The text of a manual · part 18 of 60

C200HX/C200HG/C200HE Programmable Controllers Operation Manual, pages 164 to 173

Pages 164 to 173 of 586

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200HE-CPU42-E

Page 164

Section 5-7

Instruction Set Lists Mnemonic

Code

Words

ASFT(@)

17

4

ASYNCHRONOUS SHIFT REGISTER

178

ASL (@)

25

2

ARITHMETIC SHIFT LEFT

175

ASR (@)

26

2

ARITHMETIC SHIFT RIGHT

175

AVG (@)

––

4

AVERAGE VALUE

259

BCD (@)

24

3

BINARY TO BCD

205

BCDL (@)

59

3

DOUBLE BINARY-TO-DOUBLE BCD

206

BCMP (@)

68

4

BLOCK COMPARE

197

BCNT (@)

67

4

BIT COUNTER

312

BIN (@)

23

3

BCD-TO-BINARY

204

BINL (@)

58

3

DOUBLE BCD-TO-DOUBLE BINARY

205

BSET (@)

71

4

BLOCK SET

181

BXF2 (@)

––

4

EM BLOCK TRANSFER

190

CLC (@)

41

1

CLEAR CARRY

229

CMCR (@)

––

4

PCMCIA CARD MACRO

357

CMP

20

3

COMPARE

193

CMPL

60

4

DOUBLE COMPARE

196

CNT

None

2

COUNTER

166

CNTR

12

3

REVERSIBLE COUNTER

169

COLL (@)

81

4

DATA COLLECT

185

COLM(@)

64

4

LINE TO COLUMN

225

COM (@)

29

2

COMPLEMENT

277

CPS

––

4

SIGNED BINARY COMPARE

202

CPSL

––

4

DOUBLE SIGNED BINARY COMPARE

203

DBS (@)

––

4

SIGNED BINARY DIVIDE

255

DBSL (@)

––

4

DOUBLE SIGNED BINARY DIVIDE

256

DEC (@)

39

2

BCD DECREMENT

228

DIFD

14

2

DIFFERENTIATE DOWN

151

DIFU

13

2

DIFFERENTIATE UP

151

DIST (@)

80

4

SINGLE WORD DISTRIBUTE

183

DIV (@)

33

4

BCD DIVIDE

236

DIVL (@)

57

4

DOUBLE BCD DIVIDE

237

DMPX (@)

77

4

16-TO-4/256-TO-8 ENCODER

212

DSW

––

4

DIGITAL SWITCH

343

DVB (@)

53

4

BINARY DIVIDE

248

EMBC (@)

––

2

SELECT EM BANK

321

END

01

1

END

158

FAL (@)

06

2

FAILURE ALARM AND RESET

304

FALS

07

2

SEVERE FAILURE ALARM

304

FCS (@)

––

4

FCS CALCULATE

312

FDIV (@)

79

4

FLOATING POINT DIVIDE

238

FPD

––

4

FAILURE POINT DETECT

314

HEX (@)

––

4

ASCII-TO-HEXADECIMAL

219

HKY

––

4

HEXADECIMAL KEY INPUT

347

HMS (@)

66

4

SECONDS TO HOURS

208

IEMS (@)

––

2

INDIRECT EM ADDRESSING

320

IL

02

1

INTERLOCK

155

ILC

03

1

INTERLOCK CLEAR

155

INC (@)

38

2

INCREMENT

228

INT (@)

89

4

INTERRUPT CONTROL

289

146

Name

Page

Page 165

Section 5-7

Instruction Set Lists Mnemonic

Code

Words

Name

Page

IORD (@)

––

4

SPECIAL I/O UNIT READ

354

IORF (@)

97

3

I/O REFRESH

310

IOWR (@)

––

4

SPECIAL I/O UNIT WRITE

355

JME

05

2

JUMP END

157

JMP

04

2

JUMP

157

KEEP

11

2

KEEP

154

LD

None

1

LOAD

149

LD NOT

None

1

LOAD NOT

149

LINE (@)

63

4

COLUMN TO LINE

224

LMSG (@)

47

4

32-CHARACTER MESSAGE

308

MAX (@)

––

4

FIND MAXIMUM

257

MBS (@)

––

4

SIGNED BINARY MULTIPLY

253

MBSL (@)

––

4

DOUBLE SIGNED BINARY MULTIPLY

254

MCMP (@)

19

4

MULTI-WORD COMPARE

192

MCRO (@)

