CN9000 Series Miniature Microprocessor Temperature Controllers Operator's Manual, pages 28 to 36

Pages 28 to 36 of 45

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omega CN9122A

Page 28 read from a scan by OCR; it may hold reading errors

TABLE 3-7 (cont’d) MAKING PARAMETER ADJUSTMENTS

STEP ACTION DISPLAY

3 To index sequentially. The FUNCTION digit(s) will flash indicating that the FUNCTIONS can be indexed sequentially from 3 to 23 enabling previously entered or Default

OPTIONS to be viewed: PRESS AORY lofeii72) eg. FUNCTION 12 OPTION 2. 4 To alter an OPTION: PRESS * oan

To cause the flashing of the display to shift from the FUNCTION column to the OPTION column to the left of the decimal point. Note that it is the flashing digit(s) that can be altered.

To change OPTION number: PRESS AAA Osin 2) OR PRESS ¥ Li4I)2) To return to FUNCTION indexing: PRESS * Li4)i2}

When all required OPTIONS have been selected for each FUNCTION, to place in memory and commence control under the new instructions: PRESS P (THE|MIP)

3.6 EXAMPLES OF PARAMETER ADJUSTMENTS

Refer to Table 3-8 for examples of parameter adjustments for the CN9000 Controller.

25

Page 29 read from a scan by OCR; it may hold reading errors

TABLE 3-8 EXAMPLES OF PARAMETER ADJUSTMENTS

STEP ACTION DISPLAY

A. CHANGING SP1 PROPORTIONING TIME To change SP1 proportioning time from 30 secs (Default setting) to 20 secs: FUNCTION 4: Change OPTION 0 to OPTION 4

1 To display OPTION/FUNCTION List: PRESS P [_Tollol[3) Ensure that link behind lower bezel is in ‘unlocked’ position.

2 To index the FUNCTION number to 4: PRESS & [ Jojolf4] 3 Change to OPTION numbers: PRESS * Cole) 4 To alter OPTION number 0 to

OPTION number 4: PRESS AAAS Toei) 5 To place in memory: PRESS P (TIEIMP]

B. USE OF MANUAL RESET

P and PD mode. When the system has settled, if a discrepancy exists between Set Point and Process Temperature, the ‘offset’ can be re-moved by the use of Manual Reset. For example, if the process temperature is 252°C and the set point is 250°C

Process temperature is, aeGe) 1 To view the set point . temperature: PRESS * SBEC)

2 To correct ‘offset’ of -2°C, Display shows FUNCTION 3,

OPTIONO: PRESS P [_lalfal3} 3 To index to FUNCTION 1: PRESS Y ¥ {Tole} 4 Change to OPTION numbers flashing: PRESS * [lolol 5 To key in the ‘offset’ .

temperature ( - 2°C): PRESS ¥ ¥ oli) 6 To place in memory: PRESS P 2512)

The process temperature reading will settle from 252°C to 250°C. (Jalil)

26

Page 30 read from a scan by OCR; it may hold reading errors

3.7

3.8

NEGATIVE TEMPERATURE RANGING

The following sensor types can be used for negative temperatures. The negative value shown against each type is automatically set by the choice of sensor (Function 16) and requires enabling with Function 17, Option 1.

Type T; -90°C,, 130°F

PT100: -100°C, -148°F

TypeN: - - 50°C,, 58°F non-linearized Type K: - - 50°C,, 58°F non-linearized

PARAMETER LOCK

The chosen parameters may be permanently locked into memory by removing or altering the position of the jumper behind the lower front bezel (see Figure 3-2). Note that locked positions (2) and (3) are alternatives and that the jumper socket is in the ‘‘inactive’’ position in (2). NOTE It is important to switch off briefly after changing jumper position.

When the parameter lock has been applied, only the Set-Up adjustments listed below are possible (depress the P key):

1. Adjust manual reset (PD, P and ON/OFF modes only), see Table 3-8 for key sequences.

2. Adjust the second set point (assuming Function 19, either Options 1, 2 or 3 have been selected).

3. Lock the main set point to prevent adjustment by the operator.

Parameter Setting Position (1) Locked Position (2) Locked Postion (3)

Figure 3-2. Parameter Lock Positions 27

Page 31 read from a scan by OCR; it may hold reading errors

3.9

3.10

FAULT INDICATION

Depending or the selection made at Functions 20 and 21, the SP1 and SP2 outputs are turned ON or OFF if sensor is open. The main temperature display, on a fault indication, is replaced by ‘‘EE"’ flashing, followed by a digit. This indicates that an error has been detected in the system. Action should be taken as follows:

EE1 Sensor burnout. Check sensor and/or connections, then key *.

EE2 Tempcrary System Error. Self clearing.

EE8 Loss of calibration. Contact the OMEGA Customer Service Department at (203) 359-1660.

EE9 Non-volatile memory data fault. Contact the OMEGA Customer Service Department at (203) 359-1660.

CALIBRATION

The CN9000 is not designed to allow field calibration.

Aone point ‘‘Display Offset’’ can be programmed from the front of the unit using Function 9 (Display Bias). This function should not be used in normal operation.

Display Bias can be used to correct for small errors in calibration of a particular thermocouple or the CN9000. It should never be used as a fudge factor to account for temperature gradients ina system.

