For the Omron C200H-CPU01-E

Page 114

Appendix B

Specifications ! Caution

Ensure that the external variable resistor connectors are open when using the internal variable resistor.

External variable resistor connector

External variable resistor

B7A Interface Unit C200H-B7Aj1 (Basic I/O Unit Type) The B7A Interface Unit used with the B7A Link Terminal allows the transmission and reception of 16-point I/O data over two wires. The following B7A Interface Unit and B7A Link Terminal models are available. B7A Interface Unit 16-point input: C200H-B7AI1

B7A Link Terminals B7A-T6j1 (Screw terminal models) B7A-T6D2 (Modular models) B7A-R6jj1 (Screw terminal models) B7A-R6A52 (Modular models)

16-point output: C200H-B7AO1

Mount the B7A Interface Unit to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. Note If the B7A Interface Unit is connected to the C200H-CPU03-E or C200H-PS211, supply 24 VDC from an independent power supply to the B7A Interface Unit or use a transformer to separate the power supply line to the B7A Interface Unit from the power supply lines to the CPU and I/O Power Supply Unit.

I/O indicator ERR indicator

Connection terminals Connection terminals for the B7A Link Terminal: Connect this terminal to the SIG terminal of the B7A Link Terminal. Connect this terminal to the negative power terminal of the B7A Link Terminal. Supply 12 to 24 VDC. 12 to 24 VDC

I/O Indicator Indicates the ON or OFF status of input from the B7A Link Terminal or the ON and OFF status of output to the B7A Link Terminal. ERR Indicator Incorporated by the B7AI1 and lit when the B7AI1’s data transmission or reception is abnormal.

100

Page 115

Appendix B

Specifications

Connection Terminals SIG: Connects to the SIG terminal of the B7A Link Terminal. V–: Connects to the negative power terminal of the B7A Link Terminal. ! Caution

If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be damaged.

Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm2 minimum. 2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit. Input Mode Selector The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can be set. Input mode

15 points + 1 error

16 points

Function

Fifteen-point input from the B7A Link Terminal is effective. Bit 15 is used as transmission error bit.

Sixteen-point input from the B7A Link Terminal is effective.

Switch setting Bit no. allocation

Upper side

Lower side

00 to 14 15 Status of input indicator lamp 15

Input 00 to input 14 Transmission error bit Not used

Input 00 to input 14 Input 15 Lit when input 15 is ON. Not lit when input 15 is OFF.

Status of the ERR indicator

Lit when there is a transmission error and OFF during normal transmission

The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next transmission cycle. When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the transmission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is transmitted in the first transmission cycle when the B7A Link Terminal is turned on again. Transmission errors between the C200H-B7A01 and B7A Link Terminal are detected by the B7A Link Terminal only. Check the ERR indicator and error bit for any error.

Performance Specification Item I/O points

C200H-B7AI1

C200H-B7AO1

Transmission distance

16 points or 15 points and 1 error 16 output points input 500 m max. if power is supplied to the Interface Unit and B7A Link Terminal separately. 100 m max. if power is supplied to the Interface Unit and B7A Link Terminal from a single power supply.

Transmission delay

Typ. 19.2 ms, 31 ms max.

Minimum input time (see note 2)

---

Internal current consumption

5 VDC, 100 mA max.

External power supply (see note 1)

12 to 24 VDC ±10%, 10 mA min.

Weight

200 g max.

16 ms 12 to 24 VDC ±10%, 30 mA min.

Note 1. The external power supply capacity does not include the capacity required by the B7A Link Terminal. 2. The minimum input time is the minimum time required to read input signals from the CPU. Be sure that the ON/OFF width of signals sent to B7A Interface Unit output relays is at least 16 ms.

101

Page 116

Appendix B

Specifications

Dimensions Racks The dimensions shown below are for both the CPU Rack and Expansion I/O Rack. The C dimension for the Programming Console will increase by 30mm when the Programming Console Adapter C200H-BP001 is used, and will increase by 50 mm when the Programming Console Adapter C200H-BP002 is used.

