Page 90
Appendix B
Specifications
CPU Unit Specifications Main Control Element Programming Method Instruction Length
MPU, CMOS, LS-TTL
Number of Instructions Execution Time
CPU21-E/23-E 168 (12 basic instructions + 156 special instructions) CPU31-E 172 (12 basic instructions + 160 special instructions) Basic instructions: 0.75 to 2.25 µs Special instructions: 34 to 724 µs
Memory Capacity
6,974 words (with 8k-word memory) I/O bits for Group-2 480 bits High-density Units (00000 through and Group-2 B7A 02915) Interface Units: 320 3,296 bits bits (03000 through (03000 through 04915) 23515)
IR Area: I/O bits
IR Area: Work bits
Ladder diagram 1 address/instruction, 1 to 4 words/instruction
I/O bits for I/O Units mounted to Slave Racks: 800 bits (05000 through 09915)
I/O bits for Special I/O Units: 1,600 bits (10000 through 19915)
I/O bits for Optical I/O Units: 512 bits (20000 through 23115)
SR bits
312 (23600 through 25507)
TR bits
8 (TR 0 through 7)
HR bits
1,600 (HR bits 0000 through 9915)
AR bits
448 (AR 0000 through 2715)
LR bits
1,024 (LR 0000 through 6315)
Timers/Counters
512 (TIM/CNT 000 through 511) TIMs: 0 through 999.9 s TIMHs: 0 through 99.99 s CNT: 0 through 9999 counts Read/write: 1,000 (DM 0000 through 0999) Read only: 1,000 (DM 1000 through 1999) DM area is in Memory Pack. Contacts are closed while PC is in RUN mode and operating. Max. switching capacity: 2A 250 VAC (resistive load) 0.5 A 250 VAC (inductive load, cosφ = 0.4) 2 A 24 VDC
DM words RUN Output
Power failure backup function Memory Protection
Holds HR, AR, CNT, and DM contents. The memory backup period varies with the Memory Unit. RAM Pack, battery back-up: Program (including clock function) and data areas protected. EEPROM Pack (with clock function): Clock function and data areas protected. C200H-CPU31-E: Program and data areas (including clock function) protected. Battery life expectancy is 5 yrs at 25°C. Life expectancy decreases with higher temperature. Refer to 2-6 Memory Units for more details. RAM Pack, capacitor back-up: Program and data areas protected. EPROM Pack: Data areas protected. EEPROM Pack (without clock function): Data areas protected. Memory is protected for 20 days without PC power at 25°C. Length of protection decreases at higher temperature. Refer to Section 2-6 Memory Units for more details.
Self-diagnostic Functions
CPU Unit failure (watchdog timer) Cycle time error I/O bus failure Remote I/O error, etc.
Program Check
Program check (executed on start of RUN operation): END missing Instruction errors (Program can be checked by Programming Console or GPC at three levels.)
84
Battery failure Memory failure Host Link error
Page 91
Appendix B
Specifications
Standard I/O Units AC Input Unit C200H-IA121 Rated Input Voltage
100 to 120 VAC 50/60 Hz
Operating Input Voltage
85 to 132 VAC 50/60 Hz
Input Impedance
9.7 kΩ (50 Hz), 8 kΩ (60 Hz)
Input Current
10 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Response Time
35 ms max. (at 100 VAC, 25°C)
OFF Response Time
55 ms max. (at 100 VAC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration IN
100 to 120 VAC
IN
0.33 µF 470 Ω Internal circuit
330 kΩ 910 Ω
COM
Input indicator
Terminal Connections 0 A0 1 2 100 to 120 VAC
3 4 5 6 7 COM
NC
A1 A2 A3 A4 A5 A6 A7 A8 A9
85
Page 92
Appendix B
Specifications
AC Input Unit C200H-IA122/IA122V Rated Input Voltage
100 to 120 VAC 50/60 Hz
Operating Input Voltage
85 to 132 VAC 50/60 Hz
Input Impedance
9.7 kΩ (50 Hz), 8 kΩ (60 Hz)
Input Current
10 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Response Time
35 ms max. (at 100 VAC, 25°C)
OFF Response Time
55 ms max. (at 100 VAC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
300 g max./400 g max. (IA122V)
Dimensions
B-shape
Circuit Configuration IN
100 to 120 VAC
IN
0.33 µF 470 Ω Internal circuit
330 kΩ COM
910 Ω
Input indicator
Terminal Connections
1 3 5 100 to 120 VAC
7 9 11 13 15 COM
86
B0 A0 A1 A2 A3
0
B1
2
B2
4
B3
6
B4
8
A4
B5 10
A5
B6 12 B7 14
A6 A7 A8
B8
NC
B9
NC
Page 93
Appendix B
Specifications
AC Input Unit C200H-IA221 Rated Input Voltage
200 to 240 VAC 50/60 Hz
Operating Input Voltage
170 to 264 VAC 50/60 Hz
Input Impedance
21 kΩ (50 Hz), 18 kΩ (60 Hz)
Input Current
10 mA typical (at 200 VAC)
