Page 44
Section
System Configurations
3-3
Special I/O Units
Host Link Unit and Remote I/O Master Unit
I/O Units
Memory Packs
•Up to ten Special I/O
•Up to two Units can be
•I/O Units available with 5, 8,
•RAM, EPROM, or EE-
Units can be mounted. •Mount Special I/O Units to any slot on the CPU Rack (except the two slots to the left of the CPU) or the Expansion I/O Rack.
mounted. •Host Link Units and Remote I/O Master Units can be mounted to any slot on the CPU Rack (except the two slots to the left of the CPU) or the the Expansion I/O Rack.
12, or 16 points. •Units available with 10- or 19-terminal terminal blocks. •Units with 5 and 8 points have 10-terminal terminal blocks and Units with 10 and 12 points have 19-terminal terminal blocks. •There are some restrictions on the mounting position of 19-terminal I/O Units (refer to Appendix B Specifications).
PROM Packs available.
•EEPROM requires an optional EEPROM Chip. •EPROM requires a separately available EPROM Chip.
CPU Built-in power supply I/O Unit Cover For 10-terminal block I/O Units SYSMAC NET LINK Unit and SYSMAC LINK Unit • Use up to two Units, mounted to either of the two slots to the left of the CPU. •When using either of these two Units the use of peripheral devices is limited. Refer to Section 4-3 Maximum Current and Power Supplied.
Backplane 3-, 5-, 8-, 10-slot types available
Expansion I/O Racks Up to two Expansion I/O Racks can be connected to one CPU Rack.
Expansion I/O Power Supply I/O Connecting Cable
•Available in lengths from 30 cm to 1 m. •Total length of I/O Connecting Cables between all Racks must not exceed 12 m.
Remote I/O Slave Unit Up to five Units can be connected.
Backplane 3-, 5-, or 8-slot types available
Remote I/O Slave Unit Power supply built-in Optical Fiber Cable or Wire Cable
30
Page 45
SECTION 4 System Connections In the preceding sections we have covered what all the parts of a PC are and how they should be assembled. This section provides detailed information about the types of considerations involved in making all of the PC connections. Also included in this section are considerations that should be kept in mind when using the C200H-CPU11-E as the CPU. 4-1 4-2 4-3 4-4
IR Word Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maximum Current and Power Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
Page 46
Section
IR Word Allocation
4-1
4-1
IR Word Allocation Each slot of the Backplane is assigned a hardware word number. This word is accessible for I/O use only in the given slot. However, standard I/O Units are available in 5-, 8-, 12-, and 16-point models. If an I/O Unit other than a 16-point model is mounted, the unused points of that word are accessible only as “work bits” (refer to the C200H Operation Manual). The number of I/O bits available for the entire system, therefore, varies according to the model of I/O Units used, as well as the model of Backplanes used. The figure below shows the relationship between the model of I/O Unit and work bits. The shaded bits can only be used as work bits.
32
5-point Unit
8-point Unit
12-point Unit
16-point Unit
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Page 47
Section
IR Word Allocation
4-1
The CPU Rack begins with word 000 at the leftmost slot. The first Expansion I/O Rack begins with word 010, and the second Expansion I/O Rack with word 020. The first word of each Rack is fixed, regardless of the model of Backplane used. As with the I/O bits unused by individual I/O Units, the bits of the I/O words unused by a Backplane can be used as work bits. The following figure shows the relationship between the model of Backplane and I/O words. The shaded bits can only be used as work bits.
C200H-BC031 Backplane Word
000
001
002
003
004
005
006
007
008
009
00
00
00
00
00
00
00
00
00
00
15
15
15
15
15
15
15
15
15
15 bits
C200H-BC051-V1 Backplane Word
000
001
002
003
004
005
006
007
008
009
00
00
00
00
00
00
00
00
00
00
15
15
15
15
15
15
15
15
15
15 bits
C200H-BC081-V1 Backplane Word
000
001
002
003
004
005
006
007
008
009
00
00
00
00
00
00
00
00
00
00
15
15
15
15
15
15
15
15
15
15 bits
Note The C200H-OC225/OD212/OD21A 16-point Output Unit and C200H-B7AO1 1-V1/V2 Backplane. B7A Interface Unit can be mounted only to a C200H-BC For example, if a PC consists of three 8-slot Racks with 8-point I/O Units mounted to all I/O Unit mounting positions, the number of I/O points for the entire PC will be: 8 points x 8 slots x 3 Racks = 192 points If a PC consists of three 8-slot Racks with the I/O Unit mounting positions equally divided between 16-point Input Units and 12-point Output Units, the number of I/O points for the entire PC will be: Input points = 16 points x 4 slots x 3 Racks = 192 points Output points = 12 points x 4 slots x 3 Racks = 144 points Total I/O points = 192 + 144 = 336
33
Page 48
Section
Remote I/O
4-2
The following figure shows the word allocation for a fully expanded C200H with three 8-slot Backplanes.
