Page 80

Appendix A Standard Models C200H Racks Name Backplane (same for all Racks)

CPU Rack

CPU Units

Memory Units

Expansion I/O Racks

EPROM I/O Power Supply Units I/O Connecting Cables (max. total length: 12 m)

Specifications

Model number

10 slots 8 slots 5 slots 3 slots

C200H-BC101-V2 C200H-BC081-V2 C200H-BC051-V2 C200H-BC031-V2 w/built-in power supply (100 to 120/200 to 240 VAC); Output current: 4.6 A (3.2 A to I/O Units) w/built-in power supply (24 VDC); Output current: 3 A (1.6 A to I/O Units) w/built-in power supply (100 to 120/200 to 240 VAC); Output current: 4.6 A (3.0 A to I/O Units);

C200H-CPU21-E

Can support SYSMAC NET Link/SYSMAC LINK Units. CMOS-RAM Units; battery back-up UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words CMOS-RAM Units; battery back-up; UM: 3K words; with clock DM: 1K words UM: 7K words; DM: 1K words CMOS-RAM Units; capacitor back-up UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words EPROM Unit UM: 7K words; (EPROM ordered separately) DM: 1K words EEPROM Units UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words EEPROM Units with clock UM: 3K words; DM: 1K words UM: 7K words; DM: 1K words 27128; 150 ns; write voltage: 12.5 V 100 to 120/200 to 240 VAC (selectable) 24 VDC 30 cm 70 cm 2m 5m 10 m

C200H-CPU23-E C200H-CPU31-E

C200H-MR431 C200H-MR831 C200H-MR433 C200H-MR833 C200H-MR432 C200H-MR832 C200H-MP831 C200H-ME431 C200H-ME831 C200H-ME432 C200H-ME832 ROM-ID-B C200H-PS221 C200H-PS211 C200H-CN311 C200H-CN711 C200H-CN221 C200H-CN521 C200H-CN131

73

Page 81

Appendix A

Standard Models

C200H Standard I/O Units Name Input Units

AC Input Units

DC Input Units

AC/DC Input Units Output Units

Relay Output Units

Specifications 8 pts

100 to 120 VAC

C200H-IA121

16 pts

100 to 120 VAC

C200H-IA122/IA122V

8 pts

200 to 240 VAC

C200H-IA221

16 pts

200 to 240 VAC

C200H-IA222/IA222V

8 pts

No-voltage contact; NPN

C200H-ID001

8 pts

No-voltage contact; PNP

C200H-ID002

8 pts

12 to 24 VDC

C200H-ID211

16 pts

24 VDC

C200H-ID212

8 pts

12 to 24 VAC/DC

C200H-IM211

16 pts

24 VAC/DC

C200H-IM212

8 pts 12 pts 16 pts

2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VDC (For resistive loads) 2 A, 250 VAC/24 VAC (For resistive loads)

C200H-OC221 C200H-OC222 C200H-OC2251, 2

5 pts

C200H-OC223

8 pts

2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 1 A, 120 VAC

8 pts

1.2 A, 120 VAC

C200H-OA122-E

8 pts

1 A, 250 VAC

C200H-OA221

8 pts

1.2 A 250 VAC

C200H-OA223

12 pts

0.3 A, 250 VAC

C200H-OA222V

12 pts

0.5 A, 250 VAC

C200H-OA224

8 pts 12 pts 16 pts

1 A, 12 to 48 VDC 0.3 A, 24 VDC 0.3 A, 24 VDC

C200H-OD411 C200H-OD211 C200H-OD2121

8 pts

2.1 A, 24 VDC

C200H-OD213

8 pts 8 pts

0.8 A, 24 VDC; source type (PNP); with load C200H-OD214 short protection 0.3 A, 5 to 24 VDC; source type (PNP) C200H-OD216

12 pts

0.3 A, 5 to 24 VDC; source type (PNP)

12 pts

1 A, 24 VDC; source type (PNP); with load C200H-OD21A short protection 0.1 to 1 s, 1 to 10 s, 10 to 60 s, or 1 min to C200H-TM001 10 min (switchable) Connector with lead wire (2 m) for 1 external C4K-CN223 resistor

8 pts Triac Output Units

Transistor Output Units

Analog Timer Unit

4 timer pts Variable Resistor Connector (Related Product)

Standard B7A Interface Units

Model number

16 input Connects to B7A Link Terminals. pts 16 output pts

C200H-OC224 C200H-OA121-E

C200H-OD217

C200H-B7AI1 C200H-B7AO11

Note 1. C200H-OD212/OD21A Transistor Output Unit, C200H-OC225 Contact Output Unit and C200H-B7AO1 B7A Interface Unit must be mounted to either a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200HBC081-V1/V2, or C200H-BC101-V1/V2 Backplane. 2. The C200H-OC225 might overheat if more than 8 outputs are turned ON simultaneously.

