Appendix A Specifications ID Sensor Unit C200H-IDS01-V1/IDS21 Unit Dimensions

130 mm

35 mm

100.5 mm

Mounted Dimensions

Backplane

117 mm Approx. 200 mm

Note Verify the depth of the control panel before mounting the ID Sensor Unit.

77

Page 93

Specifications

Appendix A

Characteristics Item

Specifications

Communication Control Procedure

Interactive

Number of R/W Heads (Antennas) connected Data Carrier (DC)

One per ID Sensor Unit.

Commands

The following seven commands are used: Read, Write, Auto Read, Auto Write, Clear-all, Auto Read/Write Abort, and Data Management (C200H-IDS01-V1 only) Up to 512 words (1024 bytes) can be transferred at 20 words/scan.

Data transferrable per instruction Diagnostic functions

Monitoring functions

C200H-IDS01-V1: C200H-IDS21:

V600series Data Carrier V620series Data Carrier

• CPU watchdog timer • Communication errors Six communication errors identify the causes of errors that have occurred during communication between the Data Carrier and the ID Sensor Unit. (i.e. Data Carrier missing, communication error) • Error Log The Error Log function allows communication errors to be displayed in statistical form or in order of occurrence. Error information is retained by the back-up capacitor. The following monitoring functions are available when the ID Sensor Unit is connected to a Hand-held Programming Console. (Use the keyboard sheet provided with the ID Sensor Unit.) (Cable length: 4 m max.) Read (1 byte) Stepwise Write (1 byte) Continuous Write Test Error Log

Memory backup Error information is backed up by a capacitor for 15 days (at 25°C). See note 2. Number of words required Internal current consumptions Dimensions

5 words between words 100 through 199 (reserved for Special I/O Units) in the IR area 250 mA max. at 5 VDC. 120 mA max. at 26 VDC (to drive Read/ Write Head or R/W Antenna; See note 1.) 35(W)x130(H)x100.5(D) mm

Weight

400 grams max.

Note 1. The Read/Write Head (or Antenna) is supplied 26 VDC. Refer to the C200H PC Installation Guides (W111 and W218) for information on system design.

78

Page 94

Specifications

Appendix A

2. The error information stored in the memory of the ID Sensor Unit is retained by a built-in backup capacitor for 15 days at an ambient temperature of 25°C. As shown in the following diagram, the duration of the backup shortens as the temperature rises.

Back-up duration (days)

15

10

5 2 0

25 30

40

50

60

Ambient temperature (°C)

79

Page 95

This page is a scan with no text; see it in the PDF.

Page 96

Appendix B Standard Models Name

Model Number

Electromagnetic Induction ID Sensor Unit Microwave Induction ID Sensor Unit

C200H-IDS01-V1 C200H-IDS21

Hand-held Programming Console Connecting Cable (2 m) (See note.)

C200H-PRO27-E C200H-CN222

Connecting Cable 42 m) (See note.)

C200H-CN422

Note The cable connects the Handheld Programming Console to the ID Sensor Unit.

81

Page 97

This page is a scan with no text; see it in the PDF.

Page 98

Appendix C ASCII Code List ASCII Code List Higher digit (higher 4 bits)

Lower digit (lower 4 bits)

83

Page 99

This page is a scan with no text; see it in the PDF.

Page 100

Appendix D Using the C200H ID Sensor Unit with CS1-series PCs Points of Caution Note the following points when using the C200H-IDS01-V1 or C200H-IDS21 with a CS1-series PC.

1) Differences in I/O Bit and DM Area Allocation • The beginning word, n, of the area allocated for I/O between the CPU Unit and the ID Sensor will change from n = 100 + (unit number × 10) to n = 2000 + (unit number × 10). • The beginning word, m, of the area in the DM Area allocated to the ID Sensor will change from m = DM 1000 + (unit number × 100) to m = D20000 + (unit number × 100).

2) Command Storage Area and Read Data Receiving Area Specification Specify the command storage area and read data receiving area for a CS1-series PC using the CIO Area (words n+2 and n+3) in the way shown below.

