The text of a manual · part 1 of 5
CN9000 Series Miniature Microprocessor Temperature Controllers Operator's Manual, pages 1 to 9
Pages 1 to 9 of 45
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omega CN9122A
Page 1
!
ENGINEERING, INC
An OWEGA Group Company
LE cxs000 SERIES
MINIATURE
Cy-OMEGA
CONTROLLERS im MICROPROCESSOR e TEMPERATURE QC
Operator’s Manual
Page 2
TABLE OF CONTENTS CN9000 SERIES MINIATURE MICROPROCESSOR TEMPERATURE CONTROLLERS
SECTION PAGE SECTION 1 INTRODUCTION..................... 1 1 General Description... .........0 0.00.00 cece eee 1 1.2 Available Models... 0.0.0... 2.000. c eee eee ees 2 SECTION 2 INSTALLATION ..................... 5 21 Unpacking .. 0.0... ke ee ees 5 2.2 Mounting... 0.2... 0... eee ee eee eee 5 2.3 Wiring... 0... ee eee eens 7 2.4 Typical Wiring Diagrams... ... 2.2.2.0... 0.0000 eee 8 SECTION 3 OPERATION.....................005 9 3.1 General Considerations ............. 020000 eeae 9 3.2 Controls and Indicators ... 0.2... 0.0.2 ccc ee eee 10 3.3 Default (Pre-set) Settings ..................-2-00- 12 3.3.1 Changing Allowable Set Point Range ................ 12 3.4 Operation With Default Settings ................... 14 3.5 Parameter Adjustments ................0-.000000e 15 3.6 Examples of Parameter Adjustments ................ 25 3.7 Negative Temperature Ranging ..................-. 27 3.8 Parameter Lock... 2... 2... 2. ee ee ee 27 3.9 Fault Indication... 2.0... ee es 28 3.10 Calibration... 0. ee ees 28
Page 3
TABLE OF CONTENTS (cont‘d)
SECTION PAGE SECTION 4 TUNING .......................... 29 41 The Simplified Method..........0.0....... 0.00000. 29 4.2 Proportioning Time .........0.0.. 0.000. c eee eeeeee 31 4.3 Proportional Band ...........0.. 0.00000 cee eeee 31 4.4 Integral (Reset) Time ...................00.0000. 32 4.5 Derivative (Rate) Time ............... 0000 ce eee 32 4.6 Derivative Approach Control. .................005. 33 4.7 Heating and Cooling ............ 00.0.0. cece 34 SECTION 5 SPECIFICATIONS.................... 34
ADDENDUM A INTERNAL JUMPER CHANGES FOR 115/230 VAC AND 2-WIRE/3-WIRE
RTD CONVERSIONS .....................000005- 38 Al 115/230 Vac Conversion ......... 0.0.00 ce eee eee 39 A.2 2-Wire/3-Wire RTD Conversion .................00. 39 A.3 Installing the Triac Output, 4-20mA and 0-10Vdc Output Options .... 0.0.0.0... 0. cee eee eee eens 40
Page 4
SECTION 1 INTRODUCTION
11
GENERAL DESCRIPTION
The OMEGA® CN9000 Series Miniature Microprocessor Controllers are designed for accurate, precise temperature control. They feature high accuracy and reliability, and the sophisticated PID with approach control (PDPI) for optimal control during start-up and steady-state operation.
The CN9000 Series feature models with user selectable input type from eight thermocouple types or 2-wire RTD, or models with 3-wire RTD input. These units are °C/°F switchable, offer a0.1° resolution up to 200°, and the second set point and output are standard.
The CN9000 controllers are well suited to a broad range of applications, and are easy to install and operate. For most applications, the user need only select the desired input type by using the front pushbuttons. The CN9000 is pre-set for control parameters which are suitable for many applications. These pre-set (default) parameters can be changed by the operator at any time, to fine tune the controller to an individual process.
The CN9000 features advanced PDPI control, which enables the unit to suppress overshoot, and allows the process warm-up to be tuned independently from the steady-state operating conditions. For other processes, a user may select PID (Proportional- Integral-Derivative), PD (Proportional-Derivative), Proportional, or ON/OFF control.
