The text of a manual · part 5 of 5
CN9000 Series Miniature Microprocessor Temperature Controllers Operator's Manual, pages 37 to 45
Pages 37 to 45 of 45
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omega CN9122A
Page 37
4.7
HEATING AND COOLING GENERAL CONSIDERATIONS
Ideal settings for these systems are very dependent on the application, and are often best determined by experiment.
The following general points may prove useful for initial consideratian:
1.
A common characteristic is that there is a considerable difference between the system response to the input of heating and of cooling energy.
In general, both channels can be set independently using the tuning guidelines for settings for Proportioning Time and Proportioning Band, and where it is known that one channel has a dominating and rapid effect on system temperature, the employment of narrow hysteresis ON/OFF settings for this may give excellent results.
Where both set points are required to be set close together (small deadband), wide proportioning or hysteresis band settings will overlap allowing simultaneous operation of outputs, which may give the best overall control.
SECTION 5 SPECIFICATIONS
POWER: Dual 115/230 V +15% 50-60 Hz 5VA, factory set, jumper changeable
OUTPUT MODULES DUAL OUTPUT (STANDARD): SP1 Relay, SPDT relay, rated 5 A at
250 V continuous use, 10 A at 250 V maximum; SP2 Relay, SPOT relay, rated 3 A at 250 V continuous use, 5 A at 250 V maximum
NOTE
Although $P1 relay is capable of handling a current of 10 A and SP2 a current of 5A, the life of the relays will be considerably reduced if the controller is used con-tinuously (24 hours/day) at or near 10 A (SP1) or 5 A (SP2)
Using the controller in an elevated ambient temperature, or with a slightly inductive load, also derates the relays. Therefore, the rating of SP1 is 5 A and SP2 is 3A.
34
Page 38
SPECIFICATION (cont‘d)
OPTIONAL OUTPUTS FOR SP1 & SP2:
PULSE OUTPUT (SSD): Non-isolated 5 Vdc for driving external relay FOR SP1 ONLY (USING PLUG-IN OUTPUT POWER SOCKET, SUPPLIED)
SSR: 1A/264V 100 VA max, SPST
4-20 mA: Isolated, 500 Qmax.
0-10 V: Isolated, 20 mA max.
ACCURACY & RANGES
CALIBRATION ACCURACY: + 0.25% of range +1°C (+0.5°C in Hi-res)
CONTROL STABILITY: Typically +0.15% of full scale, dependent on application
MAIN TEMPERATURE SET POINT (SP1): See Table 5-1
FULL SCALE (FS): See Table 5-1
SAMPLING TIME: 3 samples per second. Re-zero of CJC and auto calibrate every 5 seconds
TEMPERATURE COEFFICIENT: < 150Oppm/°C of max. linearized range typical
REFERENCE CONDITIONS: 22°C +2°C, 115/230 V +15%, after 30 minutes settling time
SENSORS
INPUT TYPES: Thermocouple types J, K, E, R, S, N, J DIN, 2-wire Pt RTD, user selectable; 3-wire Pt RTD
EXTERNAL RESISTANCE (TC): 100 ohms max.
COLD JUNCTION COMPENSATION: 0.05°/°ambient typical BURNOUT PROTECTION: Fault display, upscale (downscale key selectable)
COMMON MODE NOISE REJECTION: 140 dB, 240 V, 50-60 Hz NORMAL MODE NOISE REJECTION: 60 dB, 50 Hz
CONTROL MODES DEFAULT (PRE-SET) MODE: SP1: PDPI (Proportional + Derivative + Integral (with Approach Control); Cycle Rate (prop time) 30 sec; Gain (prop band) 2.5% of FS; Rate (derivative time) 25 sec; Reset (integral time) 350 sec.; SP2: Off (inactive)
35
Page 39
SPECIFICATIONS (cont’d.)}
TABLE 5-1 DISPLAY- LINEARITY AND DEFAULT SETTINGS SENSOR _LINEARIZED TOLERANCE DEFAULT TYPE _ RANGE + SETPOINT ADJ J 0 to 800°C 1°C 400°C K Oto 1200°C 1°C 400°C N Oto 1200°C 1°C 400°C R 0 to 300°C 4°C 1600°C 300 to 1600°C 2°C S 0 to 400°C 4°C 1600°C 400 to 600°C 2°C 600 to 1600°C 1°C T ~90 to 250°C 1°C 250°C E 0 to 600°C 1°C 500°C JDIN Oto 800°C 1°C 400°C PTIOORTD -90to 250°C 0.25°C 200°C 250 to 400°C 0.5°C
KEY SELECTABLE MODES (also see Table 5-2) SP1; PID (3 TERM), PD, P or on/off, PDP (with Approach Control in PD mode)
sp2: Alarm high, alarm low or ‘‘out of limits’’, adjustable +0° - 99°C/F about SP1 setting control modes, on/off, or Proportional
DISPLAY: 3% digit green LED, 10 mm (0.4'') high; 1 or 0.1° resolution; error indication, deviation from set point indicators (3 LEDs)
36
Page 40
SPECIFICATIONS (cont’d.)
