Page 114
Execution Examples
Section 5-4 Stepping motor Sensor
Origin signal Slit disc 1 Origin proximity signal 0 1 Origin signal 0
Pulse output Origin (Stop)
CW
CCW ORIGIN SEARCH (Start)
The origin is sought after the origin proximity signal turns OFF. Deceleration begins when the origin proximity signal turns ON.
CW
CCW Origin (Stop) ORIGIN SEARCH (Start)
Positioning axis
CW CCW Origin (Stop)
CW limit ORIGIN SEARCH (Start)
107
Page 115
Execution Examples
Section 5-4
Example 2: When Origin Proximity Reverse is Disabled
X: DM word m+21 Y: DM word m+121 ( bit 01 ON, bit 04 OFF) This example shows one pulse of the proximity signal and one pulse of the origin signal.
Origin proximity signal 1 0 1 Origin signal 0
Pulse output
CW
CCW Origin (Stop) ORIGIN SEARCH (Start)
Positioning axis
CW
CCW Origin (Stop) ORIGIN SEARCH (Start)
CW CCW Origin (Stop)
CW limit ORIGIN SEARCH (Start)
108
Page 116
Execution Examples Example 3: No Origin Proximity Signal
Section 5-4 X: DM word m+21 Y: DM word m+121 ( bit 01 OFF) Only the origin signal is used. All positioning actions are carried out at proximity speed (low speed).
1 Origin signal 0
Pulse output CCW
CW Origin (Stop) ORIGIN SEARCH (Start)
Positioning axis
CW
CCW Origin (Stop)
ORIGIN SEARCH (Start)
CW
CCW Origin (Stop) ORIGIN SEARCH (Start)
CW limit
109
Page 117
Execution Examples
Section 5-4
Mode 1 The Origin response time is 0.1 ms. Connect the encoder’s Z-phase signal to inputs 9 and 11 for the X axis, and to inputs 31 and 33 for Y axis. Be sure to use the proximity signal. Also refer to the wiring information in Section 2-4. Note In mode 1, the proximity signal is used even if the axis is set for “No proximity signal” (bit 01 OFF.)
Example 1: When Origin Proximity Reverse is Enabled
X: DM word m+21 Y: DM word m+121 ( bit 01 ON, bit 04 ON) Use the origin proximity signal to ensure sufficient deceleration time when origin proximity reverse is needed.
Origin proximity signal 1 0 1 Origin signal 0
Pulse output
CW
Origin (Stop)
CCW
Positioning axis ORIGIN SEARCH (Start)
The origin is sought after the origin proximity signal turns OFF. Deceleration begins when the origin proximity signal turns ON.
CW CCW Origin (Stop) ORIGIN SEARCH (Start)
CW CCW
Origin (Stop)
CW limit ORIGIN SEARCH (Start)
Stop Deviation counter reset
Time 0 App. 20 ms
110
Page 118
Execution Examples
Section 5-4 After positioning has stopped, a deviation counter reset signal of about 20 ms is output. In this mode, if deceleration has not ended when the origin proximity signal has turned OFF, positioning is stopped by the origin signal input after deceleration has ended. If the deceleration period is short for some reason (such as starting inside the origin proximity area), the Position Control Unit will detect another origin signal. Therefore, be sure that the origin proximity signal period is long enough, i.e., at least as long as the deceleration period.
Origin proximity signal 1 0
1 Origin signal 0
Pulse output
Positioning axis
CCW CW
ORIGIN SEARCH (Start) Ideal position for origin proximity signal to turn OFF
Positioning axis CCW ORIGIN SEARCH (Start)
Origin (Stop)
CW
Pulse output VH VL
CCW
Positioning axis
TD
CW
A general method for calculating the number of pulses within the deceleration interval is presented below. Deceleration time TD = VH – VL /1000 x R, where R: deceleration data (pps/1 ms); Number of pulses PD for deceleration period = (VH + VL ) x TD /2 = VH2 – VL2 /2000 x R. If VH = 20000 pps, VL = 1000 pps, and R = 1000 pps/ms, then PD = 200002 – 10002 /2000 x 100 = 1995. Therefore, approximately 2,000 pulses are required for deceleration.
