For the Omron C200H-CPU01-E
Page 94
Appendix B
Specifications
Triac Output Unit C200H-OA223 Max. Switching Capacity
1.2 A 250 VAC, 50/60 Hz (4 A/Unit)
Max. Inrush Current
15 A (pulse width: 100 ms) 30 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max./3 mA (240 VAC) max.
Min. Switching Capacity Leakage Current Residual Voltage ON Response Time
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to 50 mA) 1 ms max.
OFF Response Time
1/2 of load frequency+1 ms or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
5 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
E-shape
Circuit Configuration OUT L OUT
Output indicator
L
Internal circuit
Fuse
COM 250 VAC max.
Fuse blowout detection circuit
F indicator Fuse: 5 A 250 V (5.2-dia.x20) HT (SOC)
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.
Terminal Connections
250 VAC max. (1.2 A max. 4 A/Unit)
80
L
0
A0
L
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
COM
A8
NC
A9
Page 95
Appendix B
Specifications
Triac Output Unit C200H-OA224 Max. Switching Capacity
0.5 A 250 VAC, 50/60 Hz (2 A/Unit)
Max. Inrush Current
10 A (pulse width: 100ms) 20 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max./3 mA (240 VAC) max.
Min. Switching Capacity Leakage Current Residual Voltage ON Response Time
1.5 VAC max. (50 to 500 mA)/5 VAC max. (10 to 50 mA) 1 ms max.
OFF Response Time
1/2 of load frequency + 1 ms or less.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
270 mA 5 VDC max.
Fuse Rating
3.15 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration OUT L OUT
Output indicator
L
Internal circuit
Fuse
COM 250 VAC max.
Fuse: 3.15 A 250 V (5.2-dia.x20) MT4 (SOC)
Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output.
Terminal Connections
1 L
3 L L L
5 7 9
L
11 L
250 VAC max. (0.5 A max., 2 A/Unit)
B0 A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM
A8
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
NC
B7
NC
B8
NC
B9
NC
L L L L L L
81
Page 96
Appendix B
Specifications
Contact Output Unit C200H-OC221 Max. switching capacity
2 A 250 VAC (cos of phase angle = 1), 2 A 250 VAC (cos of phase angle = 0.4), 2 A 24 VDC 8 A/Unit
Min. switching capacity
10 mA 5 VDC
Relay
G6B-1174P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration
OUT L Output LED indicator OUT L Internal circuit COM 250 VAC 24 VDC max.
Terminal Connections 0 L
A0 1 A1
L
2 A2
L
3 A3
L
4 A4
L
5 A5
L
6 A6
L
7 A7
L COM
A8 NC
250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)
82
A9
Page 97
Appendix B
Specifications
Contact Output Unit C200H-OC222 Max. switching capacity
2 A 250 VAC (cos of phase angle = 1), 2 A 250 VAC (cos of phase angle = 0.4), 2 A 24 VDC 8 A/Unit
Min. switching capacity
10 mA 5 VDC
Relay
G6B-1174P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
1 (12 points/common) 8 points max. can be ON simultaneously.
Internal Current Consumption
10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration
OUT L Output LED indicator OUT L Internal circuit
COM 250 VAC 24 VDC max.
Terminal Connections
1 L L L
3 5 7
L
9 L
11 L
B0 A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM
A8
0
L
B1
2
L
B2
4
L
B3
6
B4
8
B5 10 B6
NC
B7
NC
B8
NC
B9
NC
L L L
250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)
83
Page 98
Appendix B
Specifications
Contact Output Unit C200H-OC223 Max. switching capacity
2 A 250 VAC (cos of phase angle = 1), 2 A 250 VAC (cos of phase angle = 0.4), 2 A 24 VDC 10 A/Unit
Min. switching capacity relay
10 mA 5 VDC
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
5 independent contacts
Internal Current Consumption
10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration
Output LED indicator OUT L Internal circuit
OUT 250 VAC 24 VDC max.
