Page 54
Section
I/O Connections
4-4
4-4
I/O Connections Connect the I/O Devices to the I/O Units using AWG 22 (cross-sectional area of 0.3 mm2) for 19-terminal terminal blocks and AWG 22 to 18 lead wire (cross-sectional area of 0.3 to 0.75 mm2) for 10 terminal terminal blocks. The terminals have screws with 3.5-mm diameter heads and self-raising pressure plates. Connect the lead wires to the terminals as shown below. Tighten the screws with a torque of 0.8 N S m.
If you wish to attach solderless type terminals to the ends of the lead wires, use terminals having the dimensions shown below.
7 mm max.
Terminal Block
7 mm max.
The terminal block of an I/O Unit can be removed by loosening the mounting screws. You do not have to remove the lead wires from the terminal block in order to remove it from an I/O Unit.
Locks for terminal block. Unlock to remove the terminal block from the I/O Unit. Make sure the terminal block is locked securely after wiring is complete.
40
Page 55
Section
I/O Connections I/O Unit Cover
4-4
A C200H-COV11 Cover is provided as an I/O Unit cover for Units that use 10P terminal block connectors. After the I/O wiring has been completed, slide the cover up from the bottom, as shown in the illustration below.
Attach
Remove
DC Two-wire Sensor Connection Precautions
I/O Unit cover
If a two-wire sensor is used with a 12-VDC or 24-VDC input device, make sure that the following conditions are satisfied. Malfunctions will occur if these conditions are not satisfied. • The relationship between the PC ON voltage and the sensor residual voltage is as follows: VON x VCC – VR • The relationship between the PC ON current and the sensor control output (load current) is as follows: IOUT (min) x ION x IOUT (max) ION = (VCC – VR – 1.5 (PC internal residual voltage))/RIN Connect R bleeder resistance if ION is less than IOUT (min). The constant for bleeder resistance is determined by the following equation. R x (VCC – VR)/(IOUT (min) – ION) Power W y (VCC – VR)2/R 4 (margin) • The relationship between the PC OFF current and sensor leakage current is as follows: IOFF x Ileak Refer to the information on input and output leakage current on page 56 for details. The value of IOFF depends on the Unit used. For Input Units that have an unspecified OFF current, however, the value of IOFF is always 1.8 mA. DC Input Unit
Two-wire sensor
VR
R
RIN
VCC
Wiring Examples
VCC:
Power supply voltage
VR:
Sensor output residual voltage
VON:
PC ON voltage
IOUT:
Sensor control output (load current)
ION:
PC OFF current
Ileak:
Sensor leakage current
IOFF:
PC OFF current
R:
Bleeder resistance
RIN:
PC input impedance
The following are examples of how to connect I/O devices to I/O Units. During wiring, work slowly and carefully. If an input device is connected to an Output Unit, damage may result. Check all I/O devices to make sure they meet the specifications (refer to Appendix B Specifications).
41
Page 56
Section
I/O Connections
4-4
DC Input Units Contact output
IN
DC input
COM
When using the configuration shown below, the sensor and Input Unit should receive their power from the same supply. NPN current output + Current regulator
IN
Output 7 mA 0V
Sensor Power Supply
DC input
COM
NPN open-collector output +
Sensor Power Supply DC input
IN
Output 7 mA
COM
0V PNP current output +
Sensor Power Supply
Output
AC/DC input
IN
7 mA 0V
COM
0V
The circuit below should be used for I/O devices having a voltage output. Voltage output + COM Output 0V
IN
DC input
Sensor Power Supply
The circuit below should NOT be used for I/O devices having a voltage output. Voltage output + Output 0V
42
Sensor Power Supply IN COM
DC input
Page 57
Section
I/O Connections
4-4
AC Input Units Contact output
IN
AC input
COM
AC Switching IN Prox. switch main circuit
! Caution
Output Units
AC input
COM
When using Reed switch as the input contacts for AC Input Units, be sure the allowable current of the switch is at least 1 A. Using switches with lower capacities may cause the contacts to fuse due to surge current. A fuse placed in the output circuit will protect the output element, circuit board, etc., in the event of a short circuit in the output circuit. Although some transistor Output Units and Triac Output Units have a built-in fuse, it is recommended that you connect an external fuse to each Output Unit for extra safety and ease of maintenance.
