CN9000 Series Miniature Microprocessor Temperature Controllers Operator's Manual, pages 10 to 18
Pages 10 to 18 of 45
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omega CN9122A
Page 10
2.3
WIRING
The CN9000 operates on either 115 Vac +15%, 50-60 Hz (std) or 230 Vac +15%, 50-60 Hz (selectable by changing internal jumper, refer to Addendum A). See Figure 2-2. The CN9000 Series feature (for SP1 or SP2) either the standard mechanical relay outputs or the optional non-isolated 5 Vdc pulse output (designed for operating an external DC SSR such as an OMEGA SSR240D10, SSR240D25, or SSR240D45). Three other optional outputs are available for SP1, using a plug-in output power socket (provided). These outputs are, a 1A SSR, Oto 10 V, or 4to 20mA output. 115 VAC 50-60 HZ 9 10 #4 1 2 1 ASSR, MECHANICAL RELAY | N.O. C. NC. tL oN 0-10V, 4-20 mA, SSd (PULSE) |, +
SSd(PULSE)} +, MECHANICAL RELAY | N.C. C. NO.
8 7 6 5 43
Ur
Figure 2-2. Wiring Connections
TERMINAL DESIGNATIONS
Controller Power 115 Vac (230 Vac optional) Controller Power Neutral
RTD (third wire) Thermocouple ( - ) or RTD Thermocouple (+) or RTD
SP2 Mechanical! Relay Normally Open (N.O.) SP2 Mechanica! Relay Common (C.); or 5V Pulse ( - ) SP2 Mechanical Relay Normally Closed (N.C.); or 5V Pulse (+)
-_
“Selman oiaaewln-
SP1 Mechanical Relay N.O.; 1 A SSR N.O.; 5V Pulse ( - ); O-10V (--); or 4-20 mA ( - ' SP1 Mechanical Relay C.; 1 A SSR C; 5V Pulse (+); O-10V (+); or 4-20 mA (+) SP1 Mechanical Relay N.C.; or 1 A SSR N.C.
7
Page 11
Check side label for supply voltage.
Thermocouple types J, K, T, E, R, S, N, J DIN, and PT100 RTD (2-wire) are selectable via the keys on the CN900C front panel (refer to Figure 2-3 for input wiring configurations). 3-wire configuration is available by internal jumper change (refer to Addendum A).
Connections for Connections for
Connections for Thermocouple 2 wire PT100/RTD 3 wire PT100/RTD ok I a oe
Figure 2-3. Thermocouple and RTD Input Wiring
2.4 TYPICAL WIRING DIAGRAMS
Figures 2-4 and 2-5 illustrate typical wiring of the CN9000 Controllers.
230/115V + 15% 50~60Hz ' 10A(max)
LOAD, - > LOW ALARM OR WITHIN LIMITS SIGNAL, - - - - * HIGH ALARM OR OUT OF LIMITS SIGNAL
Figure 2-4. Wiring Heater with Alarms
Page 12
TYPICAL WIRING & FAST BLOW FUSE N 230/115V_+ 15% 50 - 60Hz SSR output SP1 4 1
LI DC INPUT SSR
LOAD
' SOLENOID 5A (max) VALVE if q
' COOLING WATER
Figure 2-5. Heating and Cooling
NOTE
The CN9000 Series has been designed to be as im-mune as possible to electrical interference. However, electrical noise suppression may be required in some applications, particularly if the output of the controller is firing a contactor or coil. A noise suppression kit is available for use with 115 Vac, OMEGA part no. 1821-101 (consists of an RC network or metal oxide varistor (MOV).
SECTION 3 OPERATION
3.1
GENERAL CONSIDERATIONS
The CN9000 is pre-set for control parameters that are suitable for many applications. The CN9000 can be operated with the default (pre-set) settings, or the default settings can be overridden by more appropriate control modes and parameters and/or enabling of the second set point, by programming the CN9000 through the front panel keys. Refer to Table 3-1 Controls and Indicators and Table 3-4 Functions and Options.
Page 13
3.2
CONTROLS AND INDICATORS
Figure 3-1 and Table 3-1 illustrate the controls and indicators of the CN9000 Series Controllers.
Figure 3-1. Controls and Indicators
TABLE 3-1
CONTROLS AND INDICATORS
ITEM CONTROL/INDICATOR FUNCTION
1
LED Display
The four-digit display norrnally shows process temperature to 1°C or Fandin high resolution (up to 200°) 0.1°C or F. The display also shows the set point value (flashing) and the FUNCTION and OPTION list when in the Set-Up Mode (for changing default parameters). Functions are the available controller facilities (eg., Derivative); Options are the available values for each Function (eg., Derivative value, 50 seconds). When in the Set-Up Mode, the Function numbers are on the right and the Option numbers are on the left of the floating decimal point.
10
Page 14
2
3
4
5
TABLE 3-1 (cont’d) CONTROLS AND INDICATORS
ITEM CONTROL/INDICATOR FUNCTION
Error Indicator
SP1 Output Indicator
SP2 Output Indicator
Control Keys
These three LEDs display the difference between set point and process tem- peratures in five steps, each one repre- senting 2% of full scale value. Flashing >3% above set point Steady 1%-3% above set point Steady +1% about set point Steady 1%-3% below set point Flashing > 3% below set point The error indicator can also be used in high resolution, +1% steps or low res- olution, +4% steps.
This LED is illuminated (green) when SP1 output ON.
lHluminated SP2 output ON or OFF de- pending on mode of operation (amber). Refer to Table 3-6, Set Point 2 Opera- tion.
% When pressed displays main set point (SP1) temperature.
* A Keyed together increases main set point temperature.
* ¥ Keyed together decreases main set point temperature.
p Selects Set-Up Mode (entry to Function and Option List, see Table 3-2). Display flashes, normal control maintained.