74

Page 82

Appendix A

Standard Models

C200H Group-2 High-density I/O Units Name DC Input Unit

Transistor Output Units

Specifications

Model number

64 pts

12 VDC

C200H-ID111

32 pts.

24 VDC

C200H-ID216

64 pts.

24 VDC

C200H-ID217

32 pts. 64 pts.

16 mA 4.5 VDC to 100 mA 26.4 VDC 16 mA 4.5 VDC to 100 mA 26.4 VDC

C200H-OD218 C200H-OD219

C200H Group-2 B7A Interface Units Name Group-2 B7A Interface Units

Specifications Connects to B7A Link Terminals.

32 input pts 32 output pts 16 input pts and 16 output points 32 input pts and 32 output points

Model number C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22

C200H Special I/O Units All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit. Name HighDC Input density I/O Units Units Transistor Output Units DC Input/ Transistor Output Units

Specifications

Model number

32 pts

5 VDC (TTL inputs); with high-speed input function

C200H-ID501

32 pts

24 VDC; with high-speed inputs

C200H-ID215

32 pts 32 pts

0.1 A, 24 VDC (usable as 128-point dynamic output unit) C200H-OD215 35 mA, 5 VDC (TTL outputs) (usable as 128-point dy- C200H-OD501 namic output unit) 16 input/ 12-VDC inputs; with high-speed input function C200H-MD115 16 output pts 0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 24-VDC inputs; with high-speed input function C200H-MD215 16 output pts 0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 5 VDC (TTL inputs); with high speed input function 35 C200H-MD501 16 output pts mA, 5 VDC Output (TTL outputs) (usable as 128-point dynamic input unit)

Analog I/O Units

Analog Input Units Analog Output Unit

Temperature Sensor Units

Temperature Control Units

4 to 20 mA, 1 to 5/0 to 10 V; 4 inputs 4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V; 8 inputs 4 to 20 mA, 1 to 5/0 to 10 V; 2 outputs 4 to 20 mA, –10 to 10 V; 4 outputs Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs Thermocouple (K(CA) or L(Fe-CuNi)) (switchable); 4 inputs Platinum resistance thermometer (JPt) (switchable), DIN standards; 4 inputs Platinum resistance thermometer (Pt) (switchable); 4 inputs Thermocou- Transistor output ple Voltage output Current output Platinum re- Transistor output sistance Voltage output thermomeCurrent output ter

C200H-AD001 C200H-AD002 C200H-DA001 C200H-DA002 C200H-TS001 C200H-TS002 C200H-TS101 C200H-TS102 C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101 C200H-TC102 C200H-TC103

75

Page 83

Appendix A

Standard Models Name Heat/Cool Temperature Control Units

PID Control Units

Position Control Units

Cam Positioner Unit

High-speed Counter Units

ASCII Unit Connecting Cable

Specifications Thermocou- Transistor output ple Voltage output Current output Platinum re- Transistor output sistance Voltage output thermomeCurrent output ter

Model number C200H-TV001 C200H-TV002 C200H-TV003 C200H-TV101

Transistor output (open collector); 4 to 20 mA/1 to 5 V/0 to 5V/0 to 10 V inputs (selectable) Voltage output; 4 to 20 mA/1 to 5 V/0 to 5V/0 to 10 V inputs (selectable) Current output; 4 to 20 mA/1 to 5 V/0 to 5V/0 to 10 V inputs (selectable) 1 axis Pulse output; speeds: 1 to 100,000 pps 1 axis Pulse output; directly connectable to servomotor driver; compatible with line driver; speeds: 1 to 250,000 pps 2 axis Pulse output; 1 to 250,000 pps, 53 pts per axis Detects angles of rotation by means of a resolver and provides ON and OFF outputs at specified angles. A maximum of 48 cam outputs (16 external outputs and 32 internal outputs) maximum are available.