TABLE 5-2 KEY SELECTABLE PARAMETERS
Key selectable parameters, SP1 Default
Tp1 Cycle rate/prop time 50 ms, 1, 5, 10, 20, 30, 60 secs 30 sec ¢ Fast cycle < 10 sec, SSR or SSd/logic recommended * Cycle rate > 1 sec, min on/off times 0.5% x Tp1 e Linear dc, internal/external, key 50ms cycle rate
Xpl Gain/prop band 0.5, 1, 2, 2.5, 3, 5, 10, 20% x Span 2.5% Td1 Rate/derivative time off 5, 10, 25, 50, 100, 200 sec 25 sec Ac Approach control 0.5, 1, 1.5, 2, 2.5, 3, 4, 5x XP1 1.5 Derivative activated about SP1 Ww Integral/auto reset off 25, 50, 100, 200, 350, 600,1000 sec 350 sec MR Manual reset PD, P & on/off modes, 0° +99°C/F about SP1 Xsd1 Hysteresis 0.25, 0.5, 1, 1.25, 1.5, 2.5, 5, 10%xSpan None On/off mode only Key selectable parameters, SP2 Default Tp2/Xp2/Xsd2 Cycle rate/gain and hysteresis as SP1 None GENERAL
AMBIENT TEMPERATURE: 5° - 49°C (40° - 120°F)
NOISE IMMUNITY: Tested for power interference on Shaffner 200/222 Interference Simulator, no effect on stored data. Normal control restored within a short time after major power disturbance and ‘’brown outs”.
DATA RETENTION: 10 years with instrument unpowered
SAFETY STANDARDS: Designed in accordance with: UL 873, in-dustrial Temperature Controllers, CSA C22.2/24-1981, VDE 0411 Class 1; Mouldings in flame retardent polycarbonate
37
Page 41
SPECIFICATIONS (cont‘d.)
DEGREE OF PROTECTION: Designed in accordance with: IEC 529:1976 BS 5490:1977; Bezel assembly IP-54 ‘‘Protected against splashing water and dust”’; Case inside panel IP-30 ‘‘Protected agairist > 2.5 mm dia. objects”
DIMENSIONS: 48 x 48 x 13 mm (1.89" x 1.89” x 0.5") bezel; 115 mm (4.4’’) depth behind panel
PANEL CUTOUT: 45 mm square (1.772"' square) per DIN WEIGHT: 380 g
ADDENDUM A_ INTERNAL JUMPER CHANGES FOR 115/230 VAC AND 2-WIRE/3-WIRE RTD CONVERSIONS
Voltage and RTD 2-wire/3-wire conversions require wire solder jumper changes on the analog PCB. THESE MODIFICATIONS SHOULD BE MADE ONLY BY A QUALIFIED TECHNICIAN.
NOTE Use 22 SWG 19 AWG or 0.71 mm 2 tinned copper wire for jumpers.
To remove analog PCB refer to Figure A-1 and proceed as follows:
1. Separate the output module assembly from the main module by gently levering the retaining clips from both slots in the cover with a screwdriver.