Note that this is not a true calibration since the entire curve is shifted, and although the unit can be recalibrated at one point, the reading can be off at another temperature since the temperature curve is not exactly linear. Therefore, the Display Bias should be attempted as close to the desired set point temperature as possible.

To set up Display Bias: 1. Power up instrument and allow at least 30 minutes warm-up time.

2. Key into Function 9 as normal. 3. Press * and hold.

28

Page 32 read from a scan by OCR; it may hold reading errors

4. Press AY. Release x, and A ¥ together.

6. Enter Bias Value in (+) or ( - ) 0.1° increments in Function 9, in normal manner, up to a maximum of 12.7°. (Note that the increments are in °C or °F depending on Function 22 setting.)

7. Press P.

8. Check that the Bias Value has been entered correctly by checking Function 9.

a

NOTE In later units, it is no longer required to perform steps 3, 4and 5; however, if said steps are performed, unit will still function properly.

SECTION 4 TUNING

411

THE SIMPLIFIED METHOD

If the pre-set PID Default values prove to be unsuitable for a particular application, the following method can be used to establish new settings which should be acceptable and which can be adjusted to give optimum control. Other methods may also be used, tuning is a trial and error process.

The first step is to control the system with the instrument in ON/OFF mode and use these results to calculate the new parameter values for SP1.

Check that all settings are in Default. If required, range adjustments should be made first (refer to paragraph 3.3).

Check that the Parameter Lock is in the Parameter Setting Position (see Figure 3-2) and proceed as follows:

1. Adjust Proportioning Time to ON/OFF. (This switches off all other control terms and sets Hysteresis to 1.25% of full scale.)

2. Key in set point temperature.

3. Switch ON and allow process to stabilize. Monitor process temperature, ideally using a chart recorder, or alternatively by taking readings from the display at regular intervals, as frequently as possible. The results should look similar to Figure 4-1.

29

Page 33 read from a scan by OCR; it may hold reading errors

amplitude

Figure 4-1. Simplified Tuning Method

4. Using the figures obtained for the oscillation period (T) seconds and amplitude (A) degrees (see Figure 4-1), the following parameter values can be calculated:

a. Proportional Time = T If 10 seconds or less use 20 the pulse output module.

b. Proportional Band % = Ax1.5x100 Settonext full scale LARGER

% setting. c. Derivative (Rate) Time = T Set to next 10 SHORTER setting.

d. Integral (Reset) Time = T Set to next LONGER time setting.

NOTE

Approach control will be activated in DEFAULT setting = 1.5 x prop. band. If the warm up characteristic is unacceptable, refer to paragraph 4.6.

5. Enter these new values and restart the process from cold.

The above settings can be further adjusted to give optimum performance. Paragraphs 4.2 through 4.7 will provide guidance for tuning the individual control terms.

30

Page 34 read from a scan by OCR; it may hold reading errors

4.2 PROPORTIONAL TIME

The Proportional Time setting determines the cycle rate of the output device. In the interest of long contact life, this should be the slowest (longest setting) possible if mechanical relay output is being used. Otherwise there is no disadvantage in using faster settings. See Figure 4-2.

ideat Setting Setting Too Long

Figure 4-2. Proportioning Time

4.3 PROPORTIONAL BAND

This term is employed to smooth out the oscillating control characteristic typical of ON/OFF control.

A feature of proportional control is that the system may run at a slightly different temperature to the set point (Offset), and have a slower reaction to disturbances. See Figure 4-3.

Setting too narrow Setting Ideal Setting too wide slow system oscillates warm up and poor control

Figure 4-3. Proportional Band

31

Page 35 read from a scan by OCR; it may hold reading errors

4.4

INTEGRAL (RESET) TIME

The purpose of the integral term is to automatically correct for offset errors caused by the introduction of Proportional control. If incorrectly set, this can cause instability or increase warm up time.

If the Integral Time (constant) is too long, the process will take a long time to return the temperature to the set point. Conversly, if the Integral Time is too short, the process temperature oscillates because the integral action outruns the process. See Figure 4-4.

Setting too short Ideal setting Setting too long

4.5

Figure 4-4. Integral (Reset) Time

DERIVATIVE (RATE) TIME

Derivative enables the controller to shift the proportional band up or down in an amount proportional to the rate of temperature change to help the system compensate for rapidly changing temperature.

The derivative term is added to Proportional Control action to speed up response to disturbances and to suppress overshoot. In applications where these two requirements would need different settings, the use of Derivative Approach Control for adjusting warm-up characteristics allows the Derivative setting to be biased in favour of disturbance behaviour. See Figure 4-5.

32

Page 36 read from a scan by OCR; it may hold reading errors

Setting too long Ideal setting Setting too short

Figure 4-5. Derivative (Rate) Time

4.6 DERIVATIVE APPROACH CONTROL

This feature allows the warm-up characteristics to be tuned separately from normal running conditions and is particularly useful for applications where the sensor is some distance from the heater. The setting determines where the derivative action starts with respect to set point. The smaller the setting, the closer to set point. See Figure 4-6.

Setting too small Setting ideal Setting too large

Figure 4-6. Derivative Approach Control Where a given application cannot be tuned to give acceptable results over the required range of process temperatures and conditions, it is possible that better results may be obtained with Proportional, Derivative and Approach Control terms only.

33