Page 84
Appendix B
Specifications
AC Input Unit C200H-IA222/IA222V Rated Input Voltage
200 to 240 VAC 50/60 Hz
Operating Input Voltage
170 to 264 VAC 50/60 Hz
Input Impedance
21 kW (50 Hz), 18 kW (60 Hz)
Input Current
10 mA typical (at 200 VAC)
ON Voltage
120 VAC min.
OFF Voltage
40 VAC max.
ON Response Time
35 ms max. (at 200 VAC, 25°C)
OFF Response Time
55 ms max. (at 200 VAC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
IA222: 300 g max. IA222V: 400 g max.
Dimensions
B-shape
Circuit Configuration IN
0.15 mF 680 W (IA222) IN
200 to 240 VAC 680 kW 910 W
COM
Input LED indicator
Terminal Connections
1 3 5 100 to 120 VAC
7 9 11 13 15 COM
70
B0 A0 A1 A2 A3 A4 A5 A6 A7 A8
0
B1
2
B2
4
B3
6
B4
8
B5 10 B6 12 B7 14 B8
NC
B9
NC
Internal circuit
Page 85
Appendix B
Specifications
No-Voltage Contact Input Unit C200H-ID001 Input Voltage
No-voltage contact/NPN output type (negative common)
Input Impedance
3 kW
Input Current
7 mA typical
ON Voltage
(14.4 VDC min.)
OFF Voltage
(5.0 VDC max.)
ON Response Time
1.5 ms max. (no-voltage contact, at 25°C)
OFF Response Time
1.5 ms max. (no-voltage contact, at 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration Current
IN
IN
3 kW 0.01 mF
COM
Internal circuit
1.8 kW
Input LED indicator
0.3 A 24 VDC Power supply
+ Internal 24 VDC – power supply CPU, Expansion I/O Power Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.
Terminal Connections 0 1 2 3 Current (NPN output)
4 5 6 7 COM NC
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
71
Page 86
Appendix B
Specifications
No-Voltage Contact Input Unit C200H-ID002 Input Voltage
No-voltage contact/NPN output type (positive common)
Input Impedance
3 kW
Input Current
7 mA typical
ON Voltage
(14.4 VDC min.)
OFF Voltage
(5.0 VDC max.)
ON Response Time
1.5 ms max. (no-voltage contact, at 25°C)
OFF Response Time
1.5 ms max. (no-voltage contact, at 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
3 kW 0.01 mF
COM
1.8 kW
Internal circuit
Current
Input LED indicator
0.3 A 24 VDC Power supply
+ Internal 24 VDC – power supply CPU, Expansion I/O Power Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.
Terminal Connections 0 1 2 3 Current (PNP output)
4 5 6 7 COM NC
72
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
Page 87
Appendix B
Specifications
DC Input Unit C200H-ID211 Rated Input Voltage
12 to 24 VDC
Operating Input Voltage
10.2 to 26.4 VDC
Input Impedance
2 kW
Input Current
10 mA (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
1.5 ms max. (at 24 VDC, 25°C)
OFF Response Time
1.5 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (8 point/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
2 kW 0.01 mF
COM
Internal circuit
1.8 kW
12 to 24 VDC
Input LED indicator
Terminal Connections 0 1 2 3 12 to 24 VDC
4 5 6 7 COM
NC
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
73
Page 88
Appendix B
Specifications
DC Input Unit C200H-ID212 Rated Input Voltage
24 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Input Impedance
3 kW
Input Current
7 mA (at 24 VDC)
ON Voltage
14.4 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
1.5 ms max. (at 24 VDC, 25°C)
OFF Response Time
1.5 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration IN
IN
3 kW 0.01 mF
COM
Internal circuit
1.8 kW
24 VDC
Input LED indicator
Terminal Connections
1 3 5 7 24 VDC
9 11 13 15 COM
74
A0 A1 A2 A3
B0
0
B1
2
B2
4
B3
6
B4
8
A4
B5 10
A5
B6 12 B7 14
A6 A7 A8
B8
NC
B9
NC
Page 89
Appendix B
Specifications
AC/DC Input Unit C200H-IM211 Rated Input Voltage
12 to 24 VDC
