4194-E P-20 SECTION 2 MAINTENANCE AND INSPECTION
SECTION2 MAINTENANCE AND INSPECTION
1-4;
1-2.
Daily checks greatly help to keep your CNC operating properly at all times. The self-diagnostic function, integrated in the CNC, help you locate the trouble if the machine malfunctions, allowing the user to take appropriate corrective action to minimize down time.
Consult also the following section: Section 3 "TROUBLES AND TROUBLESHOOTING” Inspection during Installation
Installation Site
When determining the installation place of the machine and the CNC unit, accessibility to ihe machine for easy operation is an important factor to be carefully attended to. In addition, easy access to the CNC unit and the control enclosure for the purpose of maintenance and inspection must also be taken into consideration. r (4.9 ft) ZY We ea Control enclosure
\\
NN
¥
LLL
Fig. 2-17 Layout
OS
Arrange the machine and the CNC unit in the manner shown above.
For the inspection and maintenance, space as shown in the illustration must be secured to allow doors of the control enclosure to be opened with sufficient area for working. Do notinstall the enclosure close to the shop wall. Environmental Requirements Observe the following points when installing the CNC unit and the control enclosure. - Make sure that the CNC unit will not be subject to direct sunlight. - Make sure that the control enclosure will not be splashed with chips, water, or oil.
- Make sure that the control enclosure and the operation panel will not be subject to excessive vibration or shock.
Permissible ambient temperature range of the control enclosure is 0 to 40°C.
Permissible humidity range of the control enclosure is 75% or lower (no condensation).
- The maximum altitude at which the control enclosure can be installed is 1000 m (3281 ft.).
Page 32
4194-E P-21 SECTION 2 MAINTENANCE AND INSPECTION
1-3.
Primary Power Supply Prepare the primary power supply that complies with the following requirements. - Voltage: 200 V - Voltage fluctuation: +10% max. - Power supply frequency: 50/60 Hz
- Do not draw the primary power supply from the distribution panel that also supplies the power to a major noise source (for example, an electric welder and electric discharge machine) since this could cause malfunctioning of the CNC unit.
- lf possible, connect the conirol enclosure to a ground independently. If there is no choice but to use a ground with other equipmeni, avoid connection to the ground where noise generating equipment such as an electric welder or an electric discharge machine is connected.
Main motor kW kVA | Please prepare the power source - conforming to the items specified Power requirements kW | in the final specifications.
Cable size mm? Momentary voliage variation rate
Apparent power
Refer to 1-4 and 1-5.
Power source inductance nH
Input Voltage Range Including Voltage Variation
Make sure that the voltage of the power source, including the momentary voltage variation, is within the range indicated below. Ifthe input voliage is outside the range indicated below, acceleration/deceleration time of the spindle will be elongated.
Input voltage range: 200 VAC, 10% to 230 VAC +10%
Page 33
4194-E P-22 SECTION 2 MAINTENANCE AND INSPECTION
1-5. | Momentary Voltage Variation Rate and Power Source Inductance
Table 2-1 indicates the permissible inductance of the power source for MPS and MIP units. If the inductance of the power source is larger than the permissible value, acceleration/deceleration time of the spindle will be elongated even if the power source voltage is within the range indicated above.
Since it will be difficult to measure the inductance of the power source, measure the rate of momentary voltage variation caused by acceleration and deceleration of the spindle instead of the inductance and ensure that the measured value is within the momentary voltage variation rate indicated in Table 2-1. Ifthe inductance of the power source is large, momentary voltage variation rate gets larger accordingly.
Table 2-1 Power Source Inductance Momentary Voltage Variation Rate Unit | 230 V Power | 220 V Power | 200 V Power | 230 V Power | 220 V Power | 200 V Power Source Source Source Source Source Source (70 pH (70 pH (70 nH MPS60 or less) or less) or less) (140 pH (140 wH (140 nH 5 MPS30 or less) or less) or less) 15% orless | 15% orless | 15% orless 400 H 400 nH 400 pH MPStO or less or less or less (110 wH 110 uH 230 pH MIP22 or less) or less or less ih an Bear bees Ris (230 oH 230 nH 480 nH (6% or less) 6 or less 15% or less or less) or less or less Note: A value in ( ) shows an estimated value. AXCAUTION : (1) If more than one machine is connected to the same power source, the value of
“inductance of power source” for each machine is obtained by dividing the value in the table by the number of the machines to be connected.
(2) Wiring inductance in 50-meter cable (164.05 ft) is approximately 12 wH when general KIV cable is used.
Page 34
4194-E P-23 SECTION 2 MAINTENANCE AND INSPECTION
[ Calculating momentary voltage variation rate ] i Oo oR ' ee ( i L 3-phase power source - VACIII drive unit VAC motor Vo: Voltage while the moior is stopped. Vi: Maximum voltage during motor deceleration. AC voltmeter “a Vi-V Momentary voltage variation rate = a 0
(1) Connect an AC voltmeter to the power supply terminals at the spindle drive motor controller as shown above.