4-2 word 000 word 001 word 002 word 003 word 004 word 005 word 006 word 007
CPU word 010 word 011 word 012 word 013 word 014 word 015 word 016 word 017
Power Supply word 020 word 021 word 022 word 023 word 024 word 025 word 026 word 027
Power Supply
Remote I/O There are limits to how long the normal wiring between the PC and its Expansion I/O Racks can be. A Remote I/O Unit can extend this distance greatly, so that the PC and its Expansion I/O Racks can even be located in separate buildings. There are two types of Remote I/O Systems, optical and wired. By locating a Rack farther from the CPU Rack, a Remote I/O System eliminates the time and mess in wiring (or changing wiring) to many devices that are separated from the CPU Rack. Although all I/O points must ultimately be wired individually, the question is one of distance: Do you want to wire dozens of terminals all the way across a factory complex or do you want to run a single cable for most of the distance and then wire individual terminals locally? A PC with an Expansion I/O System is called an Expanded PC. I/O words 100 through 199 and DM words 1000 through 1999 are allocated to Special I/O Units. There are limitations to the number and model of Special I/O Units that can be mounted to a Remote I/O Slave Rack. Provided no other models of Special I/O Units are mounted to a Remote I/O Slave Rack, the maximum number of Special I/O Units that can be mounted is shown below for each model. Group
Units
Total number
A
High-speed Counter, Position Control (NC111/NC112), ASCII, Analog I/O, ID Sensor, Fuzzy Logic Unit
4 Units
B
High-density and Mixed I/O, Cam Positioner, Temperature Control, PID Control, Heat/Cool Temperature Control
8 Units
C
Temperature Sensor, Voice
6 Units
D
Position Control (NC221)
2 Units
When using a combination of A, B, C, and D Units on a Remote I/O Slave Rack, the number of each model of Unit being used must satisfy the following two formulas. 3A + B + C + 6D 12 A+B+C+D 8
34
Page 49
Section
Maximum Current and Power Supplied
4-3
In addition, when PC Link Units are used, a maximum of ten Special I/O Units and PC Link Units total can be mounted to one Expanded PC. When a High-density I/O Unit is mounted to a Remote I/O Slave Rack, the RM001-PV1 or RM201 Remote I/O Master Unit must be used.
4-3
Maximum Current and Power Supplied The power supplies, including those built in the CPUs, are limited in the total current they can supply to I/O units. The table below shows the maximum currents supplied by each power supply. There are three categories in the “Maximum current supplied”:
1, 2, 3...
1. The 5-V internal logic current powers I/O Cards and communications cards. Refer to the deductions table to determine what trade-offs must be made when the total I/O and peripherals exceed the CPUs internal logic current capacity. 2. The 26-V relay current powers relay output cards and ID Sensor Units. 3. Finally, the external 24-VDC power supply on the CPU powers external input devices. The total wattage of all three categories cannot exceed the wattage listed in the last column, “Maximum power”. You should not exceed any of the individual current ratings for the voltage supplied by any single unit, nor should you exceed the total maximum power output.
