The text of a manual · part 3 of 5

CN9000 Series Miniature Microprocessor Temperature Controllers Operator's Manual, pages 19 to 27

Pages 19 to 27 of 45

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omega CN9122A

Page 19 read from a scan by OCR; it may hold reading errors

PARAMETER NUMBER

4.

10.

11.

12.

13.

DESCRIPTION

SP1 Proportional Time, Total length of time that the output will cycle on and off when the temperature is within the proportional band. This can also be set for ON/OFF Control. Note that cycle times of less than 10 seconds are not recommended for use when SP1 is a mechanical relay. The 0.05 second time should only be used with analog outputs (4-20 mAdc or 0-10 Vdc) which will be available at a future time.

SP1 Proportional Band, This is the percent of the Span (allowable set point range) (linearized range) both below and above set point in which proportion action is active. Output is 100% at the bottom of the proportional banc!, 0% at the top, and proportional in between. If ON/OFF Control was selected (Function 4, Option 7), then this selection represents deadband (hysteresis), or the amount the temperature must fall after reaching set point before the relay returns to original state.

SP1 Derivative Time, Also known as rate. Refer to paragraph 4.5. Set to OUT (Option 1) if Proportional only Control is clesired.

SP1 Derivative Approach Control, Used to eliminate derivative action during system warm-up time. Refer to paragraph 44.6.

SP1 Integral Time, Also known as reset. Refer to paragraph 4.4.

Display Bias, Factory calibration. No adjustment required.

SP2 Proportional Time, Cycle time for second set point. Set similar to first set point (Function 4). Note that SP2 must be activated in (Function 19). Pre-set default setting for SP2 is ON/OFF.

SP2 Proportional Band, Set similar to first set point proportional band (Function 5).

Error Indication Resolution, Allows adjustment in the indication of the deviation from set point.

Not used. 16

Page 20 read from a scan by OCR; it may hold reading errors

PARAMETER NUMBER

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

DESCRIPTION

Derivative Polling Ratio, Allows adjustment of the frequen-cy at which the controller checks the derivative function. This should not have to be adjusted from the Default value (0.5 x Derivative Time) for most processes. Not applicable if SP1 derivative is not used.

Reset All Functions To Default, Allows quick reset of all functions to Default settings. Only Function 22 (C/F) will not be reset.

Sensor select, Selects thermocouple type or RTD. This is the first selection that must be made for unit to be used. Note: if 3-wire RTD configuration is ordered, then PT100 (Option 9) must be selected.

Negative Temperature Ranges, Must be enabled to allow negative temperatures to be measured (using either T thermocouple or RTD only).

High Resolution, Allows selection of 0.1° resolution over limited temperature range ( - 99.9 to 199.9).

SP2 Operating Mode, Allows for activation of second set point. See SP2 Operation Table, 3-6. Note that in ON/OFF mode SP2 acts as a deviation alarm from the first set point. Itcan be set as a high deviation, low deviation, or either high or low deviation (out of bounds).

SP1 Sensor Burnout Protection, Allows for selection of upscale or downscale thermocouple break protection for first set point so that output will be in safest state if inputis lost. Most heating applications require upscale protection.

SP2 Sensor Burnout Protection, Allows for selection of upscale or downscale protection for second output.

°C/°F, Allows selection of °C or °F for display. Note that correct bezel must be used.

Not used.

7

Page 21 read from a scan by OCR; it may hold reading errors

FUNCTION OPTION

TABLE 3-4

FUNCTIONS AND OPTIONS

NUMBER NUMBER NOTE: For each Function, 0 is the Default Setting.

1

% of span

Adjusting offset. Key in correction (in degrees)

Key in setting (from SP1) in degrees

- oO

“ Aah w Ny hWN-Oo

PARAMETER

Manual Reset +1° steps Range:

Prop Band + 2 (max 99°)

SP2 Adjust

1° steps

Range:

0° to 99°

{inoperative until Option selected at Function 19)

SP1 Lock Unlocked Locked

SP1 Prop Time

30 sec

1 sec (not recommended with mechanical relay)

5 sec (not recommended with mechanical relay)

10 sec

20 sec

60 sec

0.05 sec (for use with the 0-10V or 4-20 mA output options)

ON/OFF

SP1 Prop __ Hystersis Band (Dead Band) 2.5% 1.25% 0.5% 0.25%

1% 0.5%

2% 1.0%

3% 1.5%

18

Page 22 read from a scan by OCR; it may hold reading errors

FUNCTION NUMBER

5 (cont'd)

TABLE 3-4 (cont’d) FUNCTIONS AND OPTIONS

OPTION NUMBER

NOOR WON - OO OohwWNn OO NO Oo

NOOR WN - OO

PARAMETER

SP1Prop __ - Hystersis

Band (Dead Band}

5% 2.5%

10% 5.0%

20% 10.0%

PD, P mode: Max 255° (25.5° in Hi-Res); PID mode: Max. 127° (12.7° in Hi-Res)

SP1 Derivative Time 25 sec

OUT

5 sec

10 sec

50 sec

100 sec

200 sec

SP1 Derivative Approach Control

1.5(x) Prop Band

0.5

SP1 Integral Time 350 sec

OUT

25 sec

50 sec

100 sec

200 sec

600 sec

1000 sec

19

Page 23 read from a scan by OCR; it may hold reading errors

FUNCTION NUMBER

9

10

11

% of span

12

13

TABLE 3-4 (cont'd)

