Page 1 of SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide

Manual · Omron

SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide

Manual186 pagesPDF 1.6 MB

Installation guide for OMRON C200H PLCs with CPU21-E/23-E/31-E, with specifications for I/O units such as the C200H-OD212 and OD218.

Download the PDF1.6 MB

Covers · 2 models

The models it covers

Summary

What is in it

OMRON's installation guide for C200H C-series Programmable Controllers using the C200H-CPU21-E, CPU23-E or CPU31-E. It describes every unit of the system, how to assemble and mount it, I/O word allocation and remote I/O, the installation environment, power and safety considerations, and replacing fuses, relays and batteries. Appendices list standard models and give unit specifications, including the C200H-OD212 16-point and C200H-OD218 32-point transistor output units.

Its parts

  1. Precautions
  2. Section 1 Introduction
  3. Section 2 Unit Description
  4. Section 3 Assembly Instructions
  5. Section 4 System Connections
  6. Section 5 Installation Environment
  7. Section 6 Power Considerations
  8. Section 7 Safety Considerations
  9. Section 8 Inspection and Maintenance
  10. Appendix A Standard Models
  11. Appendix B Specifications

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

An installation guide for SYSMAC C200H programmable controllers built on the C200H-CPU21-E, C200H-CPU23-E and C200H-CPU31-E CPU Units. It covers the whole system: mounting units, I/O word allocation, wiring, the installation environment, and replacing fuses, relays and batteries. Its appendix lists the standard models and gives specifications for each I/O unit, among them the C200H-OD212 and C200H-OD218 transistor output units.

Read for this summary: pages 1 to 2, 6, 19 to 20, 29, 37, 41, 45, 51, 75, 78 to 82, 113 to 114 and 129 to 130 of 186.

C200H-OD212 outputs
C200H-OD212: transistor output unit, 16 points on one common, 0.3 A at 24 VDC per point (4.8 A per unit) p. 113
C200H-OD218 outputs
C200H-OD218: transistor output unit, 32 points on one common, 16 mA at 4.5 VDC to 100 mA at 26.4 VDC p. 129
C200H-OD212 backplane
C200H-OD212: mounts only on a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2 or C200H-BC101-V1/V2 backplane p. 45, 81
C200H-OD218 CPUs
C200H-OD218: a Group-2 High-density I/O Unit; mounts only with a C200H-CPU21-E/23-E/31-E or on an Expansion I/O Rack, never on a Slave Rack p. 29, 41
C200H-OD212 power
C200H-OD212: 180 mA at 5 VDC internal; external 24 VDC supply of 35 mA min. p. 113
C200H-OD218 power
C200H-OD218: 180 mA at 5 VDC internal; external 5 to 24 VDC supply of 110 mA min. (3.4 mA per ON point) p. 129
C200H-OD212 fuse
C200H-OD212: 8 A 125 V fuse (5.2 dia. x 20), UL-TSC-8A-N1 (Nagasawa); no blown-fuse detector p. 113
C200H-OD218 fuse
C200H-OD218: 3.5 A fuse, not user-replaceable p. 129
C200H-OD212 response
C200H-OD212: ON 0.2 ms max., OFF 0.3 ms max.; leakage 0.1 mA max.; residual voltage 1.4 V max. p. 113
C200H-OD218 response
C200H-OD218: ON 0.1 ms max., OFF 0.4 ms max.; leakage 0.1 mA max.; residual voltage 0.8 V max. p. 129
C200H-OD212 size
C200H-OD212: B-shape unit, 350 g max. p. 113
C200H-OD218 I/O words
C200H-OD218: C-shape units take 2 words in IR 030 to IR 049, starting at IR 030 + 2 x the I/O number switch setting p. 29, 129

What this manual walks you through

  • Mounting I/O Units on the Backplane next to the CPU Unit p. 37
  • Fitting a Memory Unit into the CPU Unit p. 41
  • Setting the I/O number of a Group-2 High-density I/O Unit p. 29
  • Working out I/O word allocation for each rack p. 45
  • Checking the current each unit draws from the 5-V supply p. 51
  • Replacing output unit fuses p. 75
  • Replacing the Battery Set in a RAM Unit p. 78, 79
  • Model numbers of backplanes, CPU Units, Memory Units, power supplies and I/O cables p. 80
  • Wiring the C200H-OD212 terminals p. 113

Good to know

  • C200H-OD212: 24 VDC must be supplied to terminal B9, or current leaks through the load while the output is OFF. p. 113
  • Mounted on any backplane other than the V1/V2 models named for it, the C200H-OD212 will not operate properly. p. 37
  • A changed I/O number is recognized only after the PC is turned off, and no two units may share an I/O word. p. 29
  • Replace the battery within one week of the BATT FAIL message, and finish the swap within five minutes so data is kept. p. 78
  • The manual shows two circuit versions of the C200H-OD218: units made on or before January 28th, 2000, and on or after January 31st, 2000. p. 130

Questions this manual answers

Which backplane does the C200H-OD212 need?

