SYSMAC Programmable Controllers C200H (CPU01-E/03-E/11-E) Installation Guide, pages 104 to 113
Pages 104 to 113 of 173
The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-CPU01-E
Page 104
Appendix B
Specifications
Transistor Output Unit C200H-OD214 (Sourcing Type) Max. switching capacity
24 VDC +10%/–15% 0.8 A (2.4 A/Unit) surge current 2 A (sourcing type) PNP output
Min. switching capacity
None
Leakage Current
1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
1 ms max.
OFF Response Time
1 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
Short-circuit protection
Power for External Supply
150 mA 24 VDC +10%/–15% max.
Weight
250 g max.
Dimensions
A-shape
Overcurrent protection Thermal protection
Circuit Configuration OUT L
Out put LED indicator +V Source Driver Internal circuit Reset button
OUT L
+
24 VDC COM
Alarm Output LED
Terminal Connections 0
L
1
L
2
L L
24 VDC (2.1 A max., 5.2 A/Unit)
L L L L
3 4 5 6 7
A0 A1 A2 A3 A4 A5 A6 A7
COM (0 V)
A8
24 VDC
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
90
Page 105
Appendix B
Specifications
C200H-OD214 Short-Circuit Protection The C200H-OD214 Output Unit is equipped with two types of short-circuit protection. One is overcurrent protection, and the other is thermal protection. The short-circuit should be eliminated immediately in order to avoid damage to the Unit. Overcurrent Protection When the output current reaches 2 A, the alarm output turns ON, and the alarm LED lights. Make sure the surge current of the load does not exceed 2 A, or the alarm may be activated. Thermal Protection When the junction temperature of the output transistor reaches its upper limit, the output turns OFF, the alarm output turns ON, and the alarm LED blinks. But the output transistor is provided with a heat sink. So in some cases, when the output is short-circuited the thermal protection may not activate because the extra heat is dissipated by the heat sink. However, the alarm LED will still light and the alarm output will still turn ON. How It Works When the short-circuit protection activates, the output displays the characteristic shown below.
Output Voltage
Overcurrent limit alarm output point
Output current 2 A (minimum value)
0
Each pair of outputs share one alarm LED and one alarm output bit as shown below (bits 12 through 15 cannot be used as work bits) Output No.
0
1
2
3
4
5 6
7
Alarm LED No.
0
2
4
6
Alarm Output Point No.
08
09
10
11
Both the alarm LED and alarm output bit for the short-circuited output turn ON even if only one of the outputs is short-circuited. Both outputs should be disconnected until the short-circuit can be traced. Clearing the Alarm When the short-circuit has been eliminated, reset the Unit by pressing the reset button. The alarm LED will go out, the alarm output will turn OFF, and the output will be reset. Output LED
Alarm LED Reset button (use a screwdriver or other similar object to press it).
91
Page 106
Appendix B
Specifications
Programming Example If there is a short-circuit in an output, we want the program to turn that output OFF. Assume that the Unit is mounted at word 000. A program to turn OFF output bits 00 and 01 is shown below. A
00008 00000
B
00008 00001
Since alarm output bit 08 covers both output bits 00 and 01, both these outputs are forced OFF as soon as output bit 08 turns ON (bits A and B can be any other bits required in the program).
92
Page 107
Appendix B
Specifications
Transistor Output Unit C200H-OD216 Max. switching capacity
0.3 A 5 to 24 VDC
Min. switching capacity
10 mA 5 VDC
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
1.5 ms max.
OFF Response Time
2 ms max.
No. of Circuits
1 (8 points/common) positive common (sourcing type)
Internal Current Consumption
10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Fuse Rating
None
Power for External Supply
N/A
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration
OUT
Output LED indicator
OUT Internal Circuit
L
L
5 to 24 VDC COM
Terminal Connections L L L L
5 to 24 VDC
L L L L
0 1 2 3 4 5 6 7
A0 A1 A2 A3 A4 A5 A6 A7
COM A8 NC A9
93
Page 108
Appendix B
Specifications
Transistor Output Unit C200H-OD217 Max. switching capacity
0.3 A 5 to 24 VDC
Min. switching capacity
10 mA 5 VDC
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
1.5 ms max.
OFF Response Time
2 ms max.
No. of Circuits
1 (12 points/common) positive common (sourcing type)
Internal Current Consumption
10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Fuse Rating
None
Power for External Supply
N/A
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration
OUT
Output LED indicator
L
OUT L
Internal circuit
5 to 24 VDC COM
Terminal Connections
L L
5 to 24 VDC
L L L L
1 3 5 7 9 11
A0 A1 A2 A3 A4 A5
NC A6 NC A7 COM A8
B0
0
B1
2
B2
4
B3
6
B4
8
B5 10 B6 NC B7 NC B8 NC B9 NC
94
L L L L L L
Page 109
Appendix B
Specifications
Transistor Output Unit C200H-OD411 Max. switching capacity
12 to 48 VDC 1 A (3 A/Unit)
Min. switching capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
30 mA 12 to 48 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration OUT
L
V Output LED indicator OUT L Internal circuit
Fuse
COM 12 to 48 VDC
Fuse blowout detection circuit
F LED
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections L L L L
12 to 48 VDC (1 A max., 3 A/Unit)
L L L L
0 1 2 3 4 5 6 7
A0 A1 A2 A3 A4 A5 A6 A7
COM (0 V)
A8
12 to 48 VDC
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
95
Page 110
Appendix B
Specifications
Transistor Output Unit C200H-OD21A (Sourcing Type with Load Circuit Protection) Max. switching capacity
24 VDC +10%/–15%, 1.0 A (4 A/Unit) surge current 1.6 A (sourcing type) PNP output
No. of Circuits
1 (16 points/common)
Min. switching capacity
None
Internal Current Consumption
160 mA, 5 VDC max.