43
Page 58
Page 59
SECTION 5 Installation Environment This section details the necessary environment and conditions for installation of the PC. For specific instructions on mounting Units and wiring for I/O and power, refer to Section 2-4 Power Supply and Section 3-3 System Configurations. 5-1 5-2 5-3 5-4
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Duct Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preventing Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
45
Page 60
Section
Installation Environment
5-1
5-1
Installation Environment This section details the necessary environmental conditions for installing the PC. ! Caution
Ambient Conditions
Static electricity can damage PC components. Your body can carry an electrostatic charge, especially when the humidity is low. Before touching the PC, be sure to first touch a grounded metallic object, such as a metal water pipe, in order to discharge any static build-up.
Do not install the PC in any of the following locations. Doing so will affect PC life and may affect operating performance. • Locations subject to ambient temperatures lower than 0°C or higher than 55°C. • Locations subject to drastic temperature changes or condensation. • Locations subject to ambient humidity lower than 10% or higher than 90%. • Locations subject to corrosive or flammable gases. • Locations subject to excessive dust (especially iron dust) or chloride. • Locations that would subject the CPU to direct shock or vibration. • Locations that would subject the PC to water, oil, or chemical reagents. • Locations exposed to direct sunlight.
Cooling
There are two points to consider in order to ensure that the PC does not overheat. The first is the clearance between Racks, and the second is installation of a cooling fan.
Clearance Between Racks
The Racks need to have sufficient room between each other to allow for I/O wiring, and additional room to ensure that the I/O wiring does not hamper cooling. However, the Racks must be mounted close enough to each other that the length of the Connecting Cable between any two Racks does not exceed 10 m, and the total length of the Connecting Cables between all Racks does not exceed 12 m. As a general rule, about 70 to120 mm should be left between any two Racks.
Cooling Fan
A cooling fan is not always necessary, but may be needed in some installations. Try to avoid mounting the PC in a warm area, or over a source of heat. A cooling fan is needed if the ambient temperature may become higher than that specified (refer to Appendix B Specifications). If the PC is mounted in an enclosure, a cooling fan may need to be installed, as shown below, to maintain the ambient temperature within specifications.
Fan
PC Control Panel
46
Page 61
Section
Mounting Requirements
5-2
5-2
Mounting Requirements The PC consists of from one to three Racks. Each Rack must be mounted vertically, that is with the printing on the front panels oriented as it would normally be read. The Racks should be mounted one above the other with the CPU Rack uppermost as shown below.
CPU Rack
These connectors are not used. Cover them with caps.
Expansion Rack
Expansion Rack
The C200H is approved by Underwriters Laboratories under the condition that, “The device must be mounted vertically for ventilation purposes”. DIN Rail Mounting
The PC may be mounted using DIN Rail if desired. This type of mounting is not required, and the PC may be directly mounted to any sturdy support meeting the environmental specifications (refer to Appendix B Specifications). If you want to mount the PC on DIN Rail, you can order a DIN Rail from OMRON (refer to Appendix B Standard Models). DIN Rails come in the two heights shown below.
7.3-mm Height
16-mm Height
47
Page 62
Section
Mounting Requirements DIN Rail Mounting Bracket
5-2
The DIN Rail Mounting Bracket shown below is necessary for mounting the PC to the DIN Rail.
Procedure
1, 2, 3...
1. The following diagram is a view of the back of the Backplane. Attach one Mounting Bracket to the left and right sides of the Backplane as shown below. Backplane
DIN Rail Mounting Bracket There are two Backplane mounting screws each on the left and right sides of the Backplane. Use these screws to attach the DIN Rail Mounting Brackets to the Backplane.
2. Mount the Backplane to the DIN Rail so that the claws on the Mounting Brackets fit into the upper portion of the DIN Rail as shown below. This claw fits into the DIN Rail
DIN Rail
Backplane DIN Rail Mounting Bracket
48
Page 63
Section
Duct Work
5-3
3. Loosen the screws attaching the Mounting Brackets to the Backplane. Slide the Backplane upward as shown below so that the Mounting Bracket and Backplane clamp securely onto the DIN Rail. Tighten the screws.
DIN Rail Mounting Bracket
DIN Rail Hold-down bracket
Projections
5-3
Slide this screw to the top of the projection and then tighten it.
Duct Work If power cables carrying more than 10 A 400 V, or 20 A 220 V must be run alongside the I/O wiring (that is, in parallel with it), at least 300 mm must be left between the power cables and the I/O wiring as shown below.
Low current cable 1 300 mm min. Control cable 2
Power cable
300 mm min.
3
Grounding at resistance of less than 100 W
Where:
1 = I/O wiring 2 = General control wiring 3 = Power cables
49