Page 114
Appendix B
Specifications ! Caution
Ensure that the external variable resistor connectors are open when using the internal variable resistor.
External variable resistor connector
External variable resistor
B7A Interface Unit C200H-B7Aj1 (Basic I/O Unit Type) The B7A Interface Unit used with the B7A Link Terminal allows the transmission and reception of 16-point I/O data over two wires. The following B7A Interface Unit and B7A Link Terminal models are available. B7A Interface Unit 16-point input: C200H-B7AI1
B7A Link Terminals B7A-T6j1 (Screw terminal models) B7A-T6D2 (Modular models) B7A-R6jj1 (Screw terminal models) B7A-R6A52 (Modular models)
16-point output: C200H-B7AO1
Mount the B7A Interface Unit to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. Note If the B7A Interface Unit is connected to the C200H-CPU03-E or C200H-PS211, supply 24 VDC from an independent power supply to the B7A Interface Unit or use a transformer to separate the power supply line to the B7A Interface Unit from the power supply lines to the CPU and I/O Power Supply Unit.
I/O indicator ERR indicator
Connection terminals Connection terminals for the B7A Link Terminal: Connect this terminal to the SIG terminal of the B7A Link Terminal. Connect this terminal to the negative power terminal of the B7A Link Terminal. Supply 12 to 24 VDC. 12 to 24 VDC
I/O Indicator Indicates the ON or OFF status of input from the B7A Link Terminal or the ON and OFF status of output to the B7A Link Terminal. ERR Indicator Incorporated by the B7AI1 and lit when the B7AI1’s data transmission or reception is abnormal.
100
Page 115
Appendix B
Specifications
Connection Terminals SIG: Connects to the SIG terminal of the B7A Link Terminal. V–: Connects to the negative power terminal of the B7A Link Terminal. ! Caution
If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be damaged.
Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm2 minimum. 2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit. Input Mode Selector The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can be set. Input mode
15 points + 1 error
16 points
Function
Fifteen-point input from the B7A Link Terminal is effective. Bit 15 is used as transmission error bit.
Sixteen-point input from the B7A Link Terminal is effective.
Switch setting Bit no. allocation
Upper side
Lower side
00 to 14 15 Status of input indicator lamp 15
Input 00 to input 14 Transmission error bit Not used
Input 00 to input 14 Input 15 Lit when input 15 is ON. Not lit when input 15 is OFF.
Status of the ERR indicator
Lit when there is a transmission error and OFF during normal transmission
The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next transmission cycle. When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the transmission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is transmitted in the first transmission cycle when the B7A Link Terminal is turned on again. Transmission errors between the C200H-B7A01 and B7A Link Terminal are detected by the B7A Link Terminal only. Check the ERR indicator and error bit for any error.
Performance Specification Item I/O points
C200H-B7AI1
C200H-B7AO1
Transmission distance
16 points or 15 points and 1 error 16 output points input 500 m max. if power is supplied to the Interface Unit and B7A Link Terminal separately. 100 m max. if power is supplied to the Interface Unit and B7A Link Terminal from a single power supply.
Transmission delay
Typ. 19.2 ms, 31 ms max.
Minimum input time (see note 2)
---
Internal current consumption
5 VDC, 100 mA max.
External power supply (see note 1)
12 to 24 VDC ±10%, 10 mA min.
Weight
200 g max.
16 ms 12 to 24 VDC ±10%, 30 mA min.
Note 1. The external power supply capacity does not include the capacity required by the B7A Link Terminal. 2. The minimum input time is the minimum time required to read input signals from the CPU. Be sure that the ON/OFF width of signals sent to B7A Interface Unit output relays is at least 16 ms.
101
Page 116
Appendix B
Specifications
Dimensions Racks The dimensions shown below are for both the CPU Rack and Expansion I/O Rack. The C dimension for the Programming Console will increase by 30mm when the Programming Console Adapter C200H-BP001 is used, and will increase by 50 mm when the Programming Console Adapter C200H-BP002 is used.
