The text of a manual · part 14 of 25
SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: Appendix, pages 80 to 89
Pages 80 to 89 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 80
Appendix A Standard Models C200H Racks Name Backplane (same for all Racks)
CPU Rack
CPU Units
Memory Units
Expansion I/O Racks
EPROM I/O Power Supply Units I/O Connecting Cables (max. total length: 12 m)
Specifications
Model number
10 slots 8 slots 5 slots 3 slots
C200H-BC101-V2 C200H-BC081-V2 C200H-BC051-V2 C200H-BC031-V2 w/built-in power supply (100 to 120/200 to 240 VAC); Output current: 4.6 A (3.2 A to I/O Units) w/built-in power supply (24 VDC); Output current: 3 A (1.6 A to I/O Units) w/built-in power supply (100 to 120/200 to 240 VAC); Output current: 4.6 A (3.0 A to I/O Units);
C200H-CPU21-E
Can support SYSMAC NET Link/SYSMAC LINK Units. CMOS-RAM Units; battery back-up UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words CMOS-RAM Units; battery back-up; UM: 3K words; with clock DM: 1K words UM: 7K words; DM: 1K words CMOS-RAM Units; capacitor back-up UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words EPROM Unit UM: 7K words; (EPROM ordered separately) DM: 1K words EEPROM Units UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words EEPROM Units with clock UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words 27128; 150 ns; write voltage: 12.5 V 100 to 120/200 to 240 VAC (selectable) 24 VDC 30 cm 70 cm 2m 5m 10 m
C200H-CPU23-E C200H-CPU31-E
C200H-MR431 C200H-MR831 C200H-MR433 C200H-MR833 C200H-MR432 C200H-MR832 C200H-MP831 C200H-ME431 C200H-ME831 C200H-ME432 C200H-ME832 ROM-ID-B C200H-PS221 C200H-PS211 C200H-CN311 C200H-CN711 C200H-CN221 C200H-CN521 C200H-CN131
73
Page 81
Appendix A
Standard Models
C200H Standard I/O Units Name Input Units
AC Input Units
DC Input Units
AC/DC Input Units Output Units
Relay Output Units
Specifications 8 pts
100 to 120 VAC
C200H-IA121
16 pts
100 to 120 VAC
C200H-IA122/IA122V
8 pts
200 to 240 VAC
C200H-IA221
16 pts
200 to 240 VAC
C200H-IA222/IA222V
8 pts
No-voltage contact; NPN
C200H-ID001
8 pts
No-voltage contact; PNP
C200H-ID002
8 pts
12 to 24 VDC
C200H-ID211
16 pts
24 VDC
C200H-ID212
8 pts
12 to 24 VAC/DC
C200H-IM211
16 pts
24 VAC/DC
C200H-IM212
8 pts 12 pts 16 pts
2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VAC (For resistive loads)
C200H-OC221 C200H-OC222 C200H-OC2251, 2
5 pts
C200H-OC223
8 pts
2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 1 A, 120 VAC
8 pts
1.2 A, 120 VAC
C200H-OA122-E
8 pts
1 A, 250 VAC
C200H-OA221
8 pts
1.2 A 250 VAC
C200H-OA223
12 pts
0.3 A, 250 VAC
C200H-OA222V
12 pts
0.5 A, 250 VAC
C200H-OA224
8 pts 12 pts 16 pts
1 A, 12 to 48 VDC 0.3 A, 24 VDC 0.3 A, 24 VDC
C200H-OD411 C200H-OD211 C200H-OD2121
8 pts
2.1 A, 24 VDC
C200H-OD213
8 pts 8 pts
0.8 A, 24 VDC; source type (PNP); with load C200H-OD214 short protection 0.3 A, 5 to 24 VDC; source type (PNP) C200H-OD216
12 pts
0.3 A, 5 to 24 VDC; source type (PNP)
12 pts
1 A, 24 VDC; source type (PNP); with load C200H-OD21A short protection 0.1 to 1 s, 1 to 10 s, 10 to 60 s, or 1 min to C200H-TM001 10 min (switchable) Connector with lead wire (2 m) for 1 external C4K-CN223 resistor
8 pts Triac Output Units
Transistor Output Units
Analog Timer Unit
4 timer pts Variable Resistor Connector (Related Product)
Standard B7A Interface Units
Model number
16 input Connects to B7A Link Terminals. pts 16 output pts
C200H-OC224 C200H-OA121-E
C200H-OD217
C200H-B7AI1 C200H-B7AO11
Note 1. C200H-OD212/OD21A Transistor Output Unit, C200H-OC225 Contact Output Unit and C200H-B7AO1 B7A Interface Unit must be mounted to either a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200HBC081-V1/V2, or C200H-BC101-V1/V2 Backplane. 2. The C200H-OC225 might overheat if more than 8 outputs are turned ON simultaneously.