C200H-PID01

1 axis

C200H-CT001-V1

C200H-TV102 C200H-TV103

Pulse input; counting speed: 50 kcps; 5 VDC/12 VDC/24 VDC 1 axis Pulse input; counting speed: 75 kcps; RS-422 line driver 2 axis Pulse input; counting speed: 75 kcps; RS-422 line driver; 7-digit BCD 24K-byte RAM and 24K-byte EEPROM are built-in. RS-232C For connecting the ASCII Unit to the FIT10 (9P/25P) Cable length: 2 m

ID Sensor Units

Voice Unit

C200H-PID03 C200H-NC111 C200H-NC112 C200H-NC211 C200H-CP114

C200H-CT002 C200H-CT021 C200H-ASC02 CV500-CN228

Local application, electromagnetic coupling Remote application, microwave transmissions Read/Write Electromagnetic type Head Microwave type Data Carrier SRAM type for V600-H series. (see note) EEPROM type for V600-H series. 60 messages max.; message length: 32, 48, or 64 s (switchable) Connecting RS-232C Cable For connecting the Voice Unit to the FIT10 (6P/25P) Cable length: 2 m

Fuzzy Logic Unit

C200H-PID02

C200H-IDS01-V1 C200H-IDS21 V600-H series V620-H series V600-DjjRjj V600-DjjPjj C200H-OV001 C200H-CN224

Up to 8 inputs and 4 outputs. (I/O to and from specified data area words) C200H-FZ001

Note For Read/Write Head and Data Carrier combinations, refer to the V600 FA ID System R/W Heads and EEPROM Data Carriers Operation Manual and Supplement or V600 FA ID System R/W Heads and SRAM Data Carriers Operation Manual and Supplement.

C200H Link Units Name Host Link Units

Specifications Rack-mounting

CPU Unit-mounting

76

C200H only

Model number APF/PCF

C200H-LK101-PV1

RS-422

C200H-LK202-V1

RS-232C

C200H-LK201-V1

C1000H/C2000H

PCF

3G2A6-LK101-EV1

C500

APF/PCF

3G2A6-LK101-PEV1

Page 84

Appendix A

Standard Models Name

PC Link Unit

Specifications

Model number

C200H

RS-232C

3G2A6-LK201-EV1

C120

RS-422

3G2A6-LK202-EV1

RS-485

C200H-LK401

APF/PCF Wired APF/PCF

C200H-RM001-PV1 C200H-RM201 C200H-RT001-P

Remote I/O Master Units

Single level: 32 Units Multilevel: 16 Units Up to two per PC; connectable to up to 5 Slaves per PC total

Remote I/O Slave Units

100 to 120/200 to 240 VAC (switchable) 24 VDC

C200H-RT002-P

100 to 120/200 to 240 VAC (switchable)

Wired

24 VDC

C200H-RT201 C200H-RT202

Optional Products Name

Specifications

Model number

I/O Unit Cover

Cover for 10-pin terminal block

Terminal Block Covers

Connector Cover

Short protection for 10-pin terminal block (package of 10 cov- C200H-COV02 ers); 8 pts Short protection for 19-pin terminal block (package of 10 cov- C200H-COV03 ers); 12 pts Protective cover for unused I/O Connecting Cable connectors C500-COV01

Space Unit

Used for vacant slots

C200H-SP001

Battery Set

For: C200H-MRj31/MRj33 RAM Memory Units C200H-MEj32 EEPROM Memory Unit C200H-CPU31-E CPU Unit

C200H-BAT09

Relay

24 VDC

G6B-1174P-FD-US DC24

Backplane Insulation Plates

For 10-slot Backplane

C200H-ATTA1

For 8-slot Backplane

C200H-ATT81

For 5-slot Backplane

C200H-ATT51

For 3-slot Backplane

C200H-ATT31

For 5-slot Backplane

C200H-ATT53

For 8-slot Backplane

C200H-ATT83

For 3-slot Backplane

C200H-ATT33

To secure Memory Unit to CPU Unit Solder terminal; 40 pin with connector cover Straight type Right-angle type Solderless terminal (crimp-type); 40 pin with Straight type connector cover Right-angle type Pressure welded terminal; 40 pin

C200H-ATT03

Solder terminal; 24 pin with connector cover

C500-CE241

Solderless terminal; 24 pin with connector cover (crimp-type)

C500-CE242

Pressure welded terminal; 24 pin

C500-CE243

I/O Brackets

Memory Unit Lock Fitting External Connectors

C200H-COV11

C500-CE401 C500-CE404 C500-CE402 C500-CE405 C500-CE403

Note 1. When ordering, specify the model name (any component of which is not sold separately). 2. Order the pressfit tool from the manufacturer.