M-4 screws 130 118
A W
6.5
7.5
C200H-BC101 505 491 270.5
Model
A
W
C200H-BC031
246
260
C200H-BC051-V1
316
330
C200H-BC081-V1
421
435
C200H-BC101
491
505
135 Peripheral device
D C
CPU Unit
102
D
C200H-CPU01/02/03
118
C200H-CPU11
143
Page 117
Appendix B
Specifications Mounted Unit
C CPU01/03
CPU11
Programming Console
148
173
Other peripheral devices
160
185
B-shape I/O Units
145
145
E-shape I/O Units
138
138
I/O Units The dimensions shown below are for the three shapes of I/O Units mentioned throughout these specifications. A-shape I/O Units x x Backplane
130 x x 101 35
118
B-shape I/O Units
130 x x x x x x Backplane x x 128
35
145
103
Page 118
Appendix B
Specifications E-shape I/O Units
Backplane x x 130 x x 121 35
138
Backplane Insulation Plates The dimensions shown below are for Backplane Insulation Plates. PC mounting screws Four screws with 4-mm diameter heads are provided.
Insulation plate mounting screws Four screws with 5-mm diameter shafts are provided. B
135
118 110
C D A E 6 5 dia
12 dia
10
Specifications
104
Model
D
E
C
A
B
3 slots
C200H-ATT31
210
261
---
246
---
5 slots
C200H-ATT51
280
331
---
316
---
8 slots
C200H-ATT81
385
436
---
421
---
10 slots
C200H-ATTA1
455
506
227.5
491
270.5
Page 119
Appendix B
Specifications I/O Connecting Cables The dimensions shown below are for I/O Connecting Cables. L
Cable
Length (L)
C200H-CN311
30 cm
C200H-CN711
70 cm
C200H-CN221
2m
C200H-CN521
5m
C200H-CN131
10 m
105
Page 120
Page 121
Appendix C Standard Models The C200H is a Rack-type PC that can be configured many different ways. Here is a series of tables listing the Units available for the C200H, along with a brief description of the Unit and its model number.
C200H Racks Name Backplane (same for all Racks)
CPU Rack
CPU
Specifications
Model number
10 slots 8 slots 5 slots 3 slots 100 to 120/200 to 240 VAC (Does not support SYSMAC LINK and SYSMAC NET Link Systems.)
C200H-BC101-V2 C200H-BC081-V2 C200H-BC051-V2 C200H-BC031-V2 C200H-CPU01-E
100 to 120/200 to 240 VAC (Supports SYSMAC LINK and C200H-CPU11-E SYSMAC NET Link Systems.) Memory Unit
24 VDC CMOS-RAM Unit; built-in backup battery
UM: 7K words; DM: 1K words
C200H-MR831
UM: 3K words; DM: 1K words
C200H-MR432
UM: 7K words; DM: 1K words
C200H-MR832
EPROM Unit (EPROM ordered separately)
UM: 7K words; DM: 1K words
C200H-MP831
EEPROM Unit
UM: 3K words; DM: 1K words
C200H-ME431
EEPROM Unit
UM: 7K words; DM: 1K words
C200H-ME831
CMOS-RAM Unit; capacitor backup
Expansion I/O Racks
EPROM I/O Power Supply Unit I/O Connecting Cable (max. total length: 12 m)
UM: 3K words; DM: 1K words
C200H-CPU03-E C200H-MR431
27128; 150 ns; write voltage: 12.5 V 100 to 120/200 to 240 VAC 24 VDC 30 cm 70 cm 2m 5m 10 m
ROM-ID-B C200H-PS221 C200H-PS211 C200H-CN311 C200H-CN711 C200H-CN221 C200H-CN521 C200H-CN131
107
Page 122
Appendix C
Standard Models
C200H I/O Units Name Input Units
AC Input Unit
DC Input Unit
AC/DC Input Unit Output Units
Relay Output Unit
Triac Output Unit
Transistor Output Unit
Analog Timer Unit
Specifications 8 pts
100 to 120 VAC
C200H-IA121
16 pts
100 to 120 VAC
C200H-IA122/IA122V
8 pts
200 to 240 VAC
C200H-IA221
16 pts
200 to 240 VAC
C200H-IA222/IA222V
8 pts
No-voltage contact; NPN
C200H-ID001
8 pts
No-voltage contact; PNP
C200H-ID002
8 pts
12 to 24 VDC
C200H-ID211
16 pts
24 VDC
C200H-ID212
8 pts
12 to 24 VAC/DC
C200H-IM211
16 pts
24 VAC/DC
C200H-IM212
8 pts 12 pts 16 pts
2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VAC (For resistive loads)