ON Voltage
120 VAC min.
OFF Voltage
40 VAC max.
ON Response Time
35 ms max. (at 200 VAC, 25°C)
OFF Response Time
55 ms max. (at 200 VAC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
0.15 µF 820 Ω
200 to 240 VAC
Internal circuit
680 kΩ 910 Ω
COM
Input indicator
Terminal Connections 0 A0 1 2 200 to 240 VAC
3 4 5 6 7 COM
NC
A1 A2 A3 A4 A5 A6 A7 A8 A9
87
Page 94
Appendix B
Specifications
AC Input Unit C200H-IA222/IA222V Rated Input Voltage
200 to 240 VAC 50/60 Hz
Operating Input Voltage
170 to 264 VAC 50/60 Hz
Input Impedance
21 kΩ (50 Hz), 18 kΩ (60 Hz)
Input Current
10 mA typical (at 200 VAC)
ON Voltage
120 VAC min.
OFF Voltage
40 VAC max.
ON Response Time
35 ms max. (at 200 VAC, 25°C)
OFF Response Time
55 ms max. (at 200 VAC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
300 g max./400 g max. (IA222V)
Dimensions
B-shape
Circuit Configuration IN
IN
0.15 µF 680 Ω
200 to 240 VAC
Internal circuit
680 kΩ COM
910 Ω
Input indicator
Terminal Connections
1 3 5 200 to 240 VAC
7 9 11 13 15 COM
88
B0 A0 A1 A2 A3
0
B1
2
B2
4
B3
6
B4
8
A4
B5 10
A5
B6 12 B7 14
A6 A7 A8
B8
NC
B9
NC
Page 95
Appendix B
Specifications
No-Voltage Contact Input Unit C200H-ID001 Input Voltage Input Impedance
No-voltage contact/NPN output type (negative common) 3 kΩ
Input Current
7 mA typical
ON Voltage
(14.4 VDC min.)
OFF Voltage
(5.0 VDC max.)
ON Response Time
1.5 ms max. (no-voltage contact, at 25°C)
OFF Response Time
1.5 ms max. (no-voltage contact, at 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration Current
IN
IN
COM
3 kΩ 0.01 µF
Internal circuit
1.8 kΩ
Input indicator
0.3 A, 24 VDC Power supply
+ Internal 24 VDC – power supply CPU Unit, Expansion I/O Power Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU Unit, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.
Terminal Connections 0 1 2 3 Current (NPN output)
4 5 6 7 COM NC
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
89
Page 96
Appendix B
Specifications
No-Voltage Contact Input Unit C200H-ID002 Input Voltage Input Impedance
No-voltage contact/NPN output type (positive common) 3 kΩ
Input Current
7 mA typical
ON Voltage
(14.4 VDC min.)
OFF Voltage
(5.0 VDC max.)
ON Response Time
1.5 ms max. (no-voltage contact, at 25°C)
OFF Response Time
1.5 ms max. (no-voltage contact, at 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
COM
3 kΩ 0.01 µF
Internal circuit
1.8 kΩ
Current
Input indicator
0.3 A, 24 VDC Power supply
+ Internal 24 VDC – power supply CPU Unit, Expansion I/O Power Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU Unit, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.
Terminal Connections 0 1 2 3 Current (PNP output)
4 5 6 7 COM NC
90
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
Page 97
Appendix B
Specifications
DC Input Unit C200H-ID211 Rated Input Voltage
12 to 24 VDC
Operating Input Voltage
10.2 to 26.4 VDC
Input Impedance
2 kΩ
Input Current
10 mA (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
1.5 ms max. (at 24 VDC, 25°C)
OFF Response Time
1.5 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (8 point/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
2 kΩ
0.01 µF
Internal circuit
1.8 kΩ
COM
12 to 24 VDC
Input indicator
Terminal Connections 0 1 2 3 12 to 24 VDC
4 5 6 7 COM
NC
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
91
Page 98
Appendix B
Specifications
DC Input Unit C200H-ID212 Rated Input Voltage
24 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Input Impedance
3 kΩ
Input Current
7 mA (at 24 VDC)
ON Voltage
14.4 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
1.5 ms max. (at 24 VDC, 25°C)
OFF Response Time
1.5 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration IN
IN
3 kΩ
0.01 µF
Internal circuit
1.8 kΩ
COM
24 VDC
Input indicator
Terminal Connections
1 3 5 7 24 VDC
9 11 13 15 COM
92
A0 A1 A2 A3 A4 A5 A6 A7 A8
B0
0
B1
2
B2
4
B3
6
B4
8
B5 10 B6 12 B7 14 B8
NC
B9
NC
Page 99
Appendix B
Specifications
AC/DC Input Unit C200H-IM211 Rated Input Voltage
12 to 24 VDC
Operating Input Voltage
10.2 to 26.4 VAC/DC 50/60 Hz
Input Impedance
2 kΩ
Input Current
10 mA typical (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
15 ms max. (at 24 VDC, 25°C)
OFF Response Time
15 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
COM
2 kΩ 0.01 µF
1.8 kΩ
Internal circuit
12 to 24 VAC/DC Input indicator
Terminal Connections 0 1 2 3 12 to 24 VAC/DC
4 5 6 7 COM
NC
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
93