77

Page 85

Appendix A

Standard Models

Optical Units Name Optical I/O Units

Specifications 100 to 120 VAC power supply

No-voltage Input Units 8 pts. AC/DC Input Units AC Input Units Relay Output Units

3G5A2-ID001-PE 3G5A2-ID001-E 3G5A2-IM211-PE

PCF

3G5A2-IM211-E

APF/PCF

3G5A2-IA121-PE

PCF

3G5A2-IA121-E

APF/PCF

3G5A2-OC221-PE

PCF

3G5A2-OC221-E

1A, 100 to 120/200 to 240 VAC (w/built-in surge killer) 8 pts.

APF/PCF

3G5A2-OA222-PE

PCF

3G5A2-OA222-E

Connected between 32nd and 33rd Units when connecting more than 33 Units in a Remote Subsystem; power supply: 85 to 250 VAC.

APF/PCF

3G5A2-RPT01-PE

PCF

3G5A2-RPT01-E

12 to 24 VAC/DC 8 pts. 100 to 120 VAC 8 pts. 2A, 250 VAC/24 VDC (w/relay socket) 8 pts.

Triac Output Units

Repeater Units

Model no. APF/PCF PCF APF/PCF

100 to 120/200 to 240 VAC power supply

Link Adapters Name

Specifications

Link Adapters

Model no.

3 RS-422 connectors

3G2A9-AL001

3 optical connectors (APF/PCF)

3G2A9-AL002-PE

3 optical connectors (PCF)

3G2A9-AL002-E

1 connector each for APF/PCF, RS-422, and RS-232C

3G2A9-AL004-PE

1 connector each for PCF, RS-422, and RS-232C

3G2A9-AL004-E

1 connector each for APF/PCF and APF

3G2A9-AL005-PE

1 connector each for PCF and AGF

3G2A9-AL005-E

O/E converter; 1 connector for RS-485, 1 connector each for APF/PCF

B500-AL007-PE

Used for on-line removal of FIT or SYSMAC NET Link Units from the SYSMAC NET Link System, SYSMAC NET Optical Link Adapter 3 connectors for APF/PCF.

B700-AL001

DIN Products Name

Specifications

Model number

DIN Track Mounting Bracket 1 set (2 included)

C200H-DIN01

DIN Track

Length: 50 cm; height: 7.3 cm

PFP-50N

Length: 1 m; height: 7.3 cm

PFP-100N

Length: 1 m; height: 16 mm

PFP-100N2

End Plate

---

PFP-M

Spacer

---

PFP-S

78

Page 86

Appendix A

Standard Models

Optical Fiber Cable Plastic Optical Fiber Cable (APF) APF stands for “All-Plastic Fiber.” This cable can be used to connect only Units having the suffix “-P” in their model number. The maximum length is 20 m. The 3G5A2-PF002 cable comes without connectors and must be assembled by the user. Product

Description

Model no.

Plastic Optical Fiber Cable

Cable only (optical connectors not provided) Order in units of 5 m for cable less than 100 m, or in units of 200 m or 500 m.

3G5A2-PF002

Optical Connector A

2 pcs (brown),for plastic Optical fiber 10 m long max.