AY When in Set-Up Mode, indexes FUNCTION/ OPTION number up or down in single digits.
*% When in Set-Up Mode changes manipulation from Functions to Options and vice-versa.
a
Page 15
3.3
3.3.1
DEFAULT (PRE-SET) SETTINGS
For ease of use in normal applications, the CN9000 has been pre-set with factory, or DEFAULT, settings in place of customer options. (To change parameters refer to paragraph 3.5 and Table 3-4.)
These pre-set parameters enable the instrument to operate in PID Control Mode, with a single set point and slow cycle relay output. This configuration should give good results where the heater is adequately rated and the control sensor is sited reasonably close to it.
Default settings (for SP1 only) are:
Proportional Time (Cycle Rate) = 30 seconds Proportional Band (Gain) = 2.5% of Default full scale Derivative Time (Rate) = 25 seconds
Integral Time (Reset) = 350 seconds
To use the controller with default settings requires only that the Option number of the sensor, selected from Table 3-2, Sensor Default Set Point Range Table, be keyed into the instrument. Also, check that the instrument is set to either °C or °F, as desired. (Refer to paragraph 3.5 and Table 3-4.) Also check that the desired control temperature is within the set point Default range (see the, following).
To operate unit:
Apply power. All L.ED segments will be briefly illuminated during the self-check routine, then the display will request sensor selection (from Table 3-2), i.e., the Option number for Function 16, and will not respond to any further instructions until this is made.
Changing the Allowable Set Point Range
The Default Range will limit the set point values only. The instrument will indicate process temperatures over the full linearized range shown in Table 3-5. The Default set point full scale {automatically selected by choice of sensor) may be altered to any value within the linearized band (Table 3-5) by using the following procedure: 12
Page 16
1. Press P (use blunt-pointed tool-P is a recessed button) once and release.
Press P again and hold.
Press *% and hold.
Release P (hold x). Default full scale flashes on display. . Press either A or ¥ to adjust full scale value.
Release A or V.
Release x.
. Repeat steps 1-4 to view new full scale value.
© ON anr WN
Adjust set point to desired value.
Ensure that the set point range maximum is com-patible with safety requirements.
NOTE If an attempt is made to set the set point outside of the set point range, the set point will be at the end of the range.
TABLE 3-2 SENSOR DEFAULT SET POINT RANGE TABLE Option Type Min/Max °C ‘°F 1. J lron-Constantan 0-400 32-800 2. K Chromel-Alumel 0-400 32-800 3. N Nicrosil-Nicrosil 0-400 32-800 4. R Pt/Pt-13% Rh 0-1600 32-1999 5. S Pt/Pt-10% Rh 0-1600 32-1999 6. T Copper-Constantan 0-250 32-500 7. E Chromel-Constantan 0-500 32-1000 8. J DIN 0-400 32-800 9. PT100 RTD 0-200 32-400
Note: if the Default set point range maximum is not suitable, it can be increased or decreased to any desired value within the linearized band.
13
Page 17
3.4 OPERATION WITH DEFAULT SETTINGS Refer to Table 3-3 for operation of the CN9000 with the Default settings. TABLE 3-3 OPERATION WITH DEFAULT SETTINGS STEP ACTION DISPLAY 1 Install Unit. Power on. * Note: digits shown [ ole}
Check that display reads: bold are flashing |
2 To key in the selected sensor type. Example: OPTION 2, K-Type Heiile thermocouple: PRESS A TWICE Check that display reads:
3 To enter the selected
1 thermocouple type into memory: PRESS P ONCE OU) The display now reads sensor Temperature®, eg. Ambient (18°C).
4 To key in the set point value: PRESS * and HOLD To increase the set point: PRESS A Oo To decrease the set point: PRESS ¥ It should be noted that the digit rollover rate increases (ie. SHEC accelerate). eg. Set Point 250°C.
When the keys in (4) above are released the unit will operate as a normal temperature controller. The square LED, is illuminated, showing that SP1 output is energized. To view the set point temperature: PRESS * To adjust the set point value at any time: REPEAT STEP 4
Should a particular application require the use of additional features, for example: second setpoint output or High Resolution, refer to Paragraph 3.5. PARAMETER ADJUSTMENTS.
This also applies where the Default settings prove to be unsuitable. The CN9000 can be tuned for optimum performance by the adjustment of contra! parameters.
If guidance is needed to establish the appropriate settings, refer to Section 4: TUNING. 14
Page 18
3.5 PARAMETER ADJUSTMENTS
To change the CN9000’s Default parameters to new parameter settings refer to Tables 3-4 through 3-8. All adjustable parameters are held in memory.
NOTES
Because the selection of high resolution (Function 18 Option 1), °C/°F selection (Function 22), and set point range adjustments influence the values of other settings and can have a fundamental effect on control characteristics, it is important that, when required, they should be made during initial set-up to avoid the need for re-tuning.
If the temperature scale is changed, it is essential to change the upper bezel to correspond to the scale selected.
The following gives a description of the adjustable parameters listed in Table 3-4.
PARAMETER NUMBER
1.
DESCRIPTION
Manual Reset, If the CN9000 is used in Proportional only (P) or Proportional-Derivative without Automatic Reset (PD), the system is offset by altering, digitally, the amount of the offset in +1° steps, up to half of the proportional band or +99°, whichever is smaller.
SP2 Adjust, Deviation from first set point in 1° steps, up to 99° (9.9° in high resolution). The second set point tracks the first set point. Therefore, if the first set point is changed, the second set point changes along with it.
SP1 Lock, Allows the first set point to be locked to keep it from being changed inadvertently. This is the Function that the unit starts with when Parameter (P) key is first pressed.
1S