Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 10 of 18

SYSMAC Programmable Controllers C200H (CPU01-E/03-E/11-E) Installation Guide, pages 84 to 93

Pages 84 to 93 of 173

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-CPU01-E

Page 84

Appendix B

Specifications

AC Input Unit C200H-IA222/IA222V Rated Input Voltage

200 to 240 VAC 50/60 Hz

Operating Input Voltage

170 to 264 VAC 50/60 Hz

Input Impedance

21 kW (50 Hz), 18 kW (60 Hz)

Input Current

10 mA typical (at 200 VAC)

ON Voltage

120 VAC min.

OFF Voltage

40 VAC max.

ON Response Time

35 ms max. (at 200 VAC, 25°C)

OFF Response Time

55 ms max. (at 200 VAC, 25°C)

No. of Circuits

1 (16 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

IA222: 300 g max. IA222V: 400 g max.

Dimensions

B-shape

Circuit Configuration IN

0.15 mF 680 W (IA222) IN

200 to 240 VAC 680 kW 910 W

COM

Input LED indicator

Terminal Connections

1 3 5 100 to 120 VAC

7 9 11 13 15 COM

70

B0 A0 A1 A2 A3 A4 A5 A6 A7 A8

0

B1

2

B2

4

B3

6

B4

8

B5 10 B6 12 B7 14 B8

NC

B9

NC

Internal circuit

Page 85

Appendix B

Specifications

No-Voltage Contact Input Unit C200H-ID001 Input Voltage

No-voltage contact/NPN output type (negative common)

Input Impedance

3 kW

Input Current

7 mA typical

ON Voltage

(14.4 VDC min.)

OFF Voltage

(5.0 VDC max.)

ON Response Time

1.5 ms max. (no-voltage contact, at 25°C)

OFF Response Time

1.5 ms max. (no-voltage contact, at 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration Current

IN

IN

3 kW 0.01 mF

COM

Internal circuit

1.8 kW

Input LED indicator

0.3 A 24 VDC Power supply

+ Internal 24 VDC – power supply CPU, Expansion I/O Power Supply, Remote I/O Slave Unit

Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.

Terminal Connections 0 1 2 3 Current (NPN output)

4 5 6 7 COM NC

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

71

Page 86

Appendix B

Specifications

No-Voltage Contact Input Unit C200H-ID002 Input Voltage

No-voltage contact/NPN output type (positive common)

Input Impedance

3 kW

Input Current

7 mA typical

ON Voltage

(14.4 VDC min.)

OFF Voltage

(5.0 VDC max.)

ON Response Time

1.5 ms max. (no-voltage contact, at 25°C)

OFF Response Time

1.5 ms max. (no-voltage contact, at 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration IN

IN

3 kW 0.01 mF

COM

1.8 kW

Internal circuit

Current

Input LED indicator

0.3 A 24 VDC Power supply

+ Internal 24 VDC – power supply CPU, Expansion I/O Power Supply, Remote I/O Slave Unit

Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.

Terminal Connections 0 1 2 3 Current (PNP output)

4 5 6 7 COM NC

72

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

Page 87

Appendix B

Specifications

DC Input Unit C200H-ID211 Rated Input Voltage

12 to 24 VDC

Operating Input Voltage

10.2 to 26.4 VDC

Input Impedance

2 kW

Input Current

10 mA (at 24 VDC)

ON Voltage

10.2 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time

1.5 ms max. (at 24 VDC, 25°C)

OFF Response Time

1.5 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (8 point/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration IN

IN

2 kW 0.01 mF

COM

Internal circuit

1.8 kW

12 to 24 VDC

Input LED indicator

Terminal Connections 0 1 2 3 12 to 24 VDC

4 5 6 7 COM

NC

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

73

Page 88

Appendix B

Specifications

DC Input Unit C200H-ID212 Rated Input Voltage

24 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Input Impedance

3 kW

Input Current

7 mA (at 24 VDC)

ON Voltage

14.4 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

1.5 ms max. (at 24 VDC, 25°C)

OFF Response Time

1.5 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (16 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

300 g max.

