes "stored" message and advances to "Anti Integral" submenu. 45

Page 54

part

3

OPERATION: CONFIGURATION MODE

Output 1 cont. Display

ANTI I NTG

Action

Response

Press ENTER Press MAX

ANTI INTEGRAL SUBMENU: 25) Display flashes "enbl" or "dsbl". 26) Scroll through the available selections: Enable or Disable. If "Enabled", this feature allows the error term outside the proportional band to be calculated and accumulated for integration. This may be an important feature in applications where fast response time is desirable.

ANTI ENBL Press ENTER

STRT PID STRT ENBL Note ☞

46

Press ENTER Press MAX

Press ENTER

27) Display flashes "stored" message and advances to "Proportional Band" submenu if Auto PID was disabled, otherwise it will go to "Start PID". START AUTO TUNE PID: 28) Display flashes "enbl" or "dsbl". 29) Scroll through the available selections: Enable or Disable. If "Enabled", the controller is ready to calculate P, PI or PID parameters. The setpoints must be at least 20°F or 11°C above the (PV) Process Value in order to perform autotune, otherwise an error message will be displayed. 30) Display flashes "strd" message and advances to the “Cycle Time” submenu.

To start Auto Tune PlD select PID, enable Auto PID and enable Start PID. Sometimes Auto PID parameter needs fine tuning i.e. for each 5°F over shoot increase the Proportional Band (PB) by 15% and for each ±1°F fluctuation at the Setpoint (SP) increase reset by 20%. Once started, display shows “A.tun” with the letters blinking in the rotating pattern. Do not perform any operations or settings before first stopping Auto Tune. Any alarms or other output is disabled during Auto Tune.

Page 55

part

OPERATION: CONFIGURATION MODE

3

Output 1 cont. Display

Action

Response If "AUTO TUNE PID" was "DISABLED", the display will show the following three submenus so the user may manually enter values for Proportional, Reset and Rate terms corresponding to P, I, and D. It also can be used for auto PID for disabling unwanted parameters e. g. PI, enter 0000 for rate:

PROP BAND

Press ENTER Press MAX & MIN Press ENTER

PROPORTIONAL BAND SUBMENU: 28) Display flashes 1st digit of the previous P "Proportional Band" value. 29) Press MAX and MIN buttons to enter a new "Proportional Band" value. 30) Display flashes "strd" message and advances to "Reset Setup" submenu. NOTE: Proportional band is in degrees of temperature or counts of process.

REST STUP

Press ENTER Press MAX & MIN Press ENTER

RESET SETUP SUBMENU: 31) Display flashes 1st digit of the previous I "Reset" value. 32) Press MAX and MIN buttons to enter a new "Reset" value. 33) Display flashes "strd" message and advances to "Rate Setup" menu. NOTE: Reset unit is in seconds 0-3999.

RATE STUP

Press ENTER Press MAX & MIN Press ENTER

RATE SETUP SUBMENU: 34) Display flashes 1st digit of previous D "Rate" value. 35) Press MAX and MIN buttons to enter a new "Rate" value. 36) Display flashes "strd" message and advances to the "Cycle Time" submenu for RTD and Thermocouple types. If the Output 1 is analog option the display skips to "Damping Factor". NOTE: Rate unit is in seconds 000.0-399.9. 47

Page 56

part

3

OPERATION: CONFIGURATION MODE

Output 1 cont. Display

Action

Response

CYCL TIME

Press ENTER

CYCLE TIME SUBMENU: 37) Display flashes 1st digit of the previous "Cycle Time" value.

CYCL 0010 Note ☞

48

Press MAX & MIN

38) Press MAX and MIN buttons to enter a new "Cycle Time" value. (1 to 199 seconds).

Press ENTER

39) Display flashes "stored" message and advances to "Damping Factor" submenu.

A Cycle Time selected between 1 and 199 seconds determines the total On/Off time of each proportional cycle. For example, a 15 second Cycle Time means that every 15 seconds the output will turn on for part or all of the cycle. For Relay control outputs, do not select a cycle time of less than 7 seconds or the relays life time will be shortened. For a Cycle Time of less than 7 seconds select SSR or DC pulse. Use an external SSR with the DC pulse option for higher currents (higher than 1 Amp).

Page 57

part

OPERATION: CONFIGURATION MODE

3

Output 1 cont. Display

DPNG FCTR DPNG 0001 Note ☞

Action

Response

Press ENTER

DAMPING FACTOR SUBMENU: 40) Display flashes the previous "Damping Factor" selection.

Press MAX Press ENTER

41) Scroll through the available selections: 0000, 0001, 0002, 0003, 0004, 0005, 0006, 0007, 0008 - Default is 0003. 42) Display flashes "strd" message and advances to the "Output 2" menu.

Damping Factor is a measure of speed, overshoot, and undershoot in which the process variable responds to the output changes of the controller, which were used during the Auto Tune. This value is typically set to the ratio of Rate to Reset. This Default value is (0003). For fast response time, this value should be decreased while for slow response time it should be increased.

49

Page 58

part

3

OPERATION: CONFIGURATION MODE

Output 1 cont. Display

Action

DEAD BAND

Press ENTER

DEAD 006. 7 Note ☞

50

Press MAX & MIN Press ENTER

Response The "Dead Band" submenu will only appear if the "On/Off" was selected from the "Control Type" menu. DEADBAND SUBMENU: 43) Display flashes 1st digit of the previous "Dead Band" value.

44) Press MAX and MIN buttons to enter a new "Dead Band" value 45) Display flashes "strd" message and advances to the "Output 2" menu. Note ☞

Dead Band units are the degree of temperature or counts of process.

The Dead Band or neutral zone is the number of degrees or counts (if input type is process) around the setpoint which the process variable must pass above or below the setpoint, before the output changes state.

Page 59 read from a scan by OCR; it may hold reading errors

OPERATION: CONFIGURATION MoDE

MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MINY PRESS MAX & PRESS ENTER OUT \yyes OUT 2 PID F ON OFF 2 ON-OFF | PID >

ACTION p - REVERSE | TYPE Lm DIRECT

DISABLE PID

{ __} - - - AUTO L___ ENABLE

PROP. BAND

DEAD BAND

CYCLE TIME

Figure 3.7 Flowchart for Output 2

51

Page 60

part

3

OPERATION: CONFIGURATION MODE

Output 2 Display

Action oUT 2

Press MENU Press ENTER

NoT _ INST

Press MENU

CTRL TYPE

Press ENTER Press MAX

CTRL PID

Press ENTER

Note ☞

52

Response 1) Press MENU, if necessary, until the "out 2" prompt appears. 2) Display advances to "Control Type" submenu. IF OUTPUT 2 IS NOT INSTALLED, THE CONTROLLER WILL SHOW "NOT INSTALLED" Press MENU, if the "not installed" message is displayed, advance to the "Ramp & Soak" submenu.

CONTROL TYPE SUBMENU: 3) Display flashes "0n . 0f" or "PId". 4) Scroll through the available selections: 0n . 0f or PId.

5) Display flashes "strd" message and advances to "Action Type" submenu.

The ON/OFF control is a coarse way of controlling the process. The "Dead Band" improves the cycling associated with the On/Off control. The PID control is best for processes where the set point is continuously changing and/or tight control of the process variable is required.