111
Page 119
Execution Examples
Section 5-4
Example 2: When Origin Proximity Reverse is Disabled
X: DM word m+21 Y: DM word m+121 ( bit 01 ON, bit 04 OFF) In this example, origin proximity reverse is not used. Positioning stops when the first origin signal is input after deceleration has ended.
Origin proximity signal 1 0 1 Origin signal 0
Pulse output
Positioning axis
CCW Origin (Stop)
CW
ORIGIN SEARCH (Start) (The origin is sought after deceleration has ended.)
Be aware that when there is an origin signal during deceleration, the stop position depends on the length of the deceleration interval. Origin proximity signal 1 0 1 Origin signal 0
Pulse output Positioning axis CCW stop start
CCW stop start
112
CW
CW
Page 120
Execution Examples
Section 5-4 In this example diagram, deceleration from ORIGIN SEARCH high speed to proximity speed (low speed) is completed in the period between the origin proximity signal and the first origin signal.
Origin proximity signal 1 0 Origin signal 1 0
VH
Pulse output VL CCW
Positioning axis
CW
PD : Number of pulses for deceleration period (p) VH : ORIGIN SEARCH high speed (pps) VL : Proximity speed (pps) R: Deceleration data (pps/ms)
PD = [(VH + VL ) x (VH – VL/1000 x R)]/2 = (VH2 – VL2/2000 x R) Set the values of VH and R, using this expression, so that the value of PD falls within the range shown in the above figure.
113
Page 121
Execution Examples
Section 5-4
Mode 2 This mode is similar to Mode 1, but the servomotor driver positioning completed signal is also used. For the connection of this signal, refer to 2-4 Wiring. The busy flag turns OFF when the positioning completed signal has been input. Keep the dwell time set to 0, for however long the dwell time is set, the busy flag takes that much longer to turn OFF. Note In mode 2, the proximity signal is used even if the axis is set for “No proximity signal” (bit 01 OFF.)
Pulse output Time Stop The “ON” condition is written as 1 for this signal level. Positioning completed signal
1 0
1 Busy flag 0 Dwell time
114
Page 122
Execution Examples
Section 5-4
Mode 3 Mode 3 makes use of the origin adjustment functions of OMRON Servomotor Drivers R88D-EP and R88D-SR. The servomotor’s positioning completed signal (INP) is used as the origin search completion signal. Do not use an origin, Z-phase, or deviation counter reset signal. Note In mode 3, the proximity signal is used even if the axis is set for “No proximity signal” (bit 01 OFF.) Example 1: When Origin Proximity Reverse is Enabled Origin proximity signal
Origin adjustment command Positioning completed signal
X: DM word m+21 Y: DM word m+121 ( bit 01 ON, bit 04 ON)
1 0
1 0 1 0
Pulse output Time Origin (Stop) ORIGIN SEARCH (Start)
Busy flag
1 0
115
Page 123
Execution Examples
Section 5-4 When the servomotor driver receives the origin adjustment command (H.RET) from the Position Control Unit, the deviation counter of the servomotor driver is internally reset by the Z-phase signal (which is output by the encoder) and the servomotor driver stops. Servomotor Driver Processing: 1
Origin adjustment command
0 1
Z-phase signal 0
1 Positioning completed signal 0 Servomotor driver stops here.
The point at which positioning stops is the same as in modes 1 and 2. There are some differences in operation depending on the starting position for ORIGIN SEARCH. For details, refer to the examples under Mode 1. Refer also to the examples under Mode 1 for certain precautions concerning the length of the origin proximity signal. In mode 3, if deceleration has not ended by the time the origin proximity signal has turned OFF, the origin adjustment signal is output when deceleration ends.
116