SYSMAC C200H-NC211 Position Control Unit Operation Manual: SECTION 9 Programming Examples, pages 203 to 211

Pages 203 to 211 of 259, from SYSMAC C200H-NC211 Position Control Unit Operation Manual

The original document is the PDF (1.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-NC211

Page 203

Example 2

Section 9-2

Program X-axis start switch DIFU(13) 3000 Y-axis start switch DIFU(13) 3100 Busy flag 03000 11012 10002 X axis ORIGIN SEARCH Busy flag 03100 11512 10502 Y axis ORIGIN SEARCH No origin 10011 No origin 11511

At origin Busy 11002 11012 10000

X axis START

10500

Y axis START

At origin Busy 11502 11512

X-axis positioning completed flag 11000 DIFU(13) 3001 Y-axis positioning completed flag 11500

DIFU(13) 3101

03001 11002 03002 03002 03101 11502

03102

03102 03002 11012 10008

X axis present position reset

10508

Y axis present position reset

10015

X axis STOP

10515

Y axis STOP

03102 11512

X-axis operation stop switch

Y-axis operation stop switch

END(01)

198

Page 204

Example 3

9-3

Section 9-3

Example 3

Using the Origin and Origin Proximity Signals Configuration (mode 0) Position Control Unit #0

C200H PC

22/34 Power supply

18

CW limit

17

CCW limit

24 VDC X axis

10 11

Origin

7

Proximity

19

Emergency stop

32 33

Origin

29

Proximity

21

CW limit

20

CCW limit

Y axis

DM Area Settings DM 1021

0

0

0

6

4 3 21 0

0 0 11 0 Direction (CW) Proximity signal present Origin proximity N.O. contact Origin N.O. contact No proximity reverse

199

Page 205

Example 3

Section 9-3

Operation SW 10002

X axis ORIGIN SEARCH

10502

Y axis ORIGIN SEARCH

SW

The possible search patterns for ORIGIN SEARCH using both an origin signal and an origin proximity signal are shown below. Origin proximity signal

1 0

Pulse output CCW

CCW

CW

START

Origin (Stop)

START

CCW

Origin (Stop)

START Origin (Stop)

200

CW

CW CW limit

Page 206

Example 4

9-4

Section 9-4

Example 4

Positioning After ORIGIN SEARCH Operation

Operation alternates between an initial positioning action and ORIGIN RETURN, using a point on the X axis as a reference (point A in the diagram below). After STOP switch input, operation returns to the origin and stops. Speed No. 1 Positioning action No. 0 (START)

ORIGIN SEARCH 0 Origin proximity signal Origin (or Z encoder signal)

10000 point A

DM Area Settings ORIGIN Initial RETURN speed speed 1 to F 0 to F DM 1000

1 1 0 0

DM 1001

1 2 1 2

Initial position no. 0 to 52

HIGH- LOW- ORIGIN Origin SPEED SPEED SEARCH prox. JOG JOG speed 1 to F 1 to F

1 to F

1 to F

Positioning action no. 0 Speed Output Dwell Completion code time No. code 1 to F 0 to F 0 to F 0 to 5

DM 1022

1 0 0 3

DM 1023

0 0 0 0

DM 1024

0 0 0 1

DM 1082

5 0 0 0 Speed No. 1

DM 1083

0 5 0 0 Speed No. 2

DM 1097

0 0 0 0 Speed units

DM 1098

0 0 0 8 Acceleration

DM 1099

0 0 0 8 Deceleration

Target position

DM 1021

0

0

0

E

4 3 21 0

0 1 11 0 Direction (CW) Proximity signal present Origin proximity N.O. contact Origin N.O. contact No proximity reverse

201

Page 207

Example 4

Section 9-4

Program Start switch DIFU(13) 3000 03000

Busy flag 11012

No origin Stop switch 11011

At origin 11002

10002

ORIGIN SEARCH

10000

START

Busy flag 11012

Start completed DIFU(13) 3001 11000 03001

11012 10003

END (01)

202

ORIGIN RETURN

Page 208

Example 5

9-5

Section 9-5

Example 5

Point to Point Operation on Both the X and Y Axes This example shows how to use ORIGIN SEARCH, present position reset, or START after present position reset to operate simultaneously on both the X and Y axes. (Unit No. 0 is used for the purpose of this example.) 1. Independent Operation CW B (0, 5000)

A (10000, 5000)