99

4

MACRO

287

MIN (@)

––

4

FIND MINIMUM

258

MLB (@)

52

4

BINARY MULTIPLY

248

MLPX (@)

76

4

4-TO-16/8-TO-256 DECODER

209

MOV (@)

21

3

MOVE

180

MOVB (@)

82

4

MOVE BIT

187

MOVD (@)

83

4

MOVE DIGIT

188

MPRF (@)

61

4

GROUP-2 HIGH-DENSITY I/O REFRESH

311

MSG (@)

46

2

MESSAGE

307

MTR

––

4

MATRIX INPUT

352

MUL (@)

32

4

BCD MULTIPLY

235

MULL (@)

56

4

DOUBLE BCD MULTIPLY

236

MVN (@)

22

3

MOVE NOT

180

NEG

––

4

2’S COMPLEMENT

226

NEGL

––

4

DOUBLE 2’S COMPLEMENT

227

NOP

00

1

NO OPERATION

158

OR

None

1

OR

149

OR LD

None

1

OR LOAD

150

OR NOT

None

1

OR NOT

149

ORW (@)

35

4

LOGICAL OR

279

OUT

None

2

OUTPUT

150

OUT NOT

None

2

OUTPUT NOT

150

PID (@)

––

4

PID CONTROL

266

PMCR (@)

––

4

PROTOCOL MACRO

339

RECV (@)

98

4

NETWORK RECEIVE

327

RET

93

1

SUBROUTINE RETURN

286

ROL (@)

27

2

ROTATE LEFT

176

ROOT (@)

72

3

SQUARE ROOT

241

ROR (@)

28

2

ROTATE RIGHT

176

RSET

None

2

RESET

153

RXD(@)

––

4

RECEIVE

333

SBB (@)

51

4

BINARY SUBTRACT

245

SBBL (@)

––

4

DOUBLE BINARY SUBTRACT

251

SBN

92

2

SUBROUTINE DEFINE

286

SBS (@)

91

2

SUBROUTINE ENTRY

285

147

Page 166

Section 5-7

Instruction Set Lists Mnemonic

Code

Words

SCAN (@)

18

4

CYCLE TIME

305

SCL (@)

––

4

SCALING

222

SDEC (@)

78

4

7-SEGMENT DECODER

215

SEC (@)

65

4

HOURS TO SECONDS

207

SEND (@)

90

4

NETWORK SEND

322

SET

None

2

SET

153

SFT

10

3

SHIFT REGISTER

171

SFTR (@)

84

4

REVERSIBLE SHIFT REGISTER

173

SLD (@)

74

3

ONE DIGIT SHIFT LEFT

177

SNXT

09

2

STEP START

295

SRCH (@)

––

4

DATA SEARCH

318

SRD (@)

75

3

ONE DIGIT SHIFT RIGHT

177

STC (@)

40

1

SET CARRY

229

STEP

08

2

STEP DEFINE

295

STUP (@)

––

2

CHANGE RS-232C SETUP

337

SUB (@)

31

4

BCD SUBTRACT

231

SUBL (@)

55

4

DOUBLE BCD SUBTRACT

233

SUM (@)

––

4

SUM CALCULATION

261

TCMP (@)

85

4

TABLE COMPARE

199

TERM (@)

48

4

TERMINAL MODE

309

TIM

None

2

TIMER

159

TIMH

15

3

HIGH-SPEED TIMER

164

TKY (@)

––

4

TEN KEY INPUT

350

TRSM

45

1

TRACE MEMORY SAMPLE

306

TTIM

87

4

TOTALIZING TIMER

165

TXD (@)

––

4

TRANSMIT

335

WDT (@)

94

2

WATCHDOG TIMER REFRESH

310

WSFT (@)

16

3

WORD SHIFT

178

XCHG (@)

73

3

DATA EXCHANGE

183

XDMR (@)

––

4

EXPANSION DM READ

319

XFER (@)

70

4

BLOCK TRANSFER

182

XFR2 (@)

––

4

EM BLOCK TRANSFER

190

XFRB (@)

62

4

TRANSFER BITS

189

XNRW (@)

37

4

EXCLUSIVE NOR

281

XORW (@)

36

4

EXCLUSIVE OR

280

ZCP

88

4

AREA RANGE COMPARE

200

ZCPL

––

4

DOUBLE AREA RANGE COMPARE

201

148

Name

Page

Page 167

Section 5-8

Ladder Diagram Instructions

5-8

Ladder Diagram Instructions Ladder Diagram instructions include Ladder instructions and Logic Block instructions and correspond to the conditions on the ladder diagram. Logic block instructions are used to relate more complex parts.