Selection of all operational controls is made through the three keys on the front panel of the CN9000, with the display prompting the user for each step. After the parameters have been set, they can be locked-in by removing the jumper located under the front bezel. The user may select control mode and parameters, display resolution (1° or 0.1°) and units (°C/°F). An operator may also utilize a ranging feature of the instrument, which limits the range in which a set point may be chosen, or lock out a user from changing the set point.
Page 5
The second set point and output of the CN9000 rnay have proportional or on/off control, and the set point is set as a deviation from the primary set point. Cycle time, proportional band and on/off deadband are all set independently of the primary set point.
The CN9000 display has a large 3% digit green LED readout, with auxiliary indicators for output 1 and output 2, and three LEDs to indicate deviation from set point. The microprocessor, in addition to automatic processing of key calculations, holds the data in non-volatile memory, with the ability to retain data for up to 10 years with no power.
1.2 AVAILABLE MODELS Refer to Figures 1-1 and 1-2, and Tables 1-1 and 1-2. TABLE 1-1 HOW TO ORDER MODEL INPUT OUTPUT 1 OUTPUT 2 CN9111 Relay Relay CN9112 Relay Pulse CN9121 Thermocouple, Pulse Relay CN9122 2-Wire RTD Pulse ___ Pulse CN9131 1A Triac Relay CN9141 4-20mA Relay CN9151 0-10 Vdc Relay CN9211 Relay Relay CN9212 Relay Pulse CN9221 Pulse Relay CN9222 3-Wire RTD Pulse Pulse CN9231 1A Triac Relay CN9241 4-20 mA Relay CN9251 0-10 Vdc Relay
Page 6
OMEGA Model Number System
CN9
L
1 Thermocouple Input
2 Sire RTD SP2 (Output No. 2) input 1 3A Mechanical Relay* 2 SSD logic 5VDC 25 mA non- isolated SP1 (Output No. 1) 1 5A Mechanical Relay* 2 SSD logic 5VDC 25 mA non-isolated 3 1ASSR 4 4-20mA DC 5 0-10 VDC *Refer to Specifications
Figure 1-1. CN9000 Model Number System
Page 7
BDS0
1 Relay 3A 2 SSD 5VDC .1 Mechanical Relay 5A 2 SSD 5VDC 3 SSR1A 4 4-20 mA DC 5 0-10VDC Figure 1-2. Replacement Relay Boards TABLE 1-2 PLUG-IN OUTPUT BOARDS MODEL OUTPUT 1 OUTPUT 2 BD9011 Relay Relay BD9021 Pulse Relay BD9012 Relay Pulse BD9022 Pulse Pulse BD9031* 1 Amp Triac Relay BD9041* 4-20mA DC Relay BD9051* 0-10 Vdc Relay
* Requires that DB9021 is already installed in unit.
Page 8
SECTION 2 INSTALLATION
2.1
2.2
UNPACKING
Remove the packing list and verify that all equipment has been received. If there are any questions about the shipment, please call OMEGA Customer Service Department at (203) 359-1660.
Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take particular note of any evidence of rough handling in transit. Immediately report any damage to the shipping agent. NOTE
The carrier will not honor any claims unless all shipping material is saved for their examination. After examining and removing contents, save packing material in the event reshipment is necessary.
MOUNTING
The CN9000 is mounted in the panel through a 45 mm square Ye DIN 43700 cutout using the special mounting clip provided (refer to Figure 2-1).
The mounting clip should be pressed home until the rachet holds the unit firmly in place. If necessary, the mounting can be further tightened using the jacking screws.
To remove the unit from the panel, press the legs of the clips in op-posite directions to release the rachet.
NOTE
When mounting multiple units allow 3% inches from center to center of the unit in the vertical direction to allow for mounting bracket and wiring, and 2 inches in the horizonal direction for heat dissipation.
Page 9
dimensions in mm
(inches) [12.5]
45x45 +0.6 Fe
(1.77x1.77 49.026)
| 20 | (0.79)
buttons
© N © |2 39 <o PANEL = A | ' , e 7 _ @ |R CUT OUT ae fej |e 5 Sk on ae ee = ~ mounting standard clip socket max panel thickness, >]}<« - 13 (0.5) *To unplug socket, press in lock buttons and pull apart MOUNTING MULTIPLE UNITS +) 1.772 3% Fe if | <_ - ___ - _ 2, __»
Figure 2-1. Mounting and Cutout Dimensions