(2) Measure the voltage while the spindle motor is stopped and take this value as “VO”.
(3) Measure the maximum voltage while the spindle motor is decelerating and take this value as vi",
(4) Calculate the momentary voltage variation rate using the following formula. Momeniary voltage variation rate = (V;, Vo)/Vg
[Supplement] 1. Since a digital AC voltmeter has slow response, momentary voltage variation rate obtained using the values measured with the digital AC voltmeter is smaller than the actual value. To obtain the precise value, it is recommended to use an analog
AC volimeter.
2. Voltage “V1” cannot be measured accurately if motor deceleration time is short. Therefore, it is recommended to start deceleration from as high spindle speed as possible.
Page 35
4194-E P-24 SECTION 2 MAINTENANCE AND INSPECTION im Daily Inspection
The CNC unit incorporates electronic devices which are susceptible to moisture, oil, dirt, dust, and chips, and also elevated temperatures in the enclosure caused by clogging of filters in the cooling unit. Therefore, daily inspection and maintenance of the CNC unit is important.
2-1. Daily Inspection
(1) Inspection of Appearance of Control Enclosure and Operation Box
Visually check the control enclosure and the operation box for adhesion of water, oil, dust, and chips and also the cooling unit filter for clogging.
If the control enclosure and the operation box are dirty, clean them. At the same time check the inside of the control enclosure and the operation box.
2-2. Every Three-month Inspection
(1) Cleaning the Cooling Unit Make sure that the cooling unit mounted at the control enclosure door operates to blow air hard. If the filter is clogged, clean it.
2-3. Cleaning the Floppy Disk Drive
(1) Cleaning the 3.5” Floppy Disk Drive Head
A dirty read/write head may sometimes cause the floppy disk read/write error. Clean the head using a head cleaning disk.
The head cleaning disk may be either a market product or the one ordered from Okuma. Okuma part No.: E0241-602-003 Okuma part name: Floppy head cleaning disk FCD-3.5W (Maker: Nippon Microcoating)
(2) Head Cleaning Procedure
To clean the head with the above cleaning disk, proceed as follows. When using the other maker's cleaning disk, follow the attached instructions.
(a) Insert the head cleaning disk into the floppy disk drive unit. (b) Drive the cleaning disk using the disk initializing function. 1) Press EDIT AUX key. 2) Press the function key [F8] (EXT END), 3) Press the function key [F2] (INIT).
4) Key in as follows: =IN FDO: Initialization OK (Y/N)! Y Formatting (Y/N) !Y Format (2DD, 720K = 0, 2HD ~ 1.44M = 1)!0
5) The drive unit's LED blinks when cleaning is started.
Page 36
4194-E P-25 SECTION 2 MAINTENANCE AND INSPECTION
6) After 90 seconds, the floppy disk read/write error occurs and the cleaning is finished. This error occurs because no data can be written onto the cleaning disk as a matter of course.
(c) This is the end of cleaning. If no good effect is found, repeat cleaning a maximum of five times.
(d) If satisfactory result is not obtained after five times of cleaning, the drive unit or the floppy disk may be faulty. . (3) Precautions for Cleaning Excessive head cleaning will give damage to the fioppy disk unit head.
When using the above recommended disk, remember that the adequate frequency is once in three months and do not exceed the limit of four times a month.
(4) Cleaning Disk Life The above cleaning disk will lose effect when used for a total of one hour (40 times) because the disk is clogged with dirt.
Page 37
4194-E P-26 SECTION 3 TROUBLES AND TROUBLESHOOTING
SECTION3 TROUBLES AND TROUBLESHOOTING
The purpose of this section is to minimize downtime of the machine through speedy detection and remedies of the cause of any trouble that might occur.
It is extremely important to make detailed checks on the condition of the machine and CNC system when the trouble arose and to carry out various kinds of tests described in this section. Thus, the customer himself will be able to fix the machine in most cases. The test results reported to your local Okuma representative will be a great help in determining the nature and extent of the trouble and the remedies to be applied.
1. General Check Procedure When Trouble Occurs
Generally, check the following matters: (1) When Trouble Occurs, (a) Mode of operation (b) Current position and command position (c) What STATUS display lamp is going on? (d) Is the ALARM lamp on?
When the ALARM lamp is on, the cause of the alarm can be known from the contents of the alarm message given on the CRT.
(2) After Resetting the CNC System, (a) Does the trouble occur at the same situation repeatedly? (b) Does the same trouble occur in other modes of operation? (c) How about frequency of the trouble?
(d) Does the trouble arise regularly in terms of time, temperature, eic.?
