Page 64

Section

Preventing Noise

5-4

If the I/O wiring and power cables must be placed in the same duct (for example, where they are connected to the equipment), they must be shielded from each other using grounded metal plates. Metal plate (iron) 200 mm min. 1

2

3

Grounding at resistance of less than 100 W

Where:

5-4

1 = I/O wiring 2 = General control wiring 3 = Power cables

Preventing Noise In order to prevent noise from interfering with the operation of the PC, use AWG 14 twisted-pair cables (cross-sectional area of at least 2 mm2). Avoid mounting the PC close to high-power equipment, and make sure the point of installation is at least 200 mm away from power cables as shown in the following diagram. Power lines

200 mm min. PC 200 mm min.

Whenever possible, use wiring conduit to hold the I/O wiring. Standard wiring conduit should be used, and it should be long enough to completely contain the I/O wiring and keep it separated from other cables.

50

Page 65

SECTION 6 Power Considerations Use a commercially available 100 to 120 VAC, 200 to 240 VAC, or 24 VDC power source, according to the model of PC you are using (refer to Appendix B Specifications). Expansion I/O Racks, if used, must also be connected to the power source. If possible, use independent power sources for the PC, input devices, and output devices. All Racks of the PC may be connected to one power source. 6-1 6-2 6-3 6-4

Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Emergency Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

51

Page 66

Section

Emergency Stop

6-1

6-3

Grounding The Line Ground (LG) terminal is a noise-filtered neutral terminal that does not normally require grounding. If electrical noise is a problem, however, this terminal should be connected to the Ground (GR) terminal. To avoid electrical shock, attach a grounded (earth ground) AWG 14 wire (crosssectional area of at least 2 mm2) to the GR terminal. The resistance to ground must be less than 100 W. Do not use a wire longer than 20 m. Care must be taken, because ground resistance is affected by environmental conditions such as soil composition, water content, time of year, and the length of time since the wire was laid underground. PC operation may be adversely affected if the ground wire is shared with other equipment, or if the ground wire is attached to the metal structure of a building. When using an Expansion I/O Rack, the Rack must also be grounded to the GR terminal. The same ground can be used for all connections.

6-2

Insulation If a separate ground is being supplied to different Racks, Insulating Plates must be used to insulate the Racks from each other. Insulating Plates are supplied as an accessory (refer to Appendix B Specifications).

6-3

Emergency Stop An external relay should be used to form an emergency stop circuit that turns the power to the PC OFF in the event of an emergency. An emergency stop routine in the PC program is not sufficient to ensure safety. The circuit shown below is an example of an emergency stop circuit.

MCB1 Power section

MCB2

CR1 Control section

Transformer or noise filter PC

Twisted DC voltage regulator PC RUN output

DC input/output

CR1

52

Surge suppressor

+ -

Page 67

Section

Wiring Power Failure

6-4

A sequential circuit is built into the PC to handle power interruptions. This circuit prevents malfunctions due to momentary power loss or voltage drops. A timing diagram for the operation of this circuit is shown below. The PC ignores all momentary power failures if the interruption lasts no longer than 10 ms. If the interruption lasts between 10 and 25 ms, the interruption may or may not be detected. If the supply voltage drops below 85% of the rated voltage for longer that 25 ms (less for the DC Power Supply), the PC will stop operating and the external outputs will be automatically turned OFF. Operation is resumed automatically when the voltage is restored to more than 85% of the rated value.

6-4

Wiring The following diagrams show the proper way to connect the power source to the PC. The terminals marked “NC” are not connected internally.

C200H-CPU01-E/CPU11-E Screw (3.5 mm head with self-raising pressure plate)

Breaker 1:1 isolation transformer

Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC leave them open. C200H-PS221 Screw (3.5 mm head with self-raising pressure plate) Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC, leave them open.

AC Power Supply Wiring

Isolation transformer • Noise between the PC and ground can be significantly reduced by connecting a 1-to-1 isolation transformer. Do not ground the secondary coil of the transformer.

AC power source

• Supply 100 to

120 or 200 to 240 VAC • Keep voltage fluctuations within the specified range (refer to Appendix B Specifications)

Power line • Use AWG 14 twisted pair cable (cross-sectional area of 2 mm2 min).

Use 1.25-mm2 cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit.

53

Page 68

Section

Wiring ! Caution

6-4

Tighten the AC Power Supply terminals on the terminal blocks to the torque of 0.8 N S m. Insufficient tightening may cause short-circuiting, malfunction, or burning.

C200H-CPU03-E Screw (3.5 mm head with self-raising pressure plate)

Breaker

• Supply 24 VDC • Keep voltage fluctuations within the specified range (refer to Appendix B Specifications)

C200H-PS211 Screw (3.5 mm head with self-raising pressure plate) Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC, leave them open.

Power Supply Wiring

54

Power line • Use AWG 14 twisted pair cable (cross-sectional area of 2 mm2 min).

Use 1.25-mm2 cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit. Tighten the terminals on the terminal blocks to the torque of 0.8 N S m.

