Page 74
Appendix A
Inspection and Maintenance 1, 2, 3...
1. Turn OFF the power to the PC. 2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block. 3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.
4. Remove the screw from the top of the Unit (Phillips screwdriver). 5. Detach the case from the Unit (flat-blade screwdriver).
6. Pull out the printed circuit board. 7. Insert a new fuse. A spare fuse is provided inside the rear of the case when the Unit is delivered. 8. Reassemble in reverse order of assembly.
Output Unit Relays To replace a Relay, follow the steps below:
1, 2, 3...
1. Turn OFF the power to the PC. 2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block.
60
Page 75
Appendix A
Inspection and Maintenance
3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.
4. Remove the screw from the top of the Unit (Phillips screwdriver). 5. Detach the case from the Unit (flat-blade screwdriver).
6. Pull out the printed circuit board. The Relays are placed on the PC boards of individual Units as shown in the figures below.
OC221/OC224
0 1 2 3 4 5 6 7
61
Page 76
Appendix A
Inspection and Maintenance
OC222
0 1 2 3 4 6 8 10
5 7 9 11
OC223
0 1 2 3 4
OC225 8 9 10 11 12 13 14 15
0 1 2 3 4 5 6 7
7. A Relay puller is provided inside the rear of the case when the Unit is delivered. Use the Relay puller to pull out the Relay as shown below. Insert a new Relay.
Relay puller Using the Relay puller, pull the relay up and out of the socket.
Printed circuit board
8. Reassemble in reverse order of assembly.
62
Page 77
Appendix A
Inspection and Maintenance
Batteries Some RAM Packs use a battery (refer to Appendix B for specifications). When the battery is nearly discharged, the ALARM indicator blinks and the message “BATT FAIL” appears on the Programming Console. When this occurs, replace the battery within one week to avoid loss of data. The battery comes together with its connector as a set. To replace the Battery Set, follow the steps below. The entire replacement must be completed within five minutes to ensure that the data will not be lost. If you are using model C200H-CPU11-E as the CPU, the battery is installed in the Unit upon delivery.
1, 2, 3...
1. Turn OFF the power to the PC. (If the power was not already ON, turn the power ON for at least one minute before turning the power OFF.) 2. Remove the cover from the battery compartment of the RAM Pack. 3. Remove the old Battery Set. 4. Install the new Battery Set as shown shown in the following diagram.
Battery connector Battery Set
5. Replace the cover of the battery compartment. 6. Press CLR, FUN, MONTR, MONTR or just turn the power to the PC OFF and then ON again to clear the error message on the Programming Console.
63
Page 78
Page 79
Appendix B Specifications
The following series of figures and tables provides a complete set of specifications for each Unit of the C200H. Note that I/O Units may take on one of three different shapes. Thus I/O Units are sometimes referred to as A-shape I/O Units, B-shape, or E-shape I/O Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these three shapes of I/O Unit.
General Specifications Item
C200H-CPU01-E, CPU11-E/PS221
C200H-CPU03/PS211
Supply Voltage
100 to 120/200 to 240 VAC selectable 50/60 Hz
24 VDC
Operating Voltage Range
85 to 132/170 to 264 VAC
20.4 to 26.4 VDC
Power Consumption
120 VA max. per Rack (Backplane)
40 W max. per Rack (Backplane)
Surge Current
Approx. 5 times the normal current
Output Capacity
CPU Rack: 3 A 5 VDC (1.6 A supplied to I/O Units) Refer to Section 4-4 Special Considerations for C200H-CPU11 Expansion I/O Unit Rack: 3 A 5 VDC (2.7 A supplied to I/O Units)
Fuse
2 A 250 V 5.2 dia. x 20 (MF51NR)
2 A 125 V 5.2 dia. x 20 (MF51NR)
24 VDC Output
0.3 A 24 VDC +10%/–20%
None
Dielectric Strength
2,000 VAC 50/60 Hz for 1 minute between See Caution. AC terminals and housing 500 VAC 50/60 Hz for 1 minute between DC terminals and housing leakage current: 10 mA max. 1,000 Vp-p, pulse width: 100 ns to 1 ms, rise time: 1 ns
Noise Immunity Vibration
Mechanical durability: 10 to 35 Hz, 1 mm double amplitude (24.5 m/s2) in X, Y, and Z directions, for 2 hours each (When mounted on DIN Rail, 16.7 Hz, 1 mm double amplitude (4.9 m/s2) in X, Y, and Z directions, for 1 hour each) Malfunction durability: 2 to 55 Hz, 19.6 m/s2, in X, Y, and Z directions, for 20 minutes each (When mounted on DIN Rail, 2 to 55 Hz, 2.94 m/s2, in X, Y, and Z directions, for 20 minutes each)
Shock
98 m/s2 in X, Y, and Z directions, 3 times each
Ambient Temperature
Operating: 0° to 55°C (0° to 45°C for Programming Console) Storage: –20° to 65°C
Humidity
35 to 85% RH (without condensation)
Atmosphere
Must be free of the following: • Corrosive gases • Abrupt temperature changes • Direct sunlight • Dust, salt, or metal filings • Water, oil, or chemicals
Grounding
Less than 100 W
Degree of Protection
Mounted in a panel
Weight
6 kg max.