Page 38
4194-E P-27 SECTION 3 TROUBLES AND TROUBLESHOOTING
2. Trouble Analysis
(The machine stopped and does not restart. )
Is the screen ON?
Is an alarm message displayed?
Is the screen display changeable?
No
Check the contents of the block in which the machine has stopped.
Is the NC STATUS - STM lamp on the operation panel lit?
a Y v
Refer to the Display the CHECK Please contact your The computer is not “ALARM & ERROR DATA screen and local Okuma operating normally. LIST” supplied check the representative. (1) Check in what separately io locate input/output signals. status the the cause of the See 3. “Checking computer has trouble. the Input/Output stopped. Signals” in this See 4. “CPU Status section, Indication” in this See Section 4, 2. section. “Check Data (2) Check the Display”. power supply unit for its input voltage. See 5. “Power Supply Unit Status Indication” in this section (3) Contact your local Okuma representative.
Page 39
4194-E P-28 SECTION 3 TROUBLES AND TROUBLESHOOTING
3.
Checking the Input/Output Signals
A variety of electric parts such as limit switches, proximity switches, solenoid valves, and motors is mounted in the machine, and these machine-mounted electric parts are placed in very severe environment affected by chips, coolant, oil, dirt, and dust. Although water- and dust-proof construction is adopted to protect these electric parts, electrical trouble causes a high rate of the CNC troubles.
However. most of the electric parts are relatively simple in their operation and can be easily checked and repaired by the user's maintenance technicians.
This section describes the practical methods for checking the input/output signals.
Checking the Input/Output Signals at the CHECK DATA Screen
(1) Displaying the I/O CHECK Screen
The ON/OFF status of the input and output Signals of the CNC unit can be checked at the I/O CHECK screen.
< Procedure > (1) Select an operation mode (automatic, MDI, manual). (2) Press function key [F7] (CHECK DATA). The CHECK DATA screen is displayed. (3) Press the page selection key to display the I/O CHECK screen.
AUTO OPERATION A. MIN 0 N 1 97/08/07 12:00:00 Py CHECK DATA 1/0 CHECK 0. 0 PAGE 1 loo | SS0i 1/2 i [INPUT] | [OUTPUT] BIT LABEL BIT LABEL | BIT LABEL BIT LABEL 0 ipITLk 8 ipRPDN | 0 opMJLL 8 1 ipPBR2 9 ipRPDP | 1. opPB2L | 2 ipPBR1 A ipPHON ] 2 opPBIL A opPHL 3. ipBLSK B ipAXS5 | 3 opBSKL B opAX5L 4 ipMRI4 C ipAXs4 | 4° opMR4L C opAX4L 5 ipMR1Z D ipAXSZ | 5 opMRZL D opAXZL 6 ipMRIY E ipAXSy | 6 opMRYL E opAXYL 7 ipMRIX F ipAXSX | 7 op¥RXL F opAXXL DATA=00H DATA=00H =| DATA=00H DATA=00H PROGRAM|ACTUAL |PART | BLOCK | | | CHECK | SELECT! POSIT. |PROGRAM| DATA |SEARCE |ATC/APC] DATA | [EXTEND]
(F1 )(F2)(F3)(F4)(F5)(F6)(F7)(F8)
Fig. 3-1
Page 40
4194-E P-29 SECTION 3 TROUBLES AND TROUBLESHOOTING
< Contents of display >
AUTO OPERATION A. MIN ie) N 1 CHECK DATA 1/0 CHECK NO. 0 PAGE 1 1mm | | | ssoi 1/2 Indicates the screen Page number within title - I/O CHECK. the CHECK DATA ge station Displayed display screen pages 1/O number number Indicates page 1 in 2 pages.
lf an I/O bit is ON, the label section (9 characters) is highlighted. fet) : = Signal ON status ipAXSX : Signal OFF status At the bottom line in each column, the value of 8 bits of that column is displayed in hexadecimal. DATA=41H : BIT7 BIT6 BIT5 BIT4 BITS BIT2 BIT1 BITO
0 1 0 0 0 0 0 1 | J L |
4 1
(2) Checking the Input Signals
The procedure for checking the status of the proximity switch that checks the spindle tool clamp using the l/O CHECK screen is explained below as an example. Other input signals can be checked in the same manner.
From the Field Net input wiring diagram, supplied separately, it is found that the spindle tool clamp confirmation signal is input to check No. 29, bit 8.
So, display the CHECK DATA screen for I/O CHECK No. 29 and see the label “iISCL” of bit 8 of INPUT. When the label is highlighted, it indicates that the input signal is ON. Conversely, when the label is not highlighted, it indicates that the input signal is OFF.
If the spindle tool clamp confirmation input signal is OFF (label not highlighted) in the state the signal must be ON, the spindle too! clamp confirmation proximity switch will be faulty.