FUNCTIONS AND OPTIONS OPTION PARAMETER NUMBER to

NOOR WNH+O N omhwW, Display Bias (not required in normal operation, refer to paragraph 3.10 Calibration)

SP2 Prop Time

ON/OFF

1 sec (not recommended with mechanical relay)

5 sec (not recommended with mechanical relay)

10 sec

20 sec

60 sec

0.05 sec (for use with the 0-10V or 4-20 mA output options)

30 sec

SP2 Prop _ - _ - Hysterisis Band (Dead Band) 2.5% 1.25% 0.5% 0.25% 1% 0.5%

2% 1.0%

3% 1.5%

5% 2.5% 10% 5.0% 20% 10.0%

PD, P mode:Max 255° (25.5° in Hi-Res); PID mode: Max 127° (12.7° in Hi-Res)

Error Indication Resolution Normal (2% x FS per segment) High (1% x FS per segment) Low (4% x FS per segment)

Spare

20

Page 24 read from a scan by OCR; it may hold reading errors

TABLE 3-4 (cont'd)

FUNCTIONS AND OPTIONS FUNCTION OPTION PARAMETER NUMBER NUMBER 14 ; Derivative Polling Ratio (@) 0.5x Derivative Time 1 0.2x Derivative Time 2 0.7x Derivative Time 3 1.0x Derivative Time 15 Reset all Functions to Default (@) Normal 1 Reset

NOTE: The selection of Option 1 at Function 15 will return all settings to Default except for the selection of °C or °F and Display Bias.

16 (6) 1 2 3 4 5 6 7 8 9 17. 0 1 18 0 1 19 0 1 2 3

Sensor Select None. Controller inoperable.

Negative Temperature Ranging Disabled Enabled

High Resolution

Normal

Hi-res ( - 99.9 to 199.9) Settings in 1° increments become 0.1° increments in High Resolution.

SP2 Operating Mode OUT

High (above SP1) Low (below SP1)

Out of limits 21

Page 25 read from a scan by OCR; it may hold reading errors

TABLE 3-4 (cont'd)

FUNCTIONS AND OPTIONS FUNCTION OPTION PARAMETER NUMBER NUMBER 20 SP1 Sensor Burnout Protection fe) SP1 output OFF (UPSCALE) 1 SP2 output ON (DOWNSCALE) 21 SP2 Sensor Burnout Protection 0 SP2 output OFF (UPSCALE) 1 SP2 output ON (DOWNSCALE) 22 °C/°F 0 °C 1 OF 23 1 Version No. (factory set) TABLE 3-5

LINEARIZED SENSOR RANGE TABLE

DEFAULT RANGE LINEARIZED FLANGE OPTION SENSOR °C oF °c °F NO. TYPE MIN MAX MIN MAX MIN MAX MIN MAX

1 J Oo 400 32 800 0 800 32 1470 2 K Oo 400 32 800 ie) 120032 1999 3 N O 400 32 800 0 1200 32 1999 4 R O 1600 32 1999 0 1600 32 1999 5 Ss O 1600 32 1999 0 1600 = 32 1999 6 T QO 250 32 500 -90 250 ~-130 480 7 E oO $00 32 1000 0 600 32 1110 8 J-DIN OQ 400 32 800 ce) 800 32 1470 9 PTI0O0 O 200 32 400 -90 400 _ -130 750

NOTE: Range adjustments (including Default) only limit set point values. Process temperatures will be displayed over the full linearized range.

22

Page 26 read from a scan by OCR; it may hold reading errors

SP2 OPERATION

TABLE 3-6

Operating Mode

Control Mode| ‘Function 19) | sp2Relay | SP2LED | ,, Typical (Function 10) etting Is Energized Is On xamples 0} Compared Use to SP 1 High i Below Above Deviation “Opten | SP2 Setting SP2 Setting Alarm High ON/OFF (Below SP1) Above Below Deviation Option 2 SP2 Setting | SP2Setting | Alarm Low (Option 0) Out of Limits Within Set Outside Set Deviation (About SP1) Band Around | Band Around Alarm Option 3 SP1 Setting | SP1 Setting High & Low High F Above Above SP2 Proportional | emo t | SP2Setting | SP2Setting | Cooling : Low Below Below SP1 Cooling OPT ons ef) eon 2 | SP2Setting | SP2Setting | SP2 Heating

23

Page 27 read from a scan by OCR; it may hold reading errors

TABLE 3-7 MAKING PARAMETER ADJUSTMENTS

STEP ACTION DISPLAY

1 Ensure that the jumper behind the lower front bezel is in the Parameter Setting Position (see Parameter Lock, paragraph 3.8).

2 To convert main display from temperature read-out into FUNCTION and OPTION listing mode: PRESS P 3 FUNCTION numbers Clalalts} appear to the right of, and OPTION numbers to the left of, the floating decimal point, starting with FUNCTION 3. OPTION O

The FUNCTION listing has been arranged to give easiest access to those which are almost frequently FUNCTION 3 used. (FLASHING)

When indexing in a positive (A) direction, FUNCTION 23 is followed by FUNCTION 3.

FUNCTIONS 2 and 1 can be accessed from FUNCTION 3 by indexing in a negative ( ¥) direction. FUNCTION 1 is followed by FUNCTION 12.

24