74
Page 82
Appendix A
Standard Models
C200H Group-2 High-density I/O Units Name DC Input Unit
Transistor Output Units
Specifications
Model number
64 pts
12 VDC
C200H-ID111
32 pts.
24 VDC
C200H-ID216
64 pts.
24 VDC
C200H-ID217
32 pts. 64 pts.
16 mA 4.5 VDC to 100 mA 26.4 VDC 16 mA 4.5 VDC to 100 mA 26.4 VDC
C200H-OD218 C200H-OD219
C200H Group-2 B7A Interface Units Name Group-2 B7A Interface Units
Specifications Connects to B7A Link Terminals.
32 input pts 32 output pts 16 input pts and 16 output points 32 input pts and 32 output points
Model number C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22
C200H Special I/O Units All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit. Name HighDC Input density I/O Units Units Transistor Output Units DC Input/ Transistor Output Units
Specifications
Model number
32 pts
5 VDC (TTL inputs); with high-speed input function
C200H-ID501
32 pts
24 VDC; with high-speed inputs
C200H-ID215
32 pts 32 pts
0.1 A, 24 VDC (usable as 128-point dynamic output unit) C200H-OD215 35 mA, 5 VDC (TTL outputs) (usable as 128-point dy- C200H-OD501 namic output unit) 16 input/ 12-VDC inputs; with high-speed input function C200H-MD115 16 output pts 0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 24-VDC inputs; with high-speed input function C200H-MD215 16 output pts 0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 5 VDC (TTL inputs); with high speed input function 35 C200H-MD501 16 output pts mA, 5 VDC Output (TTL outputs) (usable as 128-point dynamic input unit)
Analog I/O Units
Analog Input Units Analog Output Unit
Temperature Sensor Units
Temperature Control Units
4 to 20 mA, 1 to 5/0 to 10 V; 4 inputs 4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V; 8 inputs 4 to 20 mA, 1 to 5/0 to 10 V; 2 outputs 4 to 20 mA, –10 to 10 V; 4 outputs Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs Thermocouple (K(CA) or L(Fe-CuNi)) (switchable); 4 inputs Platinum resistance thermometer (JPt) (switchable), DIN standards; 4 inputs Platinum resistance thermometer (Pt) (switchable); 4 inputs Thermocou- Transistor output ple Voltage output Current output Platinum re- Transistor output sistance Voltage output thermomeCurrent output ter
C200H-AD001 C200H-AD002 C200H-DA001 C200H-DA002 C200H-TS001 C200H-TS002 C200H-TS101 C200H-TS102 C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101 C200H-TC102 C200H-TC103
75
Page 83
Appendix A
Standard Models Name Heat/Cool Temperature Control Units
PID Control Units
Position Control Units
Cam Positioner Unit
High-speed Counter Units
ASCII Unit Connecting Cable
Specifications Thermocou- Transistor output ple Voltage output Current output Platinum re- Transistor output sistance Voltage output thermomeCurrent output ter
Model number C200H-TV001 C200H-TV002 C200H-TV003 C200H-TV101
Transistor output (open collector); 4 to 20 mA/1 to 5 V/0 to 5V/0 to 10 V inputs (selectable) Voltage output; 4 to 20 mA/1 to 5 V/0 to 5V/0 to 10 V inputs (selectable) Current output; 4 to 20 mA/1 to 5 V/0 to 5V/0 to 10 V inputs (selectable) 1 axis Pulse output; speeds: 1 to 100,000 pps 1 axis Pulse output; directly connectable to servomotor driver; compatible with line driver; speeds: 1 to 250,000 pps 2 axis Pulse output; 1 to 250,000 pps, 53 pts per axis Detects angles of rotation by means of a resolver and provides ON and OFF outputs at specified angles. A maximum of 48 cam outputs (16 external outputs and 32 internal outputs) maximum are available.