It must be mounted on a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2 or C200H-BC101-V1/V2 backplane. p. 45, 81

What is the output rating of the C200H-OD212?

16 transistor outputs on one common, each switching 0.3 A at 24 VDC, with 4.8 A per unit. p. 113

Which CPU Units work with the C200H-OD218?

As a Group-2 High-density I/O Unit it mounts only with a C200H-CPU21-E, CPU23-E or CPU31-E or on an Expansion I/O Rack, not on a Slave Rack. p. 29, 41

Can I replace the fuse in a C200H-OD218?

No. Its 3.5 A fuse is not user-replaceable. p. 129

What fuse does the C200H-OD212 take?

An 8 A 125 V fuse, 5.2 dia. x 20, listed as UL-TSC-8A-N1 (Nagasawa). The unit has no blown-fuse detector. p. 113

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Front1
  2. C200H Programmable Controllers Installation Guide (For CPU21-E/23-E/31-E)2
  3. Notice:3
  4. About this Manual:6
  5. PRECAUTIONS7
    1. 1 Intended Audience8
    2. 2 General Precautions8
    3. 3 Safety Precautions8
    4. 4 Operating Environment Precautions9
    5. 5 Application Precautions9
  6. SECTION 1 Introduction11
    1. 1-1 What is a Control System?12
    2. 1-2 The Role of the PC14
    3. 1-3 How Does a PC Work?16
  7. SECTION 2 Unit Description18
    1. 2-1 CPU Rack19
    2. 2-2 CPU Units20
    3. 2-3 Expansion I/O Rack25
    4. 2-4 Power Supplies26
    5. 2-5 I/O Units27
    6. 2-6 Memory Units32
  8. SECTION 3 Assembly Instructions35
    1. 3-1 Mounting the Units36
    2. 3-2 Memory Units38
    3. 3-3 System Configurations41
  9. SECTION 4 System Connections43
    1. 4-1 I/O Word Allocation44
    2. 4-2 Remote I/O48
    3. 4-3 Maximum Current and Power Supplied49
    4. 4-4 I/O Connections55
  10. SECTION 5 Installation Environment60
    1. 5-1 Installation Environment61
    2. 5-2 Mounting Requirements62
    3. 5-3 Duct Work64
    4. 5-4 Preventing Noise65
  11. SECTION 6 Power Considerations66
    1. 6-1 Grounding67
    2. 6-2 Insulation67
    3. 6-3 Emergency Stop67
18 more lines, from page 68 on
  1. 6-4 Wiring68
  2. SECTION 7 Safety Considerations70
    1. 7-1 Interlock Circuits71
    2. 7-2 Power Supply Output71
    3. 7-3 Input Circuits71
    4. 7-4 Output Circuits72
    5. 7-5 Electrical Noise73
  3. SECTION 8 Inspection and Maintenance74
    1. 8-1 CPU Unit and Power Supply Fuses75
    2. 8-2 Output Unit Fuses75
    3. 8-3 Output Unit Relays76
    4. 8-4 Batteries78
  4. Appendix80
    1. Appendix A Standard Models80
    2. Appendix B Specifications89
  5. Glossary178
  6. Index183
  7. Revision History186

From the PDF’s own bookmarks.

The whole text · 25 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Pages 4 to 64-6
  3. PRECAUTIONS7-10
  4. SECTION 1 Introduction11-17
  5. SECTION 2 Unit Description, pages 18 to 2618-26
  6. SECTION 2 Unit Description, pages 27 to 3427-34
  7. SECTION 3 Assembly Instructions35-42
  8. SECTION 4 System Connections, pages 43 to 5143-51
  9. SECTION 4 System Connections, pages 52 to 5952-59
  10. SECTION 5 Installation Environment60-65
  11. SECTION 6 Power Considerations66-69
  12. SECTION 7 Safety Considerations70-73
  13. SECTION 8 Inspection and Maintenance74-79
  14. Appendix, pages 80 to 8980-89
  15. Appendix, pages 90 to 9990-99
  16. Appendix, pages 100 to 109100-109
  17. Appendix, pages 110 to 119110-119
  18. Appendix, pages 120 to 129120-129
  19. Appendix, pages 130 to 139130-139
  20. Appendix, pages 140 to 149140-149
  21. Appendix, pages 150 to 159150-159
  22. Appendix, pages 160 to 169160-169
  23. Appendix, pages 170 to 177170-177
  24. Glossary178-182
  25. Pages 183 to 186183-186

The file

Revision and size

Part no.W218-E1-6
RevisionRevised April 2000
PublisherOMRON
Pages186
PDF1.6 MB
TextText from the PDF itself; page 2 is a scan, read by OCR, which may hold reading errors.
W218-E1-6

The first pages · 3 of 186

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 186
Page 2
Page 2of 186
Page 3
Page 3of 186