Leakage Current
0.1 mA max.
Load Short-circuit Protection
Detection current: 1.2 A min (1.6 A typical)
Residual Voltage ON Response Time
0.8 V max. 0.1 ms max.
Power for External Supply
35 mA 24 VDC +10%/–15% min.
Alarm Output (See note)
No. of outputs: 1 (2 kΩ internal resistor) Connectable Units: Only the following DC Input Units and alarm output LED indicators can be connected: C200H-ID001, ID211, ID212, IM211 (DC), IM212 (DC), ID215, ID501, MD115, MD215, MD501
Weight Dimensions
400 g max. B-shape
OFF Response Time 0.3 ms max.
Internal Circuit
Output LED indicator
Short-circuit protection circuit
Circuit Configuration to 0V 2 kΩ
Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM output becomes active (low level). The problem can be detected externally by connecting a DC Input Unit to the ALARM output or by connecting an alarm output indicator. It’s not possible to connect both the Input Unit and the indicator at the same time.
96
Page 111
Appendix B
Specifications Terminal Connections +24 VDC
24 VDC
Note 1. When the ALARM output turns ON, remove the cause of the high current and then shut off the external power supply for approx. 1 second. After confirming that the cause has been removed, turn ON the power supply again to reset the output. As shown in the diagram, it is recommended that a relay or switch that turns ON or OFF only the external power supply be connected right before the B9 (+V). Check that this relay or switch has a contact capacity higher than the external power supply current consumption (35 mA + load current min.). 2. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
97
Page 112
Appendix B
Specifications
Analog Timer Unit Item
Specifications
Oscillation Method
RC oscillation
Time Setting Range
Use the DIP switch to set any of the following four ranges, according to the chart shown on the next page. 0.1 to 1 second (typical) 1 to 10 seconds (typical) 10 to 60 seconds (typical) 1 to 10 minutes (typical)
Timer Pause Function
The timing operation can be paused if so specified by the program. Therefore, the timers can also be used as cumulative registers.
Number of Timer Points
4
Indicators
SET and TIME UP
External Variable Resistor
External variable resistors can be used to set the time value when the IN/EXT selector is set to OFF (EXT). Use 20 kW variable resistors.
Bit Allocation
The word is determined by the system configuration.
Bit
Function
00
T0 start output
01
T1 start output
02
T2 start output
03
T3 start output
04
T0 pause output
05
T1 pause output
0
Operates
06
T2 pause output
1
Stops
07
T3 pause output
08
T0 time-up input
09
T1 time-up input
10
T2 time-up input
11
T3 time-up input
“1” when time is running
“1” when time is up
12 13 Cannot be used 14 15 Programming and Timing Chart
Timer start input word n bits 08 through 11
Timer setting (word n bits 00 through 03) Time-up output
Time-up flag Internal Current Consumption
98
60 mA 5 VDC max.
Timer start input
Time-up output Timer set value
Page 113
Appendix B
Specifications Internal variable resistors These variable resistors are used to set the timers. The settings of these resistors are effective only when the corresponding IN/EXT selector is ON. To set or adjust the time, use the screwdriver supplied with the Unit. Turn the variable resistor clockwise to increase the time value. The numbers 0 through 3 correspond to T0 through T3, respectively.
TM001
Indicators The SET indicators in the top row light when the corresponding timer is operating. The TIME UP indicators in the bottom row light when the corresponding timer (T0 through T3) turns ON.
0
1
2
3
Time range setting
Min. 0 1 External variable resistor connectors
Max.
2
External variable resistors can also be used to set the timers. The IN/EXT selector pin must be set to the OFF position. Numbers 0 through 3 correspond to T0 through T3, respectively. Use 20-kW variable resistors and AWG 22 to 28 lead wires. The connector has solderless terminals and must be wired as shown below.
3
IN/EXT selectors When the internal variable resistor is used, set the corresponding pin to ON; when an external variable resistor is used, set the corresponding pin to OFF. Pin numbers 4 through 1 correspond to T0 through T3, respectively.
Timers
Pin No.
0.1 to 1 s
0.1 to 10 s
10 to 60 s
1 to 10 m
T0
8
0
1
0
1
7
0
0
1
1
6
0
1
0
1
5
0
0
1
1
4
0
1
0
1
3
0
0
1
1
2
0
1
0
1
1
0
0
1
1
T1 T2 T3
(0: OFF 1: ON)
99