C200H-PID01
1 axis
C200H-CT001-V1
C200H-TV102 C200H-TV103
Pulse input; counting speed: 50 kcps; 5 VDC/12 VDC/24 VDC 1 axis Pulse input; counting speed: 75 kcps; RS-422 line driver 2 axis Pulse input; counting speed: 75 kcps; RS-422 line driver; 7-digit BCD 24K-byte RAM and 24K-byte EEPROM are built-in. RS-232C For connecting the ASCII Unit to the FIT10 (9P/25P) Cable length: 2 m
ID Sensor Units
Voice Unit
C200H-PID03 C200H-NC111 C200H-NC112 C200H-NC211 C200H-CP114
C200H-CT002 C200H-CT021 C200H-ASC02 CV500-CN228
Local application, electromagnetic coupling Remote application, microwave transmissions Read/Write Electromagnetic type Head Microwave type Data Carrier SRAM type for V600-H series. (see note) EEPROM type for V600-H series. 60 messages max.; message length: 32, 48, or 64 s (switchable) Connecting RS-232C Cable For connecting the Voice Unit to the FIT10 (6P/25P) Cable length: 2 m
Fuzzy Logic Unit
C200H-PID02
C200H-IDS01-V1 C200H-IDS21 V600-H series V620-H series V600-DjjRjj V600-DjjPjj C200H-OV001 C200H-CN224
Up to 8 inputs and 4 outputs. (I/O to and from specified data area words) C200H-FZ001
Note For Read/Write Head and Data Carrier combinations, refer to the V600 FA ID System R/W Heads and EEPROM Data Carriers Operation Manual and Supplement or V600 FA ID System R/W Heads and SRAM Data Carriers Operation Manual and Supplement.
C200H Link Units Name Host Link Units
Specifications Rack-mounting
CPU Unit-mounting
76
C200H only
Model number APF/PCF
C200H-LK101-PV1
RS-422
C200H-LK202-V1
RS-232C
C200H-LK201-V1
C1000H/C2000H
PCF
3G2A6-LK101-EV1
C500
APF/PCF
3G2A6-LK101-PEV1
Page 84
Appendix A
Standard Models Name
PC Link Unit
Specifications
Model number
C200H
RS-232C
3G2A6-LK201-EV1
C120
RS-422
3G2A6-LK202-EV1
RS-485
C200H-LK401
APF/PCF Wired APF/PCF
C200H-RM001-PV1 C200H-RM201 C200H-RT001-P
Remote I/O Master Units
Single level: 32 Units Multilevel: 16 Units Up to two per PC; connectable to up to 5 Slaves per PC total
Remote I/O Slave Units
100 to 120/200 to 240 VAC (switchable) 24 VDC
C200H-RT002-P
100 to 120/200 to 240 VAC (switchable)
Wired
24 VDC
C200H-RT201 C200H-RT202
Optional Products Name
Specifications
Model number
I/O Unit Cover
Cover for 10-pin terminal block
Terminal Block Covers
Connector Cover
Short protection for 10-pin terminal block (package of 10 cov- C200H-COV02 ers); 8 pts Short protection for 19-pin terminal block (package of 10 cov- C200H-COV03 ers); 12 pts Protective cover for unused I/O Connecting Cable connectors C500-COV01
Space Unit
Used for vacant slots
C200H-SP001
Battery Set
For: C200H-MRj31/MRj33 RAM Memory Units C200H-MEj32 EEPROM Memory Unit C200H-CPU31-E CPU Unit
C200H-BAT09
Relay
24 VDC
G6B-1174P-FD-US DC24
Backplane Insulation Plates
For 10-slot Backplane
C200H-ATTA1
For 8-slot Backplane
C200H-ATT81
For 5-slot Backplane
C200H-ATT51
For 3-slot Backplane
C200H-ATT31
For 5-slot Backplane
C200H-ATT53
For 8-slot Backplane
C200H-ATT83
For 3-slot Backplane
C200H-ATT33
To secure Memory Unit to CPU Unit Solder terminal; 40 pin with connector cover Straight type Right-angle type Solderless terminal (crimp-type); 40 pin with Straight type connector cover Right-angle type Pressure welded terminal; 40 pin
C200H-ATT03
Solder terminal; 24 pin with connector cover
C500-CE241
Solderless terminal; 24 pin with connector cover (crimp-type)
C500-CE242
Pressure welded terminal; 24 pin
C500-CE243
I/O Brackets
Memory Unit Lock Fitting External Connectors
C200H-COV11
C500-CE401 C500-CE404 C500-CE402 C500-CE405 C500-CE403
Note 1. When ordering, specify the model name (any component of which is not sold separately). 2. Order the pressfit tool from the manufacturer.