5-8-1 LOAD, LOAD NOT, AND, AND NOT, OR, and OR NOT Ladder Symbols

Operand Data Areas

B

B: Bit

LOAD – LD

IR, SR, AR, HR, TC, LR, TR

B: Bit

B

LOAD NOT – LD NOT

IR, SR, AR, HR, TC, LR

B: Bit

B

AND – AND IR, SR, AR, HR, TC, LR

B: Bit

B

AND NOT – AND NOT

IR, SR, AR, HR, TC, LR

B: Bit

OR – OR

B

OR NOT – OR NOT

B

IR, SR, AR, HR, TC, LR

B: Bit IR, SR, AR, HR, TC, LR

Limitations

There is no limit to the number of any of these instructions, or restrictions in the order in which they must be used, as long as the memory capacity of the PC is not exceeded.

Description

These six basic instructions correspond to the conditions on a ladder diagram. As described in Section 4 Writing and Inputting the Program, the status of the bits assigned to each instruction determines the execution conditions for all other instructions. Each of these instructions and each bit address can be used as many times as required. Each can be used in as many of these instructions as required. The status of the bit operand (B) assigned to LD or LD NOT determines the first execution condition. AND takes the logical AND between the execution condition and the status of its bit operand; AND NOT, the logical AND between the execution condition and the inverse of the status of its bit operand. OR takes the logical OR between the execution condition and the status of its bit operand; OR NOT, the logical OR between the execution condition and the inverse of the status of its bit operand. The ladder symbol for loading TR bits is different from that shown above. Refer to 4-4-3 Ladder Instructions for details.

Flags

There are no flags affected by these instructions.

149

Page 168

Section 5-9

Bit Control Instructions

5-8-2 AND LOAD and OR LOAD AND LOAD – AND LD Ladder Symbol

00000

00002

00001

00003

OR LOAD – OR LD 00000

00001

00002

00003

Ladder Symbol

Description

When instructions are combined into blocks that cannot be logically combined using only OR and AND operations, AND LD and OR LD are used. Whereas AND and OR operations logically combine a bit status and an execution condition, AND LD and OR LD logically combine two execution conditions, the current one and the last unused one. In order to draw ladder diagrams, it is not necessary to use AND LD and OR LD instructions, nor are they necessary when inputting ladder diagrams directly, as is possible from SSS. They are required, however, to convert the program to and input it in mnemonic form. The procedures for these, limitations for different procedures, and examples are provided in 4-7 Inputting, Modifying, and Checking the Program. In order to reduce the number of programming instructions required, a basic understanding of logic block instructions is required. For an introduction to logic blocks, refer to 4-4-6 Logic Block Instructions.

Flags

There are no flags affected by these instructions.

5-9

Bit Control Instructions There are five instructions that can be used generally to control individual bit status. These are OUT, OUT NOT, DIFU(13), DIFD(14), and KEEP(11). These instructions are used to turn bits ON and OFF in different ways.

5-9-1 OUTPUT and OUTPUT NOT – OUT and OUT NOT OUTPUT – OUT

Ladder Symbol

Operand Data Areas B: Bit B

OUTPUT NOT – OUT NOT

Ladder Symbol

IR, SR, AR, HR, TC, LR, TR

Operand Data Areas B: Bit B

IR, SR, AR, HR, TC, LR

Limitations

Any output bit can generally be used in only one instruction that controls its status. Refer to 3-3 IR Area for details.

Description

OUT and OUT NOT are used to control the status of the designated bit according to the execution condition.

150

Page 169

Section 5-9

Bit Control Instructions

OUT turns ON the designated bit for an ON execution condition, and turns OFF the designated bit for an OFF execution condition. With a TR bit, OUT appears at a branching point rather than at the end of an instruction line. Refer to 4-7-7 Branching Instruction Lines for details. OUT NOT turns ON the designated bit for a OFF execution condition, and turns OFF the designated bit for an ON execution condition. OUT and OUT NOT can be used to control execution by turning ON and OFF bits that are assigned to conditions on the ladder diagram, thus determining execution conditions for other instructions. This is particularly helpful and allows a complex set of conditions to be used to control the status of a single work bit, and then that work bit can be used to control other instructions. The length of time that a bit is ON or OFF can be controlled by combining the OUT or OUT NOT with TIM. Refer to Examples under 5-14-1 TIMER – TIM for details. Flags

There are no flags affected by these instructions.

