For the Omron C200H-IDS01-V1
Page 88
SECTION 4 Troubleshooting This section contains information on maintenance and troubleshooting. 4-1
Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
74
4-2
What To Do If a Malfunction Occurs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
74
4-3
Diagnostic Flowcharts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
73
Page 89
Periodic Maintenance Section Overview
Section 4-1 This section contains information that can help you to determine the cause(s) of any problems you may encounter in the operation of your ID Sensor system. Refer to this section any time you experience a malfunction. Also included is a checklist of preventive maintenance measures, which you should follow on a monthly basis to ensure long service from your ID Sensor system.
4-1
Periodic Maintenance Go over the following checklist monthly to ensure troublefree operation of the ID Sensor system. Condition
Checklist Item
Standard
Environmen- Is the ambient temperature (panel temperatal ture) appropriate?
Mounting
0° to 55°C
Is the humidity appropriate?
35 to 85%, without condensation
Is there dust on the surace of the Unit? Is the ID Sensor Unit securely mounted?
Dust-free No looseness
Is the cable securely connected?
The cable connector must not be loose Are there cracks or noticeable weak areas in Appearance must be the cable? normal, free of cracks or exposed wires
4-2
What To Do If a Malfunction Occurs The following table shows causes and corrective actions for particular malfunctions. Refer to this table if you experience trouble with the ID Sensor system. Error
Cause
Corrective Action
All indica- Power is not applied to the PC. Apply power to the PC. If the indicators tors remain coninue to remain unlit, make sure the unlit. PC is properly connected to the power supply. The ID Sensor Unit is not Completely remove the ID Sensor Unit mounted securely. from the PC (see note) and remount it, making sure the connecting terminals are secure. A WDT (watchdog timer) error has occurred in the ID Sensor Unit. CPU ERROR indicator is lit.
Turn OFF/ON/OFF the Special I/O Unit restart flag (within the range AR 0100 through 0109) that corresponds to the unit number in the PC. Locate the cause of the error in the PC and correct it.
Note Before removing the ID Sensor Unit from the PC, turn OFF the power to the PC. Replacing the Unit
Before replacing the ID Sensor Unit, be sure to turn OFF the power to the PC. Remove the Unit and replace it with a new Unit, making sure it is securely mounted. Check the new Unit thoroughly before operation. When returning a defective Unit to OMRON, include a detailed explanation of the problem.
Spare Parts
74
To minimize downtime of the system, it is advisable to keep at least one spare Unit on hand.
Page 90
Diagnostic Flowcharts
4-3
Section 4-3
Diagnostic Flowcharts If an error occurs, determine the conditions under which it occurs: intermittent or continuing; on-line or off-line. Use the following flowcharts to determine the cause of an error.
Basic Assurance Test (BAT) START Turn the power to the PC ON
RUN LED unlit lit blinking lit T/R LED unlit
PC ERROR LED lit
OK Hardware error Replace the ID Sensor Unit
Locate the error in the PC and correct it.
75
Page 91
Diagnostic Flowcharts
Section 4-3
Flowchart for Testing with the Programming Console START Connect the Programming Console Turn the power ON 1
<RUN>
Programming Console in MONITOR mode?
<MONITOR> BZ
<PROGRAM> MODE ERROR
Execute "TEST AW"
No
Hardware error Replace the ID Sensor Unit
Yes
Yes Set the Programming Console to MONITOR mode.
COM. DC E
No
Return to 1
Yes
Workpiece moving too fast? Refer to 1-5 System Connections
No
Yes VERIFY E
Adjust speed of workpiece
No Yes
Is distance between R/W Head and Data Carrier adequate? Refer to 1-5 System Connections
No No
Yes ADRS E
Adjust the distance
No Yes R/W H E
Is R/W Head defective?
No
Data Carrier defective?
Yes
No Yes Yes PROTCT E
No OK
Hardware Hardwarerror error Replace theIDID Replace the Sensor Unit Sensor Unit.
76
Replace R/W Head
Replace Data Carrier.
No