Y axis pulse

CW Origin

X axis pulse

In the diagram above, single axis positioning is executed from the origin (0, 0) to point B (0, 5000) on the Y axis, followed by point A (10000, 5000) on the X axis. X axis START use the Y axis positioning completed flag (bit 00 of word n+15). When simultaneous operation on both axes is executed with the same DM area settings, X axis START receives priority. It takes 10-50 ms to process X axis START, and Y axis START must wait for that processing to finish. DM Area Settings

X axis

Y axis

DM 1000

1 0 0 0

DM 1100

1 0 0 0

DM 1001

1 2 1 2

DM 1101

1 2 1 2

Initial ORIGIN RETURN speed speed 1 to F 0 to F

Initial position No. 0 to 52

HIGH- LOW- ORIGIN Origin SPEED SPEED SEARCH prox. JOG JOG speed speed 1 to F 1 to F

1 to F

1 to F

Positioning action no. 0 Speed Output Dwell Completion code time No. code 1 to F 0 to F 0 to F 0 to 5

DM 1022

1 0 0 3

DM 1122

1 0 0 3

DM 1023

0 0 0 0

DM 1123

5 0 0 0

DM 1024

0 0 0 1

DM 1124

0 0 0 0

DM 1082

1 0 0 0

DM 1182

1 0 0 0

Speed No. 1

DM 1083

0 1 0 0

DM 1183

0 1 0 0

Speed No. 2

DM 1098

0 0 0 5

DM 1198

0 0 0 5

Acceleration

DM 1099

0 0 0 5

DM 1199

0 0 0 5

Deceleration

Target position

203

Page 209

Example 5

Section 9-5

Program

The following diagram shows a program for executing START independently on each axis. Start switch Y axis positioning Y axis Busy flag completed flag 11512 11500

X axis Busy flag 11012

DIFU(13) 10500

Y axis START

DIFU(13) 10000

X axis START

The next diagram shows the program for simultaneous START on both axes. Start switch DIFU(13) 10000

DIFU(13) 10500

Note When operations are started on both axes simultaneously, the X axis receives priority. It takes 10-50 ms to process X axis START, and Y axis START must wait for that processing to finish.

204

Page 210

Example 5

Section 9-5

2. Interpolation Operation with Independent Axis START No. 1

CW B (0, 5000)

A (10000, 5000)

X axis

No. 0 CW

Y axis pulse

(B)

Interpolation START

B

(A)

A

No. 0 No. 1

Y axis

CW

CW

X axis pulse

Origin

The same operation as in Example 1 is possible with interpolation; there are more DM area settings to make, but the program itself is simpler. The completion code in DM word 1022 changes from #1 (Single) to #2 (Continuous), allowing continuous operation (shown by the dotted lines in the diagram). For interpolation START, use X axis START. DM Area Settings X axis

Y axis

DM 1000

1 0 0 0

DM 1100

* * * 1 0 0 0

DM 1001

1 2 1 2

DM 1101

1 2 1 2

Initial ORIGIN RETURN speed speed 0 to F 1 to F

Initial position no. 0 to 52

HIGH- LOW- ORIGIN Origin SPEED SPEED SEARCH prox. JOG JOG speed speed 1 to F 1 to F

1 to F

DM 1022

1 0 0 1

DM 1122

* * * 1 0 0 1

DM 1023

0 0 0 0

DM 1123

5 0 0 0

DM 1024

4 0 0 0

DM 1124

DM 1025

1 1 0 3

DM 1125

0 0 0 0 1* 1* 0* 3

DM 1026

0 0 0 0

DM 1126

0 0 0 0

DM 1027

4 0 0 1

DM 1127

0 0 0 0

1 to F

Positioning action no. 0 Speed Output Dwell Completime No. tion code code 1 to F 0 to F 0 to F 0 to 5 Target position

Direction Positioning action no. 1

DM 1082

1 0 0 0

DM 1182

1 0 0 0

* Speed No. 1

DM 1083

0 1 0 0

DM 1183

0 1 0 0

* Speed No. 2

DM 1098

0 0 0 5

DM 1198

0 0 0 5

* Acceleration

DM 1099

0 0 0 5

DM 1199

0 0 0 5

* Deceleration

205

Page 211

Example 5

Section 9-5

Program Start switch DIFU(13) 10000

X axis START (Interpolation)

When the direction of the X axis positioning action is set from 4 to 7, it becomes interpolation data. The speed, acceleration, deceleration, output code, and dwell time settings for interpolation become X axis values. Y axis settings (marked with an asterisk *) are ignored, but data must be input to prevent an alarm form being generated.

206