5-9-2 DIFFERENTIATE UP and DOWN – DIFU(13) and DIFD(14) Ladder Symbols

Operand Data Areas

DIFU(13) B

B: Bit IR, AR, HR, LR

DIFD(14) B

B: Bit IR, AR, HR, LR

Limitations

Any output bit can generally be used in only one instruction that controls its status. Refer to 3-3 IR Area for details.

Description

DIFU(13) and DIFD(14) are used to turn the designated bit ON for one cycle only. Whenever executed, DIFU(13) compares its current execution with the previous execution condition. If the previous execution condition was OFF and the current one is ON, DIFU(13) will turn ON the designated bit. If the previous execution condition was ON and the current execution condition is either ON or OFF, DIFU(13) will either turn the designated bit OFF or leave it OFF (i.e., if the designated bit is already OFF). The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below). Whenever executed, DIFD(14) compares its current execution with the previous execution condition. If the previous execution condition was ON and the current one is OFF, DIFD(14) will turn ON the designated bit. If the previous execution condition was OFF and the current execution condition is either ON or OFF, DIFD(14) will either turn the designated bit OFF or leave it OFF. The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below). These instructions are used when differentiated instructions (i.e., those prefixed with an @) are not available and single-cycle execution of a particular instruction is desired. They can also be used with non-differentiated forms of instructions that have differentiated forms when their use will simplify programming. Examples of these are shown below.

Flags

There are no flags affected by these instructions.

151

Page 170

Section 5-9

Bit Control Instructions Precautions

DIFU(13) and DIFD(14) operation can be uncertain when the instructions are programmed between IL and ILC, between JMP and JME, or in subroutines. Refer to 5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03), 5-11 JUMP and JUMP END – JMP(04) and JME(05), and 5-23 Subroutines and Interrupt Control for details.

Example 1: When There is No Differentiated Instruction

In diagram A, below, whenever CMP(20) is executed with an ON execution condition it will compare the contents of the two operand words (HR 10 and DM 0000) and set the arithmetic flags (GR, EQ, and LE) accordingly. If the execution condition remains ON, flag status may be changed each cycle if the content of one or both operands change. Diagram B, however, is an example of how DIFU(13) can be used to ensure that CMP(20) is executed only once each time the desired execution condition goes ON.

00000 CMP(20) HR 10

Diagram A

DM 0000

Address

Instruction

00000 00001

LD CMP(20)

Operands 00000 HR DM

10 0000

00000 DIFU(13) 22500 22500 CMP(20) HR 10

Diagram B

DM 0000

Address

Instruction

00000 00001 00002 00003

LD DIFU(13) LD CMP(20)

Operands 00000 22500 22500 HR DM

Example 2: Simplifying Programming

Although a differentiated form of MOV(21) is available, the following diagram would be very complicated to draw using it because only one of the conditions determining the execution condition for MOV(21) requires differentiated treatment.

00000 DIFU(13) 22500 22500 MOV(21) 00001

00002

00003

HR 10 DM 0000

00004

00005

Address

Instruction

00000 00001 00002 00003 00004 00005 00006 00007 00008 00009 00010

LD DIFU(13) LD LD AND NOT AND NOT OR LD LD AND NOT OR LD MOV(21)

Operands 00000 22500 22500 00001 00002 00003 --00004 00005 --HR DM

152

10 0000

10 0000

Page 171

Section 5-9

Bit Control Instructions

5-9-3 SET and RESET – SET and RSET Ladder Symbols

Operand Data Areas B: Bit

SET B

IR, SR, AR, HR, LR

B: Bit

RSET B

IR, SR, AR, HR, LR

Description

SET turns the operand bit ON when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. RSET turns the operand bit OFF when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. The operation of SET differs from that of OUT because the OUT instruction turns the operand bit OFF when its execution condition is OFF. Likewise, RSET differs from OUT NOT because OUT NOT turns the operand bit ON when its execution condition is OFF. Note The instructions SET and RESET are input as follows: Operand SET: RESET:

Operand

Precautions

The status of operand bits for SET and RSET programmed between IL(02) and ILC(03) or JMP(04) and JME(05) will not change when the interlock or jump condition is met (i.e., when IL(02) or JMP(04) is executed with an OFF execution condition).

Flags

There are no flags affected by these instructions.