C200H-OC221 C200H-OC222 C200H-OC225
5 pts
2 A, 250 VAC/24 VDC (For resistive loads) Independent commons
C200H-OC223
8 pts
2 A, 250 VAC/24 VDC (For resistive loads) Independent commons
C200H-OC224
8 pts
1 A, 120 VAC
C200H-OA121-E
8 pts
1.2 A, 120 VAC
C200H-OA122-E
8 pts
1.2 A, 250 VAC
C200H-OA223
12 pts
0.3 A, 250 VAC
C200H-OA222V
12 pts
0.5 A, 250 VAC
C200H-OA224
8 pts 12 pts 16 pts
1 A, 12 to 48 VDC 0.3 A, 24 VDC 0.3 A, 24 VDC
C200H-OD411 C200H-OD211 C200H-OD212
8 pts
2.1 A, 24 VDC
C200H-OD213
8 pts
0.8 A, 24 VDC; sourcing type (PNP); with load short protection
C200H-OD214
8 pts
5 to 24 VDC; sourcing type (PNP)
C200H-OD216
12 pts
5 to 24 VDC; sourcing type (PNP)
C200H-OD217
16 pts
1 A, 24 VDC; sourcing type (PNP); with load short protection
C200H-OD21A
4 timer pts
0.1 to 1 s, 1 to 10 s, 10 to 60 s, or 1 min to 10 min (switchable)
C200H-TM001
Connector with lead wire (2 m) for 1 external resistor
C4K-CN223
Variable Resistor Connector (Related Product) B7A Interface Units (Basic I/O Units)
Model number
Connects to B7A Link Terminals. 15 or 16 input pts
C200H-B7AI1
16 output pts
C200H-B7AO1
Note The C200H-OC225/OD212/OD21A 16-point Output Unit and the C200H-B7AO1 B7A Interface Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
108
Page 123
Appendix C
Standard Models
C200H Special I/O Units All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit. Name High-density I/O Units
DC Input Units
Transistor Output Units
DC Input/ Transistor Output Units
Specifications
Model number
32 pts
5 VDC (TTL inputs); with high-speed input function C200H-ID501
32 pts 32 pts
24 VDC; with high-speed inputs C200H-ID215 0.1 A, 24 VDC (usable as 128-point dynamic output C200H-OD215 unit)
32 pts
35 mA, 5 VDC (TTL outputs) (usable as 128-point C200H-OD501 dynamic output unit)
16 input/ 12-VDC inputs; with high-speed input function C200H-MD115 16 output pts 0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 24-VDC inputs; with high-speed input function C200H-MD215 16 output pts 0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 5 VDC (TTL inputs); with high speed input function C200H-MD501 16 output pts 35 mA, 5 VDC Output (TTL outputs) (usable as 128-point dynamic input unit)
Analog I/O Analog Input 1 to 5/0 to 10 V; 4 inputs Units Unit
C200H-AD001
4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V; 8 inputs Analog Output 1 to 5/0 to 10 V; 2 outputs Unit 4 to 20 mA, –10 to 10 V; 4 outputs Temperature Sensor Units Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs Thermocouple (K(CA) or L(Fe-CuNi)) (switchable); 4 inputs
C200H-AD002 C200H-DA001 C200H-DA002 C200H-TS001 C200H-TS002
Platinum resistance thermometer (JPt) (switchable), DIN stan- C200H-TS101 dards; 4 inputs
Temperature Control Units
Heat/Cool Temperature Control Units
PID Control Units
Platinum resistance thermometer (Pt) (switchable); 4 inputs
C200H-TS102
Thermocouple
C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101 C200H-TC102 C200H-TC103 C200H-TV001 C200H-TV002 C200H-TV003 C200H-TV101 C200H-TV102 C200H-TV103 C200H-PID01 C200H-PID02 C200H-PID03
Transistor output Voltage output Current output Platinum re- Transistor output sistance Voltage output thermometer Current output Thermocou- Transistor output ple Voltage output Current output Platinum re- Transistor output sistance Voltage output thermometer Current output Transistor output Voltage output Current output
109