Dimensions

B-shape

Circuit Configuration IN

IN

3 kW 0.01 mF

COM

Internal circuit

1.8 kW

24 VDC

Input LED indicator

Terminal Connections

1 3 5 7 24 VDC

9 11 13 15 COM

74

A0 A1 A2 A3

B0

0

B1

2

B2

4

B3

6

B4

8

A4

B5 10

A5

B6 12 B7 14

A6 A7 A8

B8

NC

B9

NC

Page 89

Appendix B

Specifications

AC/DC Input Unit C200H-IM211 Rated Input Voltage

12 to 24 VDC

Operating Input Voltage

10.2 to 26.4 VDC

Input Impedance

2 kW

Input Current

10 mA typical (at 24 VDC)

ON Voltage

10.2 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time

15 ms max. (at 24 VDC, 25°C)

OFF Response Time

15 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration IN

IN

2 kW 0.01 mF

COM

1.8 kW

Internal circuit

12 to 24 VAC/DC Input LED indicator

Terminal Connections 0 1 2 3 12 to 24 VAC/DC

4 5 6 7 COM

NC

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

75

Page 90

Appendix B

Specifications

AC/DC Input Unit C200H-IM212 Rated Input Voltage

24 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Input Impedance

3 kW

Input Current

7 mA typical (at 24 VDC)

ON Voltage

14.4 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

1.5 ms max. (at 24 VDC, 25°C)

OFF Response Time

1.5 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (16 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

250 g max.

Dimensions

B-shape

Circuit Configuration IN

IN

3 kW 0.01 mF

COM

1.8 kW

Internal circuit

24 VAC/DC Input LED indicator

Terminal Connections

1 3 5 24 VAC/DC

7 9

B0 A0 A1 A2 A3 A4

0

B1

2

B2

4

B3

6

B4

8

B5 10 11 A5 B6 12 13 A6 B7 14 15 A7 B8 NC COM A8 B9 NC

76

Page 91

Appendix B

Specifications

Triac Output Unit C200H-OA222V Max. Switching Capacity

0.3 A 250 VAC, 50/60 Hz (2 A/Unit)

Min. Switching Capacity Leakage Current

10 mA (resistive load)/40 mA (inductive load) 10 VAC 3 mA (100 VAC) max./6 mA (200 VAC) max.

Residual Voltage

1.2 V max.

ON Response Time

1/2 of load frequency or less.

OFF Response Time

1/2 of load frequency or less.

No. of Circuits

1 (12 points/common)

Internal Current Consumption

200 mA 5 VDC max.

Fuse Rating

3 A 250 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

400 g max.

Dimensions

B-shape

Circuit Configuration OUT L Output indicator

OUT L

Internal circuit

Fuse

COM 250 VAC max.

Fuse: 3 A 250 V (5.2-dia.x20) MF51SH (JIS)

Note No blown fuse detector circuit is provided.

Terminal Connections

1 L

3 L L L

5 7 9

L

11 L

250 VAC max. (0.3 A max., 2 A/Unit)

B0 A0 A1 A2 A3 A4 A5

NC

A6

NC

A7

COM

A8

0

B1

2

B2

4

B3

6

B4

8

B5

10

B6

NC

B7

NC

B8

NC

B9

NC

L L L L L L

77

Page 92

Appendix B

Specifications

Triac Output Unit C200H-OA121-E Max. switching capacity

1 A 120 VAC, 50/60 Hz (4 A/Unit)

Min. switching capacity

10 mA (resistive load)/40 mA (inductive load) 10 VAC

Leakage Current

3 mA (100 VAC) max.

Residual Voltage

1.2 V max.

ON Response Time

1 ms max.

OFF Response Time

1/2 of load frequency or less.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

140 mA 5 VDC max.

Fuse Rating

5 A 125 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

250 g max.

Dimensions

A-shape

Circuit Configuration OUT Output LED indicator

OUT

Internal circuit

Fuse

L

L

COM 120 VAC max.

Fuse blowout detection circuit F LED Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)

Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.

Terminal Connections L

A0 A1 L A2 L A3 L A4 L A5 L A6 L A7 COM A8 NC A9 L

120 VAC max (1 A max. 4 A/Unit)

78

0 1 2 3 4 5 6 7

Page 93

Appendix B

Specifications

Triac Output Unit C200H-OA122-E Max. Switching Capacity

1.2 A 120 VAC, 50/60 Hz (4 A/Unit)

Max. Inrush Current

15 A (pulse width: 100 ms) 30 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max.

Min. Switching Capacity Leakage Current Residual Voltage ON Response Time

1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to 50 mA) 1 ms max.

OFF Response Time

1/2 of load frequency+1 ms or less.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

180 mA 5 VDC max.

Fuse Rating

5 A 125 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

300 g max.

Dimensions

E-shape

Circuit Configuration OUT L OUT

Output indicator

L

Internal circuit

Fuse

COM 120 VAC max.

Fuse blowout detection circuit

F indicator Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)

Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.

Terminal Connections

120 VAC max. (1.2 A max. 4 A/Unit)

L

0

A0

L

1

A1

L

2

A2

L

3

A3

L

4

A4

L

5

A5

L

6

A6

L

7

A7

COM

A8

NC

A9

79