Manual · Omega
CN9000 Series Miniature Microprocessor Temperature Controllers Operator's Manual
Manual45 pagesPDF 1.2 MB
Operator's manual for the OMEGA CN9000 Series miniature microprocessor temperature controllers, including the CN9122 with two pulse outputs.
Covers · 1 model
The models it covers
Summary
What is in it
OMEGA operator's manual for the CN9000 Series 1/16 DIN miniature temperature controllers with thermocouple or RTD input. It lists the available models (including the CN9122 with pulse outputs) and plug-in output boards, then covers unpacking, panel mounting, wiring and typical wiring diagrams, front panel controls, default settings, parameter adjustment, parameter lock, fault indication and calibration, PID and PDPI tuning, specifications, and internal jumper changes for 230 Vac and 3-wire RTD.
Its parts
- Introduction
- Installation
- Operation
- Tuning
- Specifications
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
This is the OMEGA operator's manual for the CN9000 Series miniature microprocessor temperature controllers, covering the whole series, including the CN9122 that the site lists as CN9122A. It shows how to mount and wire the controller, run it on its default settings, change and tune its control parameters, read its fault codes, and convert the supply voltage or the RTD wiring with internal jumpers.
- What it is
- Miniature microprocessor temperature controller with PDPI control (PID with approach control) and a standard second set point and output p. 4
- CN9122 version
- CN9122: thermocouple or 2-wire RTD input; pulse outputs on both output 1 and output 2 p. 5
- Power
- 115 or 230 V, 50-60 Hz, 5 VA; factory set, changed by internal jumper p. 37
- Inputs
- Thermocouple types or 2-wire PT100 RTD, chosen from the front keys; 3-wire RTD by internal jumper change p. 11
- Pulse output
- Non-isolated 5 Vdc, 25 mA (SSD) for driving an external SSR p. 6, 38
- Display
- Green LED, 10 mm (0.4 in) high, 1 or 0.1° resolution; 3 LEDs show deviation from set point p. 39
- Accuracy
- 0.25% of range + 1°C (0.5°C in high resolution); 3 samples per second p. 38
- Relay versions
- SP1 relay 5 A at 250 V continuous, 10 A maximum; SP2 relay 3 A at 250 V continuous, 5 A maximum p. 37
- SP1 output options
- 1 A SSR (264 V, 100 VA max, SPST), isolated 4-20 mA (500 ohm max) or isolated 0-10 V (20 mA max), using the plug-in output power socket p. 38
- Plug-in output boards
- BD9011 relay/relay, BD9012 relay/pulse, BD9021 pulse/relay, BD9022 pulse/pulse; BD9031 1 Amp triac, BD9041 4-20mA DC, BD9051 0-10 Vdc p. 7
- Default settings
- Cycle time 30 s, proportional band 2.5% of full scale, derivative 25 s, integral 350 s; SP2 off p. 15, 38
- Size and weight
- 48 x 48 x 13 mm bezel, 115 mm depth behind panel; 45 mm square panel cutout; 380 g p. 41
- Ambient temperature
- 5 to 49°C (40 to 120°F) p. 40
- Noise suppression kit
- OMEGA part no. 1821-101 for 115 Vac (RC network or MOV) p. 12
What this manual walks you through
- Mounting the controller in the panel with the mounting clip p. 8, 9
- Wiring power and outputs to the terminals p. 10
- Wiring thermocouple and RTD inputs p. 11
- Wiring a heater with alarms, or heating and cooling p. 11, 12
- Running the controller on its default settings p. 15, 16, 17
- Changing the allowable set point range p. 15, 16
- Reading fault codes p. 31
- Setting the display bias p. 31
- Settings for heating and cooling systems p. 37
- Converting between 115 and 230 Vac, or 2-wire and 3-wire RTD p. 41, 42
Good to know
- The controller is not designed for field calibration; display bias shifts the whole curve and is not a true calibration. p. 31
- Converting to a 3-wire RTD prevents later use of thermocouples. p. 42
- The voltage and RTD jumper changes should be made only by a qualified technician. p. 41
- Relay life drops if run continuously near the maximum current, so the working ratings are 5 A for SP1 and 3 A for SP2. p. 37
- A set point keyed outside the allowed range is held at the end of the range. p. 16
Questions this manual answers
What should I do when the CN9000 shows EE1?
EE1 means sensor burnout: check the sensor and its connections, then press the * key. p. 31
What do the EE fault codes on the CN9000 mean?
EE1 is sensor burnout, EE2 a temporary system error that clears itself, EE8 loss of calibration, and EE9 a non-volatile memory data fault. p. 31
Does the CN9122 have relay outputs?
No. Table 1-1 lists the CN9122 with pulse outputs on both outputs; the pulse output is a non-isolated 5 Vdc signal for driving an external DC SSR. p. 5, 10
How do I change a CN9000 from 115 Vac to 230 Vac?
On the analog PCB, remove jumpers 3 and 5 and fit solder jumper 4; the manual says only a qualified technician should do this. p. 41, 42
What panel cutout does the CN9000 need?
A 45 mm square cutout; the controller is held in by the mounting clip supplied. p. 8
The whole text · 5 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file