Current Supplied Name
CPU Rack
Model number
C200H-CPU01-E
Max. current supplied
Maximum power
5V (internal logic current)
26 V (relay current)
24 V (No-voltage contact current)
1.6 A
0.6 A
0.8 A
23 W
---
18 W
0.8 A
22 W
0.8 A
28 W
---
23 W
C200H-CPU03-E C200H-CPU11-E
1.4 A
Expansion
C200H-PS221
2.7 A
I/O Rack
C200H-PS211
Slave Rack
C200H-RT001-P
2.7 A
0.6 A
0.8 A
28 W
C200H-RT002-P
0.6 A
---
23 W
C200H-RT201
0.8 A
28 W
C200H-RT202
---
23 W
Note The figures shown in the “maximum current supplied” and “maximum power supplied” columns are computed with the power consumed by the Backplanes, CPU, Memory Cassettes, Peripheral Devices, I/O Power Supply Units, and Slave Units already calculated. Design the system so that the following two conditions are satisfied. Condition 1 (1) (Total current consumption of all Units in the 5-V system) ≤ (the figure in the 5-V column) (2) (Total current consumption of all Units in the 26-V system) ≤ (the figure in the 26-V column) (3) (Total current consumption of all Units in the 24-V system) ≤ (the figure in the 24-V column) Condition 2 (1) x 5 V + (2) x 26 V + (3) x 24 ≤ (maximum power supplied)
35
Page 50
Section
Maximum Current and Power Supplied
4-3
Deductions Table CPU11-E 5-V consumption (I/O card)
CPU01/03-E 5-V consumption (I/O card)
≤ 1.4 A
≤ 1.6 A
None
> 1.4 A, but ≤ 1.7 A
> 1.6 A, but ≤ 1.9 A
PROM Writer and CPU-mounting Host Link Unit
> 1.7 A, but ≤ 1.9 A
> 1.9 A, but ≤ 2.1 A
PROM Writer, CPU-mounting Host Link Unit, Peripheral Interface Unit
> 1.9 A, but ≤ 2.1 A
> 2.1 A, but ≤ 2.3 A
PROM Writer, CPU-mounting Host Link Unit, Peripheral Interface Unit, and Printer Interface Unit
Current Drawn from 5-V Supply
Peripheral device deductions
Unit DC Input
Model number C200H-ID211
Current consumption 0.01 A each
C200H-ID212 No-Voltage Contact
C200H-ID001
Input
C200H-ID002
AC Input
C200H-IA121 C200H-IA122/IA122V C200H-IA221 C200H-IA222/IA222V
AC/DC Input
C200H-IM211 C200H-IM212
Contact Output
C200H-OC221 C200H-OC222 C200H-OC223 C200H-OC224
Transistor Output
C200H-OC225
0.05 A
C200H-OD411
0.14 A
C200H-OD211
0.16 A
C200H-OD212
0.18 A
C200H-OD213
0.14 A
C200H-OD214 C200H-OD216
0.01 A each
C200H-OD217 C200H-OD21A
0.16 A
C200H-OA121-E
0.14 A
C200H-OA122-E C200H-OA223 C200H-OA222V
0.18 A 0.18 A 0.20 A
C200H-OA224
0.27 A
Analog Timer Unit
C200H-TM001
0.06 A
B7A Interface Unit
C200H-B7AI1
0.10 A
Triac Output
C200H-B7AO1 Host Link
0.25 A
C200H-LK201-V1
0.15 A
C200H-LK202-V1
0.25 A
PC Link
C200H-LK401
0.35 A
Remote Master
C200H-RM001-PV1
0.20 A
C200H-RM201
0.25 A
C200HW-SLK13/SLK14/ SLK23/SLK24
0.8 A
SYSMAC LINK Unit
36
C200H-LK101-PV1
Page 51
Section
Maximum Current and Power Supplied Unit
Model number
4-3
Current consumption
SYSMAC NET Link Unit
C200HS-SNT32
1.0 A
Feed Adapter
C200H-APS01/ASP02
0A
TTL Input
C200H-ID501
0.13 A
DC Input
C200H-ID215
TTL Output
C200H-OD501
Transistor Output
C200H-OD215
TTL I/O
C200H-MD501
DC Input/Transistor
C200H-MD115
Output
C200H-MD215
High-speed Counter
C200H-CT001-V1
0.22 A 0.18 A
0.30 A
C200H-CT002 Position Control
Analog Input Analog Output Temperature Control Units
C200H-NC111
0.15 A
C200H-NC112
0.15 A
C200H-NC211
0.50 A
C200H-AD001
0.55 A
C200H-AD002
0.45 A
C200H-DA001 C200H-DA002 C200H-TC001 C200H-TC002 C200H-TC003
0.65 A 0.6 A 0.33 A
C200H-TC101 C200H-TC102 C200H-TC103 Heat/Cool Temperature Control Units
C200H-TV001 C200H-TV002 C200H-TV003
0.33 A
C200H-TV101 C200H-TV102 C200H-TV103 PID Control Units
C200H-PID01 C200H-PID02 C200H-PID03
0.33 A
Temperature Sensor
C200H-TS001/TS002
0.45 A
Input
C200H-TS101/TS102
0.35 A
ASCII
C200H-ASC02
0.15 A
Voice Output
C200H-OV001
0.30 A
ID Sensor
C200H-IDS01-V1
0.25 A
C200H-IDS21 Fuzzy Logic Unit
C200H-FZ001
0.30 A
Cam Positioner
C200H-CP114
0.30 A
Current Drawn from 26-V Supply
Unit
Model number
Contact Output