Terminal Connections L
0 c0
L
1 c1 2
L
250VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)
c2 L
3 c3 4
A1 A2 A3 A4 A5 A6 A7 A8
L c4
84
A0
A9
Page 99
Appendix B
Specifications
Contact Output Unit C200H-OC224 Max. switching capacity
2 A 250 VAC (cos of phase angle = 1), 2 A 250 VAC (cos of phase angle = 0.4), 2 A 24 VDC 16 A/Unit
Min. switching capacity relay
10 mA 5 VDC
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
8 independent contacts
Internal Current Consumption
10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration
Output LED indicator OUT L Internal circuit OUTc 250 VAC 24 VDC max.
Terminal Connections c0 c1
B0 A0 A1 c2
A2 c3
250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (16 A/Unit)
A3 c4
A4 c5
A5 c6
A6 c7
A7 NC
A8
B1 B2 B3 B4 B5 B6 B7
0 1 2 3 4 5 6 7
L L L L L L L L
B8 NC B9 NC
85
Page 100
Appendix B
Specifications
Contact Output Unit C200H-OC225 Max. switching capacity
2 A 250 VAC (cos of phase angle = 1), 2 A 250 VAC (cos of phase angle = 0.4), 2 A 24 VDC 8 A/Unit
Min. switching capacity
10 mA 5 VDC
Relay
G6B-1174P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
1 (16 points/common) 8 points max. can be ON simultaneously.
Internal Current Consumption
50 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
400 g max.
Dimensions
B-shape
Circuit Configuration
OUT L Output LED indicator OUT L Internal circuit
COM 250 VAC 24 VDC max.
Terminal Connections
0 B0 A0 2 3 A1 B1 L 4 5 A2 B2 L 6 7 A3 B3 L 8 9 A4 B4 L 10 B5 11 A5 L B6 12 13 A6 L 14 15 A7 B7 L B8 NC A8 COM B9 NC L
1
L L L L L L L L
250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)
Note This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
86
Page 101
Appendix B
Specifications
Transistor Output Unit C200H-OD211 Max. switching capacity
0.3 A 24 VDC +10%/–15% (2 A/Unit)
Min. switching capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
160 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
25 mA 24 VDC +10%/–15% max.
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration OUT L +V Output LED indicator OUT L Internal circuit
24 VDC Fuse
COM
Fuse: GGS (Nagasawa)
Note No blown fuse detector circuit is provided.
Terminal Connections
L L L
24 VDC (0.3 A max., 2 A/Unit)
L L L
1 3 5 7 9 11
A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM (0 V)
A8
B0
0
L
B1
2
L
B2
4
L
B3
6
B4
8
B5 10
L L L
B6
NC
B7
NC
B8
NC + 24 VDC
B9
Note Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF.
87
Page 102
Appendix B
Specifications
Transistor Output Unit C200H-OD212 Max. switching capacity
0.3 A 24 VDC +10%/–15% (4.8 A/Unit)
Min. switching capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (16 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
8 A 125 V (5.2-dia.x20)
Power for External Supply
35 mA 24 VDC +10%/–15% max.
Weight
350 g max.
Dimensions
B-shape
Circuit Configuration OUT L +V Output LED indicator OUT L Internal circuit
24 VDC Fuse
COM
Fuse: GGS (Nagasawa)
Note No blown fuse detector circuit is provided.
Terminal Connections
L L L
24 VDC (0.3 A max )
L
1 3 5 7 9
A0 A1 A2 A3 A4
B0
0
L
B1
2
L
B2
4
L
B3
6
B4
8
L L
B5 10 L 11 A5 L B6 12 L 13 A6 L B7 14 L 15 A7 L B8 NC A8 + 24 VDC COM (0 V) B9 L
Note 1. Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF. 2. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
88
Page 103
Appendix B
Specifications
Transistor Output Unit C200H-OD213 Max. switching capacity
2.1 A 24 VDC +10%/–15% (5.2 A/Unit) NPN output
Min. switching capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
8 A 125 V (5.2-dia.x20)
Power for External Supply
30 mA 24 VDC +10%/–15% max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration OUT L +V
Output LED indicator
OUT L 24 VDC
Internal circuit
Fuse
COM
Fuse blowout detection circuit
F LED
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections L L L
24 VDC (2.1 A max., 5.2 A/Unit)
L L L L L
0 1 2 3 4 5 6 7
A0 A1 A2 A3 A4 A5 A6 A7
COM (0 V)
A8
24 VDC
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
89