Page 69

SECTION 7 Safety Considerations There are certain safety requirements to be considered when installing the PC. Some of these, such as the emergency stop circuit (refer to Section 2-4 Power Supply), are part of the initial wiring. The considerations described below should be kept in mind when operating the PC and when connecting I/O devices to the PC. 7-1 7-2

Interlock Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

55

Page 70

Section

Wiring

7-1

7-2

Interlock Circuits When the PC controls an operation such as the clockwise and counterclockwise operation of a motor, provide an external interlock such as the one shown below to prevent both the forward and reverse outputs from turning ON at the same time. Interlock circuit

00501

MC2 MC1 Motor clockwise

PC 00502

MC1 MC2 Motor counterclockwise

This circuit prevents outputs MC1 and MC2 from ever both being ON at the same time. Even if the PC is programmed improperly or malfunctions, the motor is protected.

7-2

Wiring

Power Supply Output

The 24 VDC output of the CPU and Expansion I/O Power Supply may be used to power other devices. The output current of these supplies is limited to 0.3 A. A separate power supply must be provided if the devices being powered require a higher current.

Input Leakage Current

When two-wire sensors, such as photoelectric sensors, proximity sensors, or limit switches with LEDs, are connected to the PC as input devices, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below. Input power supply

Bleeder resistor

R

PC

Sensor

If the leakage current is less than 1.3 mA, there should be no problem. If the leakage current is greater than 1.3 mA, determine the value and rating for the bleeder resistor using the following formulas. I = leakage current in mA 7.2 kW max. R = –––––– 2.4 x I – 3 2.3 W = ––– W min. R

56

Page 71

Section

Wiring Output Leakage Current

7-2

If there is a possibility of leakage current causing a transistor or triac to malfunction, connect a bleeder resistor across the output as shown below. OUT

L

R Load power supply

PC Bleeder resistor COM

Determine the value and rating for the bleeder resistor using the following formula. R

Eon ––– I

Where Eon = ON voltage of the load I = leakage current in mA R = bleeder resistance Output Surge Current

When connecting a transistor or triac Output Unit to an output device having a high surge current (such as an incandescent lamp), care must be taken to avoid damage to the Output Unit. The transistor and triac Output Units are capable of withstanding a surge current of ten times the rated current. If the surge current for a particular device exceeds this amount, use the circuit shown below to protect the Output Unit.

L

OUT

+ R COM

Another way of protecting the Output Unit lets the load draw a small current (about one third the rated current) while the output is OFF, significantly reducing the surge current. This circuit (shown below) not only reduces the surge current, but also reduces the voltage across the load at the same time. R OUT

L

+ COM

Transistor Output Residual Voltage

When connecting TTL circuits to transistor Output Units, it is necessary to connect a pull-up resistor and a CMOS IC between the two. This is because of the residual voltage left on the transistor output after the output turns OFF.

57

Page 72

Section

Wiring Inductive Load Surge Suppressor

7-2

When an inductive load is connected to an I/O Unit, it is necessary to connect a surge suppressor or diode in parallel with the load as shown below. This is so that the back EMF generated by the load will be absorbed. OUT

L

Relay Output Unit Triac Output Unit Surge suppressor COM OUT

L

+

Relay Output Unit Transistor Output Unit Diode COM

Electrical Noise

Be sure to take appropriate measures when any electrical device likely to produce noise is connected to the PC as a load. Devices generating noise of more than 1,200 V (such as electromagnetic relays and valves) require noise suppression. For noise sources running off of AC power, connect a diode in parallel with the coil of each device. When mounting a CPU Rack and an Expansion I/O Rack together on a mounting plate, be sure to provide a solid ground the mounting plate. The mounting plate must be plated with a highly conductive surface in order to ensure noise immunity.

58

Page 73

Appendix A Inspection and Maintenance Certain consumable items in a PC (such as fuses, Relays, or batteries) need occasional replacement. This Appendix explains how to replace each of these items. Refer to Appendix B for the specifications of individual consumable items. Always keep spare items on hand so that they can be used as immediate replacements when needed.

CPU and Power Supply Fuses

Turn counterclockwise to remove, clockwise to attach

Standard screwdriver

To replace a fuse, follow the steps below:

1, 2, 3...

1. Turn OFF the power to the PC. 2. Remove the fuse holder by turning it approximately 50° counterclockwise with a standard screwdriver. 3. Remove the fuse from the holder. 4. Insert a new fuse. 5. Reattach the fuse holder by turning it approximately 50° clockwise with a standard screwdriver.

Output Unit Fuses To replace a fuse, follow the steps below. Use only UL/CSA certified replacement fuses. Fuse Specifications (5.2-dia. x 20) Model

F indicator (fuse blowout detection circuit)

Rating

C200H-OD411

Yes

5 A 125 V

C200H-OD211

No

C200H-OD212

No

C200H-OD213

Yes

C200H-OA121-E

Yes

C200H-OA122-E

Yes

C200H-OA222V

No

3 A 250 V

C200H-OA223

Yes

5 A 250 V

C200H-OA224

No

3.15 A 250 V

8 A 125 V 5 A 125 V

59