77
Page 85
Appendix A
Standard Models
Optical Units Name Optical I/O Units
Specifications 100 to 120 VAC power supply
No-voltage Input Units 8 pts. AC/DC Input Units AC Input Units Relay Output Units
3G5A2-ID001-PE 3G5A2-ID001-E 3G5A2-IM211-PE
PCF
3G5A2-IM211-E
APF/PCF
3G5A2-IA121-PE
PCF
3G5A2-IA121-E
APF/PCF
3G5A2-OC221-PE
PCF
3G5A2-OC221-E
1A, 100 to 120/200 to 240 VAC (w/built-in surge killer) 8 pts.
APF/PCF
3G5A2-OA222-PE
PCF
3G5A2-OA222-E
Connected between 32nd and 33rd Units when connecting more than 33 Units in a Remote Subsystem; power supply: 85 to 250 VAC.
APF/PCF
3G5A2-RPT01-PE
PCF
3G5A2-RPT01-E
12 to 24 VAC/DC 8 pts. 100 to 120 VAC 8 pts. 2A, 250 VAC/24 VDC (w/relay socket) 8 pts.
Triac Output Units
Repeater Units
Model no. APF/PCF PCF APF/PCF
100 to 120/200 to 240 VAC power supply
Link Adapters Name
Specifications
Link Adapters
Model no.
3 RS-422 connectors
3G2A9-AL001
3 optical connectors (APF/PCF)
3G2A9-AL002-PE
3 optical connectors (PCF)
3G2A9-AL002-E
1 connector each for APF/PCF, RS-422, and RS-232C
3G2A9-AL004-PE
1 connector each for PCF, RS-422, and RS-232C
3G2A9-AL004-E
1 connector each for APF/PCF and APF
3G2A9-AL005-PE
1 connector each for PCF and AGF
3G2A9-AL005-E
O/E converter; 1 connector for RS-485, 1 connector each for APF/PCF
B500-AL007-PE
Used for on-line removal of FIT or SYSMAC NET Link Units from the SYSMAC NET Link System, SYSMAC NET Optical Link Adapter 3 connectors for APF/PCF.
B700-AL001
DIN Products Name
Specifications
Model number
DIN Track Mounting Bracket 1 set (2 included)
C200H-DIN01
DIN Track
Length: 50 cm; height: 7.3 cm
PFP-50N
Length: 1 m; height: 7.3 cm
PFP-100N
Length: 1 m; height: 16 mm
PFP-100N2
End Plate
---
PFP-M
Spacer
---
PFP-S
78
Page 86
Appendix A
Standard Models
Optical Fiber Cable Plastic Optical Fiber Cable (APF) APF stands for “All-Plastic Fiber.” This cable can be used to connect only Units having the suffix “-P” in their model number. The maximum length is 20 m. The 3G5A2-PF002 cable comes without connectors and must be assembled by the user. Product
Description
Model no.
Plastic Optical Fiber Cable
Cable only (optical connectors not provided) Order in units of 5 m for cable less than 100 m, or in units of 200 m or 500 m.
3G5A2-PF002
Optical Connector A
2 pcs (brown),for plastic Optical fiber 10 m long max.