Command Storage Area/Read Data Receiving Area Specification Area

Address to be specified (see note)

Specification method from CIO Area Command data storage area address Area name Beginning word n+2, bits 12 to 15 number (1 digit, Hex) n+2, bits 0 to 11 (3 digits, BCD)

Read data receiving area address Area name n+3, bits 12 to 15 (1 digit, Hex)

Beginning word number n+3, bits 0 to 11 (3 digits, BCD)

General-purpose DM Area

D00000 to D00999

0

0000 to 0999

0

0000 to 0999

DM Area for Special I/O Units

D20000 to D20999

1

0000 to 0999

1

0000 to 0999

I/O Area Holding Area 1

0000 to 0246 H000 to H099

2 4

0000 to 0246 0000 to 0099

2 4

0000 to 0246 0000 to 0099

Holding Area 2 Data Link Area

H107 to H122 1000 to 1063

6 8

0007 to 0022 0000 to 0063

6 8

0007 to 0022 0000 to 0063

Timer Completion Flags

T0000 to T0511

A

0000 to 0511

A

0000 to 0511

Note It is not possible to specify any CS1 memory address other than the ones given in the above table.

Data Configuration CIO Area n = 2000 + (unit number × 10) Bit n to n+3 n+4

15

0 Commands from the CPU Unit

ID Sensor Unit status

Contents

Direction

Command execution flags, command data storage specification, read data destination specification, etc.

From CPU Unit to ID Sensor Unit

ID busy, Waiting for Data Carrier, command error, etc.

From ID Sensor Unit to CPU Unit

85

Page 101

Using the C200H ID Sensor Unit with CS1-series PCs

Appendix D

DM Area Allocation Not used.

Setting Procedure Hardware Settings 1. Set the unit number of the ID Sensor Unit using the rotary switch on the front of the Unit. 2. Mount on a CS1 CPU Rack, a C200H I/O Expansion Rack, a CS1 Expansion Rack, or a SYSMAC BUS Remote I/O Slave Rack. In a basic system, up to 10 Units can be mounted. (There are no restrictions on mounting order.) 3. Connect the Programming Device to the PC. 4. Turn on power to the PC. 5. Create an I/O table.

Initial Software Settings Save command data to the area specified using word n+2 of the CIO Area.

Executing Commands 1. Set the number of command data words in word n+1 of the CIO Area. 2. Set the area name and the address for the area used to store command data in word n+2 of the CIO Area. 3. When using read commands, set the area name and the address for the area used to receive read data in word n+3 of the CIO Area. 4. Execute commands for the ID Sensor Unit by turning bit 00 of word n of the CIO Area from OFF to ON.

Programming Executing Commands 1. Set the number of command data words (CIO Area, word n+1) and the command data storage area address (CIO Area, word n+2) using the MOV(021) instruction, with the normally closed condition of the ID Busy Flag (CIO Area, word n+4, bit 00) as an input condition. (When using a read command, also set the read data receiving area address (CIO Area, word n+3) using the MOV(021) instruction.) 2. Program a self-holding bit as one of the input conditions for the above MOV(021) instructions. 3. Turn ON the command execution flag (word n, bit 00) using the OUT instruction, with the normally open condition of the above self-holding bit as the input condition.

86

Page 102

Using the C200H ID Sensor Unit with CS1-series PCs

Appendix D

Program Example Execution input DIFU (013) a 200400 (word n+4, bit00)

a

MOV (021)

ID busy

#0007

7 words n+1 (number of command data words)

2001 b MOV (021) #0000

Waiting for command execution

D00000 n+2 (command data storage area address)

2002 b

If input condition a is ON for one cycle and the ID Busy Flag is OFF, sets the number of command data words to 7. At the same time, sets the command storage area beginning address to D00000. Holds status until ID Sensor Unit starts executing the command

(word n, bit 00) b 200000

Command execution flag Example: DM Area used as command data storage area at the CPU Unit Command data in CPU 15

Data to be written to Data Carrier Address 7 0

00

D00000

57

54

WT (Write)

D00001

48

31

H1 (Hexadecimal, Head 1)

D00002

00

06

D00003

10

11

Beginning address in which data is to be written in Data Carrier

D00004

12

13

Data to be written to Data Carrier, numbers 10 through 14 (5 bytes)

D00005

14

2A

D00006

0D

00

0006

10

0007

11

Write is executed. 0008

12

0009

13

000A

14

If the number of bytes to be written to the Data Carrier is odd, shift codes 2A and 0D forward one byte and write 00 into the last 8 bits.

Data cannot be written to write-protected areas.

Note Although the ID Busy flag normally turns OFF upon completion of the command, if the command execution flag is ON at this time, the ID Busy flag will stay ON. Therefore, design the program so that the command execution flag will be turned OFF when the ID Busy flag turns ON, as in the example.

87