2. Remove the output module and then pull the analog PCB from the mairi module cover.
MODULE COVER ANALOGUE OUTPUT in 1 , PCB MODULE iy i | \ tio) | ee
\
Figure A-1. Removing Analog PCB
38
Page 42
Al
A.2
115/230 VAC VOLTAGE CONVERSION
To convert from 115 Vac to 230 Vac, refer to Figure A-2 and proceed as follows:
1. Remove jumpers 3 and 5. 2. Fit solder jumper 4.
To convert from 230 Vac to 115 Vac, refer to Figure A-2 and proceed as follows:
1. Remove jumper 4. 2. Fit solder jumpers 3 and 5.
2-WIRE/3-WIRE RTD CONVERSION
NOTE
Use of a 3-wire RTD reduces display error when lead length is over 10M/30’
To convert from a 2-wire RTD to a 3-wire RTD, refer to Figure A-2 and proceed as follows:
1. Cut track where marked X on PCB. 2. Fit solder jumpers 1 and 2.
NOTE
Conversion to a 3-wire RTD inhibits subsequent selection and use of thermocouples.
39
Page 43
a ag 80 00 o000, 00 op o."00 gf oO°D
LKI eed O baw 0.60 ais ogo. OOO o8 ee wed O00 well O oo = goo unas oo Sd, Aba). beer
Figure A-2. Voltage and 2-Wire/3-Wire RTD Conversions
40
Page 44
6.0”
Figure A-3. Dimensions with the Power Socket
41
Page 45
WARRANTY
OMEGA warrants this unit to be free of defects in materials and workmanship and to give satisfactory service for a period of two (2) years from date of purchase. H the unit should malfunction, it must be returned to the factory for evaluation. Our Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge. However, this WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged as a result of excessive are damaged by misuse are not warranted. These include contact points, uses, and triacs.
THERE ARE NO WARRANTIES EXCEPT AS STATED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND OF FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL OMEGA ENGINEERING, INC. BE LIABLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES. THE BUYER'S SOLE REMEDY FOR ANY BREACH OF THIS AGREEMENT BY OMEGA ENGINEERING, INC. OR ANY BREACH OF ANY WARRANTY BY OMEGA ENGINEERING, INC. SHALL NOT EXCEED THE PURCHASE PRICE PAID BY THE PURCHASER TO OMEGA ENGINEERING, INC. FOR THE UNIT OR UNITS OR EQUIPMENT DIRECTLY AFFECTED BY SUCH BREACH.
r¢ FEOMEGA One Omega Drive, Box 4047
Stamford, Connecticut 06907-0047
(203)959-1660 Telex: 996404 Cable: OMEGA FAX: (203) 359-7700
Return Requests/inquiries Direct aff warranty and repair requeste/inquiries to OMEGA Customer Service Department, telephone number (2('3) 359-1660. BEFORE RETURNING ANY INSTRUMENT, PLEASE CONTACT THE OMEGA CUSTOMER SERVICE DEPARTMENT TO OBTAIN AN AUTHORIZED RETURN (AR) NUMBER. The designated AR number should then be marked on the outside of the return To avold processing delays, also please be sure to include:
1.7 "sname, d ph number. 2. Model and Serial numbers. instructions.
3. Repeir
Call OMEGA Toll Free* - Use these direct lines to get the service you want!
Sates: it’s Easy to Order from OMEGA! 1-4100-82-66342 1-£100-TC-OMEGA
For the BEST in Customer Service: 1-600-622-2378 1100-622-BEST
WHEN You Need Engineering Support and Technicai Assistance, Dial: 1-100-872-9436 1-800-USA-WHEN
In CT: (203) 369-1660
And International CABLE: OMEGA EASYLINK:62968934
TELEX: 996404 FAX: (203) 369-7700
OMEGA? is a registered trademark of OMEGA ENGINEERING, INC.
©Copyright 1968 OMEGA ENGINEERING, INC. All rights reserved including illustrations. Nothing in this manual may be reproduced in ‘any manner, either wholly or in part for any purpose whatsoever without written permission from OMEGA ENGINEERING, INC.
M575/048 Prinied in U.S.A.
TN gy se sa nema ca