! Caution
When conducting an insulation resistance or dielectric strength test, disconnect the power supply terminals from the LG and GR terminals. Do not conduct a dielectric strength test on the C200HCPU03-E, PS211, RT002-P, or RT202 Units. The power supply input line and internal circuit of the 24 VDC Power Supply are not isolated from each other. If a dielectric strength test is conducted, the Power Supply will be damaged.
65
Page 80
Appendix B
Specifications
CPU Specifications Main Control Element
MPU, CMOS, LS-TTL
Programming Method
Ladder diagram
Instruction Length
1 address/instruction, 1 to 4 words/instruction
Number of Instructions C200H-CPU11
145 (12 basic instructions + 133 special instructions) 159 (12 basic instructions + 147 special instructions)
Execution Time
Basic instructions: 0.75 to 2.25 ms
Memory Capacity
6,974 words (with 8k-word memory)
I/O bits
480 (00000 through 02915)
I/O Units mounted Special I/O Units to Remote I/O Slave 1,600
Optical I/O Units and I/O Terminals 512
IR bits
3,296 (03000 through 23515)
Racks 800 (05000 through 09915)
(20000 through 23115)
SR bits
312 (23600 through 25507)
TR bits
8 (TR 0 through 7)
HR bits
1,600 (HR 0000 through 9915)
AR bits
448 (AR 0000 through 2715
LR bits
1,024 (LR 0000 through 6315)
Timers/Counters
512 (TIM/CNT 000 through 511) TIMHs: 0 through 99.99 s
DM words
Read/write: 1,000 (DM 0000 through 0999) Read only: 1,000 (DM 1000 through 1999)
RUN Output
Memory Protection
Self-diagnostic Functions
Program Check
66
Special instructions: 34 to 724 ms
(10000 through 19915)
TIMs: 0 through 999.9 s CNT: 0 through 9999 counts DM area is in Memory Pack.
Contacts are closed while PC is in RUN mode and operating. Max. switching capacity: 2A 250 VAC (resistive load) 0.5 A 250 VAC (inductive load, cos of phase angle = 0.4) 2 A 24 VDC Status of HR bits, AR bits, preset value of counters (CNT), and contents of data memory (DM) are retained during power failure. Length of memory protection depends on the Memory Pack model being used (refer to Section 2-6 Memory Packs). CPU failure (watchdog timer) Battery failure Cycle time error Memory failure I/O bus failure Host Link error Remote I/O error, etc. Program check (executed on start of RUN operation): END missing Instruction errors (Program can be checked by Programming Console or GPC at three levels.)
Page 81
Appendix B
Specifications
AC Input Unit C200H-IA121 Rated Input Voltage
100 to 120 VAC 50/60 Hz
Operating Input Voltage
85 to 132 VAC 50/60 Hz
Input Impedance
9.7 kW (50 Hz), 8 kW (60 Hz)
Input Current
10 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Response Time
35 ms max. (at 100 VAC, 25°C)
OFF Response Time
55 ms max. (at 100 VAC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration IN
100 to 120 VAC
IN
0.33 mF 470 W 330 kW 910 W
COM
Internal circuit
Input LED indicator
Terminal Connections 0 A0 1 2 100 to 120 VAC
3 4 5 6 7 COM
NC
A1 A2 A3 A4 A5 A6 A7 A8 A9
67
Page 82
Appendix B
Specifications
AC Input Unit C200H-IA122/IA122V Rated Input Voltage
100 to 120 VAC 50/60 Hz
Operating Input Voltage
85 to 132 VAC 50/60 Hz
Input Impedance
9.7 kW (50 Hz), 8 kW (60 Hz)
Input Current
10 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Response Time
35 ms max. (at 100 VAC, 25°C)
OFF Response Time
55 ms max. (at 100 VAC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
IA122: 300 g max. IA122V: 400 g max.
Dimensions
B-shape
Circuit Configuration IN
100 to 120 VAC
IN
0.33 mF 470 W 330 kW 910 W
COM
Input LED indicator
Terminal Connections
1 3 5 100 to 120 VAC
7 9 11 13 15 COM
68
B0 A0 A1 A2 A3 A4 A5 A6 A7 A8
0
B1
2
B2
4
B3
6
B4
8
B5 10 B6 12 B7 14 B8
NC
B9
NC
Internal circuit
Page 83
Appendix B
Specifications
AC Input Unit C200H-IA221 Rated Input Voltage
200 to 240 VAC 50/60 Hz
Operating Input Voltage
170 to 264 VAC 50/60 Hz
Input Impedance
21 kW (50 Hz), 18 kW (60 Hz)
Input Current
10 mA typical (at 200 VAC)
ON Voltage
120 VAC min.
OFF Voltage
40 VAC max.
ON Response Time
35 ms max. (at 200 VAC, 25°C)
OFF Response Time
55 ms max. (at 200 VAC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration IN 0.15 mF
820 W (IA221)
IN 200 to 240 VAC 680 kW 910 W
COM
Internal circuit
Input LED indicator
Terminal Connections 0 A0 1 2 100 to 120 VAC
3 4 5 6 7 COM
NC
A1 A2 A3 A4 A5 A6 A7 A8 A9
69