3G5A2-CO001

Optical Connector B

2 pcs (black) for plastic Optical fiber 8 to 20 m long

3G5A2-CO002

Plastic Optical Fiber Cable

1 m, w/optical connector A provided at both ends

3G5A2-PF101

Optical Fiber Processing Kit

Accessory: 125-mm nipper (Muromoto Tekko’s 550M) for APF

3G2A9-TL101

Plastic-Clad Optical Fiber Cable (PCF) PCF stands for “Plastic-Clad Fiber.” This cable can be used to connect any Units. The maximum length for Units having the suffix “-P” in their model number is 200 m. The maximum length for Units without the suffix “-P” in their model number is 800 m. Product Optical Fiber Cables (for indoors)

Optical Fiber Cable (for outdoors)

Description 0.1 m, w/connector 1 m, w/connector 2 m, w/connector

Ambient temperature: –10° to 70°C

Model no. 3G5A2-OF011 3G5A2-OF101 3G5A2-OF201

3 m, w/connector

3G5A2-OF301

5 m, w/connector

3G5A2-OF501

10 m, w/connector

3G5A2-OF111

20 m, w/connector

3G5A2-OF211

30 m, w/connector

3G5A2-OF311

40 m, w/connector

3G5A2-OF411

50 m, w/connector

3G5A2-OF511

1 to 500 m (Order in Units of 10 m) Ambient temperature: –10° to 70°C 501 to 800 m (Order in Units of 10 m) Ambient temperature: 0° to 55°C (Must not be subjected to direct sunlight)

3G5A2-OF002

Crystal Optical Fiber Cable (AGF) AGF stands for “All-Glass Fiber.” Crystal optical fiber cable is not available from OMRON. Cable Length The connectors may be difficult to attach to the cables. Therefore, always leave a little extra length when cutting the cable. The lengths given for pre-assembled cables are as shown below.

Fiber length (m)

79

Page 87

Appendix A

Standard Models

Peripheral Devices Name Hand-held Programming Console Data Access Console

Specifications

Model number

Vertical, w/backlight Connecting cable required; sold separately Vertical, w/backlight Connecting cable required; sold separately For handheld console, 2 m

C200H-PRO27-E C200H-DAC01-E

Programming and Data Access Console Connecting For handheld console, 4 m Cables Panel Mounting Bracket Programming Console Mounting Bases Data Setting Console

C200H-CN422

Mounts Hand-held Programming Console or Data Access Con- C200H-ATT01 sole to a panel. Used to mount 16- or 32-point I/O Units to 29-mm height C200H-BP001 rightmost two slots when mounting periph49-mm height C200H-BP002 erals directly to CPU Unit. Used for data input and process value display for the C200H-DSC01 C200H-TCjjj/C200H-TVjjj/C200H-PIDjj.

Data Setting Console Con- For C200H-DSC01 necting Cables PROM Writer

C200H-CN222

2m

C200H-CN225

4m

C200H-CN425

Applicable to all C-series PCs.

C500-PRW06

Write voltages: 12.5 or 21 V Floppy Disk Interface Unit

Applicable to all C-series PCs.

3G2C5-FDI03-E

Printer Interface Unit

Applicable to all C-series PCs.

3G2A5-PRT01-E

Applicable to C200H, C1000H, or C2000H.

C2000-MP103-EV3

Connects the C200H CPU Unit to a GPC or FIT.

C200H-IP006

Memory Pack Peripheral Interface Unit

Connecting Cable sold separately. Graphic Programming Consoles Memory Pack

100- to 120-VAC power supply (Comments supported.)

3G2C5-GPC03-E

Applicable to C200H, C1000H, or C2000H.

3G2C5-MP304-EV3

CRT Interface Unit

For connection between GPC and CRT

C500-GDI01

SYSMAC Support Software (SSS) Product SYSMAC Support Software

80

Description 3.5”, 2HD for IBM PC/AT compatible Connection Cable

Model no. C500-ZL3AT1-E CQM1-CIF02 CV500-CIF01

Page 88

Appendix A

Standard Models

SYSMAC LINK Units and SYSMAC NET Link Units Name SYSMAC LINK Unit

Specifications Wired via coaxial cable. Must be mounted to rightmost 2 slots on Rack with C200H-CPU31-E Wired via optical fiber cable. Bus Connection Unit required separately. May be used with APS Power Supply Unit.