C200H-OC221/OC222/OC223/ OC224/OC225
Transistor Output
C200H-OD216/OD217
ID Sensor
C200H-IDS01-V1/IDS21
Current consumption 0.075 A*
0.12 A
37
Page 52
Section
Maximum Current and Power Supplied
4-3
Note *With all eight bits on simultaneously. Current Drawn from 24-V Supply
Unit
Model number
No-Voltage Contact Input Units
Calculation Examples
C200H-ID001/ID002
Current consumption 0.06 A
The total power consumption for each Rack can be obtained from the following formulas: CPU Rack =
Total power consumption for each Unit + 7 (8) (VA) 0.6 x 0.55 (1)
7 = CPU power consumption, (8) = Power consumption of the CPU11-E 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when CPU03-E is used.) All other Racks =
Total power consumption for each Unit + 2 0.6 x 0.55 (1)
(VA)
2 = I/O Power Supply Unit (Remote I/O Slave Unit) power consumption 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.) Example 1
Assume that four Contact Output Units, three No-Voltage Contact Input Units, and one Host Link Unit are mounted to a Rack, along with CPU01-E. The following table shows how the total power consumption is calculated. Voltage
Example 2
Current consumption (1) 0.01 x 7 + 0.25 = 0.32 A (≤ 1.6 A)
(1) x 5 V = 1.6 W
26 V
(2) 0.075 x 4 = 0.30 A (≤ 0.6 A)
(2) x 26 V = 7.8 W
24 V
(3) 0.06 x 3 + 0.3 = 0.48 A (≤ 0.8 A)
(3) x 24 V = 11.52 W
Total
---
20.92 W (≤ 23 W)
Assume that six DC Input Units and two High-speed Counter Units are mounted to a Rack, along with the PS221 Power Supply. The following table shows how the total power consumption is calculated. Voltage
Example 3
Current consumption
Power consumption
5V
(1) 0.01 x 6 + 0.3 x 2 = 0.66 A (≤ 2.7 A)
(1) x 5 V = 3.3 W
26 V
(2) 0
(2) 0
24 V
(3) Service power supply = 0.8 A (≤ 0.8A)
(3) x 24 V = 19.2 W
Total
---
22.5 W (≤ 28 W)
Assume that the following Units are mounted to a Rack to which a C200HCPU11-E is mounted. The following table shows how the total power consumption is calculated. Voltage
Current consumption
Power consumption
5V
(1) 0.01 x 6 + 0.18 = 0.24 A (≤ 1.1 A)
(1) x 5 V = 1.2 W
26 V
(2) 0.075 x 4 = 0.30 A(≤0.6 A)
(2) x 26V = 7.8 W
24 V
(3) 0.06 x 2 + 0.3 = 0.42 A(≤0.8 A)
(3) x 24 V = 10.08 W
Total
---
19.08 W (≤ 20.5 W)
• Peripheral Interface Unit (IP006) • SYSMAC LINK Units (SLK22): • Contact Output Units (OC221): • No-Voltage Contact Input Units (ID001):
38
Power consumption
5V
1 6 2
Page 53
Section
Maximum Current and Power Supplied • High-density and Mixed I/O Units (MD215): • Current for MD215: Example 4
1 0.3 A
Assume that the following Units are mounted to a rack to which is mounted the C200H-CPU11-E. The following table shows how the total power consumption is calculated. Voltage
Current consumption
Power consumption
5V
(1) 0.01 x 5 + 0.3 x 1 = 0.35 A (≤ 0.7 A)
(1) x 5 V = 1.75 W
26 V
(2) 0
(2) 0
24 V
(3) Current=0.5 A(≤0.8 A)
(3) x 24 V = 12 W
Total
---
13.75 W (≤ 18.5 W)
• Peripheral Interface Unit (IP006) • SYSMAC NET Link Units (SNT32): • Central Power Supply Adapter (Current 0): • DC Input Units (ID212): • High-speed Counter Units (CT002): • Current for ID212: Calculation of Power Consumption for Each Rack (Examples)
4-3
1 1 5 1 0.5 A
The total power consumption for each Rack can be obtained from the following formulas: • CPU Rack: Total power consumption for each Unit + 7 (8) (VA) 0.6 x 0.55 (1) Where: 7 = Power consumption of the CPU, (8) = Power consumption of the CPU11-E, 0.6 = 60% efficiency, and 0.55 (1) = Power rate (Number in parentheses: when CPU03-E is used.)
• Expansion I/O Power Supply/Remote I/O Slave Unit: Total power consumption for each Unit + 2 0.6 x 0.55 (1)
(VA)
Where: 2 = Power consumption of the I/O Power Supply or Remote I/O Slave Unit, 0.6 = 60% efficiency, and 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.)
39