Examples

The following examples demonstrate the difference between OUT and SET/ RSET. In the first example (Diagram A), IR 10000 will be turned ON or OFF whenever IR 00000 goes ON or OFF. In the second example (Diagram B), IR 10000 will be turned ON when IR 00001 goes ON and will remain ON (even if IR 00001 goes OFF) until IR 00002 goes ON. 00000 10000

Diagram A

Address

Instruction

00000 00001

LD OUT

Address

Instruction

00000 00001 00002 00003

LD SET LD RSET

Operands 00000 10000

00001 SET 10000 00002 RSET 10000

Diagram B

Operands 00001 10000 00002 10000

153

Page 172

Section 5-9

Bit Control Instructions

5-9-4 KEEP – KEEP(11) Ladder Symbol

Operand Data Areas S

B: Bit

KEEP(11) B

IR, AR, HR, LR

R

Limitations

Any output bit can generally be used in only one instruction that controls its status. Refer to 3-3 IR Area for details.

Description

KEEP(11) is used to maintain the status of the designated bit based on two execution conditions. These execution conditions are labeled S and R. S is the set input; R, the reset input. KEEP(11) operates like a latching relay that is set by S and reset by R. When S turns ON, the designated bit will go ON and stay ON until reset, regardless of whether S stays ON or goes OFF. When R turns ON, the designated bit will go OFF and stay OFF until reset, regardless of whether R stays ON or goes OFF. The relationship between execution conditions and KEEP(11) bit status is shown below. S execution condition R execution condition

Status of B

KEEP(11) operates like the self-maintaining bit described in 4-8-3 Self-maintaining Bits. The following two diagrams would function identically, though the one using KEEP(11) requires one less instruction to program and would maintain status even in an interlocked program section. 00002

00003

Address

Instruction

00000 00001 00002 00003

LD OR AND NOT OUT

S

Address

Instruction

R

00000 00001 00002

LD LD KEEP(11)

00500 00500

00002

KEEP(11) 00500

00003

Operands 00002 00500 00003 00500

Operands 00002 00003 00500

Flags

There are no flags affected by this instruction.

Precautions

Exercise caution when using a KEEP reset line that is controlled by an external normally closed device. Never use an input bit in an inverse condition on the reset (R) for KEEP(11) when the input device uses an AC power supply. The delay in shutting down the PC’s DC power supply (relative to the AC power supply to

154

Page 173

Section 5-10

INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03)

the input device) can cause the designated bit of KEEP(11) to be reset. This situation is shown below. Input Unit A

S KEEP(11)

NEVER

B

A R

Bits used in KEEP are not reset in interlocks. Refer to the 5-10 INTERLOCK – and INTERLOCK CLEAR IL(02) and ILC(03) for details. Example

If a HR bit or an AR bit is used, bit status will be retained even during a power interruption. KEEP(11) can thus be used to program bits that will maintain status after restarting the PC following a power interruption. An example of this that can be used to produce a warning display following a system shutdown for an emergency situation is shown below. Bits 00002, 00003, and 00004 would be turned ON to indicate some type of error. Bit 00005 would be turned ON to reset the warning display. HR 0000, which is turned ON when any one of the three bits indicates an emergency situation, is used to turn ON the warning indicator through 00500.

00002

S KEEP(11)

00003

Indicates emergency situation

HR 0000

00004 R Reset input 00005

HR 0000 00500

Address

Instruction

00000 00001 00002 00003 00004 00005 00006

LD OR OR LD KEEP(11) LD OUT

Operands

HR HR

00002 00003 00004 00005 0000 0000 00500

Activates warning display

KEEP(11) can also be combined with TIM to produce delays in turning bits ON and OFF. Refer to 5-14-1 TIMER – TIM for details.

5-10 INTERLOCK and INTERLOCK CLEAR – IL(02) and ILC(03)

Description

Ladder Symbol

IL(02)

Ladder Symbol

ILC(03)

IL(02) is always used in conjunction with ILC(03) to create interlocks. Interlocks are used to enable branching in the same way as can be achieved with TR bits, but treatment of instructions between IL(02) and ILC(03) differs from that with TR bits when the execution condition for IL(02) is OFF. If the execution condition of IL(02) is ON, the program will be executed as written, with an ON execution condition used to start each instruction line from the point where IL(02) is located through the next ILC(03). Refer to 4-7-7 Branching Instruction Lines for basic descriptions of both methods. If the execution condition for IL(02) is OFF, the interlocked section between IL(02) and ILC(03) will be treated as shown in the following table:

155