Model number 918 data link words 2,966 data link words 918 data link words 2,966 data link words

C200HW-SLK23 C200HW-SLK24 C200HW-SLK13 C200HW-SLK14

Terminator

One required for each node at ends of System

C1000H-TER01

Attachment Stirrup

Provided with SYSMAC LINK Unit

C200H-TL001

F Adapter

---

C1000H-CE001

F Adapter Cover Communications Cable

---

C1000H-COV01

Coaxial cables

ECXF5C-2V 5C-2V C200H-APS03

Auxiliary Power Supply Unit SYSMAC NET Link Unit Power Supply Adapter Power Cable Bus Connection Unit

Manufactured by Hitachi Manufactured by Fujigura Supplies backup power to either one or two SYSMAC LINK Units. One C200H-CN111 Power Connecting Cable included. Must be mounted to rightmost 2 slots on Rack with C200HCPU31-E Required when supplying power from For 1 Unit Central Power Supply For 2 Units Connects Power Supply Adapter and SYSFor 1 Unit MAC NET Link Unit For 2 Units Connects SYSMAC LINK Unit or SYSMAC For 1 Unit NET Link Unit to CPU Unit For 2 Units

C200HS-SNT32 C200H-APS01 C200H-APS02 C200H-CN111 C200H-CN211 C200H-CE001 C200H-CE002

81

Page 89

Appendix B Specifications The following figures and tables provide specifications for each Unit of the C200H. I/O Units may take on one of three different shapes and are sometimes referred to as A-shape Units, B-shape Units, or E-shape Units. Group-2 High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape Units or D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these five shapes of I/O Unit.

CPU Units and Power Supplies General Specifications Item Supply Voltage

C200H-CPU21-E/CPU31-E, PS221

C200H-CPU23-E, PS211 24 VDC

Operating Voltage Range

100 to 120/200 to 240 VAC selectable 50/60 Hz 85 to 132/170 to 264 VAC

Power Consumption

120 VA max.

40 W max.

Surge Current

30 A max.

30 A max.

Output Capacity

Fuse

CPU-21-E: 4.6 A 5 VDC (3.2 A supplied to I/O Units) CPU-23-E: 3 A 5 VDC (1.6 A supplied to I/O Units) CPU-31-E: 4.6 A 5 VDC (3.0 A supplied to I/O Units) Expansion I/O Rack: 3 A 5 VDC (2.7 A supplied to I/O Units) 2 A 250 V 5.2 dia. x 20 (MF51NR) 2 A 125 V 5.2 dia. x 20 (MF51NR)

24 VDC Output

0.3 A 24 VDC +10%/–20%

Insulation Resistance*

20 MΩ between AC terminals and the GR See caution. terminal at 500 VDC 2,000 VAC 50/60 Hz for 1 minute between AC terminals and housing 500 VAC 50/60 Hz for 1 minute between DC terminals and housing Leakage current: 10 mA max. 1,500 Vp-p, pulse width: 100 ns to 1 µs, rise time: 1 ns

Dielectric Strength* Noise Immunity

20.4 to 26.4 VDC

None

Vibration

Mechanical durability: 10 to 35 Hz, 1 mm double amplitude (24.5 m/s2) in X, Y, and Z directions, for 2 hours each (When mounted on DIN track, 16.7 Hz, 1 mm double amplitude (4.9 m/s2) in X, Y, and Z directions, for 1 hour each) Malfunction durability: 2 to 55 Hz, 19.6 m/s2, in X, Y, and Z directions, for 20 minutes each (When mounted on DIN track, 2 to 55 Hz, 2.94 m/s2, in X, Y, and Z directions, for 20 minutes each)

Shock

98 m/s2 in X, Y, and Z directions, 3 times each

Ambient Temperature

Operating: 0° to 55°C (0° to 45°C for Programming Console) Storage: –20° to 65°C

Humidity

35% to 85% (without condensation)

Atmosphere

Must be free of the following: • Corrosive gases • Abrupt temperature changes • Direct sunlight • Dust, salt, or metal filings • Water, oil, or chemicals

Grounding

Less than 100 Ω

Enclosure Rating

Mounted in a panel

Weight

6 kg max.

! Caution

*Internal components might be damaged if insulation resistance or dielectric strength tests for the AC power supply are repeated many times with the LG and GR terminals connected. Do not conduct a dielectric strength test on the C200H-CPU23-E, PS211, RT002-P, or RT202 Units. The power supply input line and internal circuit of the 24 VDC Power Supply are not isolated from each other; do not conduct insulation resistance or dielectric strength tests. If an insulation resistance test or dielectric strength test over 50 VDC is conducted, the Power Supply will be damaged.

83