Operating Input Voltage
10.2 to 26.4 VDC
Input Impedance
2 kW
Input Current
10 mA typical (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
15 ms max. (at 24 VDC, 25°C)
OFF Response Time
15 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
2 kW 0.01 mF
COM
1.8 kW
Internal circuit
12 to 24 VAC/DC Input LED indicator
Terminal Connections 0 1 2 3 12 to 24 VAC/DC
4 5 6 7 COM
NC
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
75
Page 90
Appendix B
Specifications
AC/DC Input Unit C200H-IM212 Rated Input Voltage
24 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Input Impedance
3 kW
Input Current
7 mA typical (at 24 VDC)
ON Voltage
14.4 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
1.5 ms max. (at 24 VDC, 25°C)
OFF Response Time
1.5 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
B-shape
Circuit Configuration IN
IN
3 kW 0.01 mF
COM
1.8 kW
Internal circuit
24 VAC/DC Input LED indicator
Terminal Connections
1 3 5 24 VAC/DC
7 9
B0 A0 A1 A2 A3 A4
0
B1
2
B2
4
B3
6
B4
8
B5 10 11 A5 B6 12 13 A6 B7 14 15 A7 B8 NC COM A8 B9 NC
76
Page 91
Appendix B
Specifications
Triac Output Unit C200H-OA222V Max. Switching Capacity
0.3 A 250 VAC, 50/60 Hz (2 A/Unit)
Min. Switching Capacity Leakage Current
10 mA (resistive load)/40 mA (inductive load) 10 VAC 3 mA (100 VAC) max./6 mA (200 VAC) max.
Residual Voltage
1.2 V max.
ON Response Time
1/2 of load frequency or less.
OFF Response Time
1/2 of load frequency or less.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
200 mA 5 VDC max.
Fuse Rating
3 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
400 g max.
Dimensions
B-shape
Circuit Configuration OUT L Output indicator
OUT L
Internal circuit
Fuse
COM 250 VAC max.
Fuse: 3 A 250 V (5.2-dia.x20) MF51SH (JIS)
Note No blown fuse detector circuit is provided.
Terminal Connections
1 L
3 L L L
5 7 9
L
11 L
250 VAC max. (0.3 A max., 2 A/Unit)
B0 A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM
A8
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
NC
B7
NC
B8
NC
B9
NC
L L L L L L
77
Page 92
Appendix B
Specifications
Triac Output Unit C200H-OA121-E Max. switching capacity
1 A 120 VAC, 50/60 Hz (4 A/Unit)
Min. switching capacity
10 mA (resistive load)/40 mA (inductive load) 10 VAC
Leakage Current
3 mA (100 VAC) max.
Residual Voltage
1.2 V max.
ON Response Time
1 ms max.
OFF Response Time
1/2 of load frequency or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration OUT Output LED indicator
OUT
Internal circuit
Fuse
L
L
COM 120 VAC max.
Fuse blowout detection circuit F LED Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.
Terminal Connections L
A0 A1 L A2 L A3 L A4 L A5 L A6 L A7 COM A8 NC A9 L
120 VAC max (1 A max. 4 A/Unit)
78
0 1 2 3 4 5 6 7
Page 93
Appendix B
Specifications
Triac Output Unit C200H-OA122-E Max. Switching Capacity
1.2 A 120 VAC, 50/60 Hz (4 A/Unit)
Max. Inrush Current
15 A (pulse width: 100 ms) 30 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max.
Min. Switching Capacity Leakage Current Residual Voltage ON Response Time
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to 50 mA) 1 ms max.
OFF Response Time
1/2 of load frequency+1 ms or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
E-shape
Circuit Configuration OUT L OUT
Output indicator
L
Internal circuit
Fuse
COM 120 VAC max.
Fuse blowout detection circuit
F indicator Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections
120 VAC max. (1.2 A max. 4 A/Unit)
L
0
A0
L
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
COM
A8
NC
A9
79