3G5A2-CO001
Optical Connector B
2 pcs (black) for plastic Optical fiber 8 to 20 m long
3G5A2-CO002
Plastic Optical Fiber Cable
1 m, w/optical connector A provided at both ends
3G5A2-PF101
Optical Fiber Processing Kit
Accessory: 125-mm nipper (Muromoto Tekko’s 550M) for APF
3G2A9-TL101
Plastic-Clad Optical Fiber Cable (PCF) PCF stands for “Plastic-Clad Fiber.” This cable can be used to connect any Units. The maximum length for Units having the suffix “-P” in their model number is 200 m. The maximum length for Units without the suffix “-P” in their model number is 800 m. Product Optical Fiber Cables (for indoors)
Optical Fiber Cable (for outdoors)
Description 0.1 m, w/connector 1 m, w/connector 2 m, w/connector
Ambient temperature: –10° to 70°C
Model no. 3G5A2-OF011 3G5A2-OF101 3G5A2-OF201
3 m, w/connector
3G5A2-OF301
5 m, w/connector
3G5A2-OF501
10 m, w/connector
3G5A2-OF111
20 m, w/connector
3G5A2-OF211
30 m, w/connector
3G5A2-OF311
40 m, w/connector
3G5A2-OF411
50 m, w/connector
3G5A2-OF511
1 to 500 m (Order in Units of 10 m) Ambient temperature: –10° to 70°C 501 to 800 m (Order in Units of 10 m) Ambient temperature: 0° to 55°C (Must not be subjected to direct sunlight)
3G5A2-OF002
Crystal Optical Fiber Cable (AGF) AGF stands for “All-Glass Fiber.” Crystal optical fiber cable is not available from OMRON. Cable Length The connectors may be difficult to attach to the cables. Therefore, always leave a little extra length when cutting the cable. The lengths given for pre-assembled cables are as shown below.
Fiber length (m)
79
Page 87
Appendix A
Standard Models
Peripheral Devices Name Hand-held Programming Console Data Access Console
Specifications
Model number
Vertical, w/backlight Connecting cable required; sold separately Vertical, w/backlight Connecting cable required; sold separately For handheld console, 2 m
C200H-PRO27-E C200H-DAC01-E
Programming and Data Access Console Connecting For handheld console, 4 m Cables Panel Mounting Bracket Programming Console Mounting Bases Data Setting Console
C200H-CN422
Mounts Hand-held Programming Console or Data Access Con- C200H-ATT01 sole to a panel. Used to mount 16- or 32-point I/O Units to 29-mm height C200H-BP001 rightmost two slots when mounting periph49-mm height C200H-BP002 erals directly to CPU Unit. Used for data input and process value display for the C200H-DSC01 C200H-TCjjj/C200H-TVjjj/C200H-PIDjj.
Data Setting Console Con- For C200H-DSC01 necting Cables PROM Writer
C200H-CN222
2m
C200H-CN225
4m
C200H-CN425
Applicable to all C-series PCs.
C500-PRW06
Write voltages: 12.5 or 21 V Floppy Disk Interface Unit
Applicable to all C-series PCs.
3G2C5-FDI03-E
Printer Interface Unit
Applicable to all C-series PCs.
3G2A5-PRT01-E
Applicable to C200H, C1000H, or C2000H.
C2000-MP103-EV3
Connects the C200H CPU Unit to a GPC or FIT.
C200H-IP006
Memory Pack Peripheral Interface Unit
Connecting Cable sold separately. Graphic Programming Consoles Memory Pack
100- to 120-VAC power supply (Comments supported.)
3G2C5-GPC03-E
Applicable to C200H, C1000H, or C2000H.
3G2C5-MP304-EV3
CRT Interface Unit
For connection between GPC and CRT
C500-GDI01
SYSMAC Support Software (SSS) Product SYSMAC Support Software
80
Description 3.5”, 2HD for IBM PC/AT compatible Connection Cable
Model no. C500-ZL3AT1-E CQM1-CIF02 CV500-CIF01
Page 88
Appendix A
Standard Models
SYSMAC LINK Units and SYSMAC NET Link Units Name SYSMAC LINK Unit
Specifications Wired via coaxial cable. Must be mounted to rightmost 2 slots on Rack with C200H-CPU31-E Wired via optical fiber cable. Bus Connection Unit required separately. May be used with APS Power Supply Unit.