M-4 screws 130 118

A W

6.5

7.5

C200H-BC101 505 491 270.5

Model

A

W

C200H-BC031

246

260

C200H-BC051-V1

316

330

C200H-BC081-V1

421

435

C200H-BC101

491

505

135 Peripheral device

D C

CPU Unit

102

D

C200H-CPU01/02/03

118

C200H-CPU11

143

Page 117

Appendix B

Specifications Mounted Unit

C CPU01/03

CPU11

Programming Console

148

173

Other peripheral devices

160

185

B-shape I/O Units

145

145

E-shape I/O Units

138

138

I/O Units The dimensions shown below are for the three shapes of I/O Units mentioned throughout these specifications. A-shape I/O Units x x Backplane

130 x x 101 35

118

B-shape I/O Units

130 x x x x x x Backplane x x 128

35

145

103

Page 118

Appendix B

Specifications E-shape I/O Units

Backplane x x 130 x x 121 35

138

Backplane Insulation Plates The dimensions shown below are for Backplane Insulation Plates. PC mounting screws Four screws with 4-mm diameter heads are provided.

Insulation plate mounting screws Four screws with 5-mm diameter shafts are provided. B

135

118 110

C D A E 6 5 dia

12 dia

10

Specifications

104

Model

D

E

C

A

B

3 slots

C200H-ATT31

210

261

---

246

---

5 slots

C200H-ATT51

280

331

---

316

---

8 slots

C200H-ATT81

385

436

---

421

---

10 slots

C200H-ATTA1

455

506

227.5

491

270.5

Page 119

Appendix B

Specifications I/O Connecting Cables The dimensions shown below are for I/O Connecting Cables. L

Cable

Length (L)

C200H-CN311

30 cm

C200H-CN711

70 cm

C200H-CN221

2m

C200H-CN521

5m

C200H-CN131

10 m

105

Page 120

This page is a scan with no text; see it in the PDF.

Page 121

Appendix C Standard Models The C200H is a Rack-type PC that can be configured many different ways. Here is a series of tables listing the Units available for the C200H, along with a brief description of the Unit and its model number.

C200H Racks Name Backplane (same for all Racks)

CPU Rack

CPU

Specifications

Model number

10 slots 8 slots 5 slots 3 slots 100 to 120/200 to 240 VAC (Does not support SYSMAC LINK and SYSMAC NET Link Systems.)

C200H-BC101-V2 C200H-BC081-V2 C200H-BC051-V2 C200H-BC031-V2 C200H-CPU01-E

100 to 120/200 to 240 VAC (Supports SYSMAC LINK and C200H-CPU11-E SYSMAC NET Link Systems.) Memory Unit

24 VDC CMOS-RAM Unit; built-in backup battery

UM: 7K words; DM: 1K words

C200H-MR831

UM: 3K words; DM: 1K words

C200H-MR432

UM: 7K words; DM: 1K words

C200H-MR832

EPROM Unit (EPROM ordered separately)

UM: 7K words; DM: 1K words

C200H-MP831

EEPROM Unit

UM: 3K words; DM: 1K words

C200H-ME431

EEPROM Unit

UM: 7K words; DM: 1K words

C200H-ME831

CMOS-RAM Unit; capacitor backup

Expansion I/O Racks

EPROM I/O Power Supply Unit I/O Connecting Cable (max. total length: 12 m)

UM: 3K words; DM: 1K words

C200H-CPU03-E C200H-MR431

27128; 150 ns; write voltage: 12.5 V 100 to 120/200 to 240 VAC 24 VDC 30 cm 70 cm 2m 5m 10 m

ROM-ID-B C200H-PS221 C200H-PS211 C200H-CN311 C200H-CN711 C200H-CN221 C200H-CN521 C200H-CN131

107

Page 122

Appendix C

Standard Models

C200H I/O Units Name Input Units

AC Input Unit

DC Input Unit

AC/DC Input Unit Output Units

Relay Output Unit

Triac Output Unit

Transistor Output Unit

Analog Timer Unit

Specifications 8 pts

100 to 120 VAC

C200H-IA121

16 pts

100 to 120 VAC

C200H-IA122/IA122V

8 pts

200 to 240 VAC

C200H-IA221

16 pts

200 to 240 VAC

C200H-IA222/IA222V

8 pts

No-voltage contact; NPN

C200H-ID001

8 pts

No-voltage contact; PNP

C200H-ID002

8 pts

12 to 24 VDC

C200H-ID211

16 pts

24 VDC

C200H-ID212

8 pts

12 to 24 VAC/DC

C200H-IM211

16 pts

24 VAC/DC

C200H-IM212

8 pts 12 pts 16 pts

2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VAC (For resistive loads)