Model number 918 data link words 2,966 data link words 918 data link words 2,966 data link words
C200HW-SLK23 C200HW-SLK24 C200HW-SLK13 C200HW-SLK14
Terminator
One required for each node at ends of System
C1000H-TER01
Attachment Stirrup
Provided with SYSMAC LINK Unit
C200H-TL001
F Adapter
---
C1000H-CE001
F Adapter Cover Communications Cable
---
C1000H-COV01
Coaxial cables
ECXF5C-2V 5C-2V C200H-APS03
Auxiliary Power Supply Unit SYSMAC NET Link Unit Power Supply Adapter Power Cable Bus Connection Unit
Manufactured by Hitachi Manufactured by Fujigura Supplies backup power to either one or two SYSMAC LINK Units. One C200H-CN111 Power Connecting Cable included. Must be mounted to rightmost 2 slots on Rack with C200HCPU31-E Required when supplying power from For 1 Unit Central Power Supply For 2 Units Connects Power Supply Adapter and SYSFor 1 Unit MAC NET Link Unit For 2 Units Connects SYSMAC LINK Unit or SYSMAC For 1 Unit NET Link Unit to CPU Unit For 2 Units
C200HS-SNT32 C200H-APS01 C200H-APS02 C200H-CN111 C200H-CN211 C200H-CE001 C200H-CE002
81
Page 89
Appendix B Specifications The following figures and tables provide specifications for each Unit of the C200H. I/O Units may take on one of three different shapes and are sometimes referred to as A-shape Units, B-shape Units, or E-shape Units. Group-2 High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape Units or D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these five shapes of I/O Unit.
CPU Units and Power Supplies General Specifications Item Supply Voltage
C200H-CPU21-E/CPU31-E, PS221
C200H-CPU23-E, PS211 24 VDC
Operating Voltage Range
100 to 120/200 to 240 VAC selectable 50/60 Hz 85 to 132/170 to 264 VAC
Power Consumption
120 VA max.
40 W max.
Surge Current
30 A max.
30 A max.
Output Capacity
Fuse
CPU-21-E: 4.6 A 5 VDC (3.2 A supplied to I/O Units) CPU-23-E: 3 A 5 VDC (1.6 A supplied to I/O Units) CPU-31-E: 4.6 A 5 VDC (3.0 A supplied to I/O Units) Expansion I/O Rack: 3 A 5 VDC (2.7 A supplied to I/O Units) 2 A 250 V 5.2 dia. x 20 (MF51NR) 2 A 125 V 5.2 dia. x 20 (MF51NR)
24 VDC Output
0.3 A 24 VDC +10%/–20%
Insulation Resistance*
20 MΩ between AC terminals and the GR See caution. terminal at 500 VDC 2,000 VAC 50/60 Hz for 1 minute between AC terminals and housing 500 VAC 50/60 Hz for 1 minute between DC terminals and housing Leakage current: 10 mA max. 1,500 Vp-p, pulse width: 100 ns to 1 µs, rise time: 1 ns
Dielectric Strength* Noise Immunity
20.4 to 26.4 VDC
None
Vibration
Mechanical durability: 10 to 35 Hz, 1 mm double amplitude (24.5 m/s2) in X, Y, and Z directions, for 2 hours each (When mounted on DIN track, 16.7 Hz, 1 mm double amplitude (4.9 m/s2) in X, Y, and Z directions, for 1 hour each) Malfunction durability: 2 to 55 Hz, 19.6 m/s2, in X, Y, and Z directions, for 20 minutes each (When mounted on DIN track, 2 to 55 Hz, 2.94 m/s2, in X, Y, and Z directions, for 20 minutes each)
Shock
98 m/s2 in X, Y, and Z directions, 3 times each
Ambient Temperature
Operating: 0° to 55°C (0° to 45°C for Programming Console) Storage: –20° to 65°C
Humidity
35% to 85% (without condensation)
Atmosphere
Must be free of the following: • Corrosive gases • Abrupt temperature changes • Direct sunlight • Dust, salt, or metal filings • Water, oil, or chemicals
Grounding
Less than 100 Ω
Enclosure Rating
Mounted in a panel
Weight
6 kg max.
! Caution
*Internal components might be damaged if insulation resistance or dielectric strength tests for the AC power supply are repeated many times with the LG and GR terminals connected. Do not conduct a dielectric strength test on the C200H-CPU23-E, PS211, RT002-P, or RT202 Units. The power supply input line and internal circuit of the 24 VDC Power Supply are not isolated from each other; do not conduct insulation resistance or dielectric strength tests. If an insulation resistance test or dielectric strength test over 50 VDC is conducted, the Power Supply will be damaged.
83