C200H-OC221 C200H-OC222 C200H-OC225

5 pts

2 A, 250 VAC/24 VDC (For resistive loads) Independent commons

C200H-OC223

8 pts

2 A, 250 VAC/24 VDC (For resistive loads) Independent commons

C200H-OC224

8 pts

1 A, 120 VAC

C200H-OA121-E

8 pts

1.2 A, 120 VAC

C200H-OA122-E

8 pts

1.2 A, 250 VAC

C200H-OA223

12 pts

0.3 A, 250 VAC

C200H-OA222V

12 pts

0.5 A, 250 VAC

C200H-OA224

8 pts 12 pts 16 pts

1 A, 12 to 48 VDC 0.3 A, 24 VDC 0.3 A, 24 VDC

C200H-OD411 C200H-OD211 C200H-OD212

8 pts

2.1 A, 24 VDC

C200H-OD213

8 pts

0.8 A, 24 VDC; sourcing type (PNP); with load short protection

C200H-OD214

8 pts

5 to 24 VDC; sourcing type (PNP)

C200H-OD216

12 pts

5 to 24 VDC; sourcing type (PNP)

C200H-OD217

16 pts

1 A, 24 VDC; sourcing type (PNP); with load short protection

C200H-OD21A

4 timer pts

0.1 to 1 s, 1 to 10 s, 10 to 60 s, or 1 min to 10 min (switchable)

C200H-TM001

Connector with lead wire (2 m) for 1 external resistor

C4K-CN223

Variable Resistor Connector (Related Product) B7A Interface Units (Basic I/O Units)

Model number

Connects to B7A Link Terminals. 15 or 16 input pts

C200H-B7AI1

16 output pts

C200H-B7AO1

Note The C200H-OC225/OD212/OD21A 16-point Output Unit and the C200H-B7AO1 B7A Interface Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.

108

Page 123

Appendix C

Standard Models

C200H Special I/O Units All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit. Name High-density I/O Units

DC Input Units

Transistor Output Units

DC Input/ Transistor Output Units

Specifications

Model number

32 pts

5 VDC (TTL inputs); with high-speed input function C200H-ID501

32 pts 32 pts

24 VDC; with high-speed inputs C200H-ID215 0.1 A, 24 VDC (usable as 128-point dynamic output C200H-OD215 unit)

32 pts

35 mA, 5 VDC (TTL outputs) (usable as 128-point C200H-OD501 dynamic output unit)

16 input/ 12-VDC inputs; with high-speed input function C200H-MD115 16 output pts 0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 24-VDC inputs; with high-speed input function C200H-MD215 16 output pts 0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 5 VDC (TTL inputs); with high speed input function C200H-MD501 16 output pts 35 mA, 5 VDC Output (TTL outputs) (usable as 128-point dynamic input unit)

Analog I/O Analog Input 1 to 5/0 to 10 V; 4 inputs Units Unit

C200H-AD001

4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V; 8 inputs Analog Output 1 to 5/0 to 10 V; 2 outputs Unit 4 to 20 mA, –10 to 10 V; 4 outputs Temperature Sensor Units Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs Thermocouple (K(CA) or L(Fe-CuNi)) (switchable); 4 inputs

C200H-AD002 C200H-DA001 C200H-DA002 C200H-TS001 C200H-TS002

Platinum resistance thermometer (JPt) (switchable), DIN stan- C200H-TS101 dards; 4 inputs

Temperature Control Units

Heat/Cool Temperature Control Units

PID Control Units

Platinum resistance thermometer (Pt) (switchable); 4 inputs

C200H-TS102

Thermocouple

C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101 C200H-TC102 C200H-TC103 C200H-TV001 C200H-TV002 C200H-TV003 C200H-TV101 C200H-TV102 C200H-TV103 C200H-PID01 C200H-PID02 C200H-PID03

Transistor output Voltage output Current output Platinum re- Transistor output sistance Voltage output thermometer Current output Thermocou- Transistor output ple Voltage output Current output Platinum re- Transistor output sistance Voltage output thermometer Current output Transistor output Voltage output Current output

109