SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: Appendix, pages 120 to 129

Pages 120 to 129 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide

The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OD212 and Omron C200H-OD218

Page 120

Appendix B

Specifications

Transistor Output Unit C200H-OD21A (Load Circuit Protection Provided) Max. switching capacity

24 VDC +10%/–15%, 1.0 A (4 A/Unit) surge current 1.6 A (sourcing type) PNP output

No. of Circuits

1 (16 points/common)

Min. switching capacity Leakage Current

None

160 mA, 5 VDC max.

Residual Voltage

0.8 V max.

Internal Current Consumption Load Short-circuit Protection Power for External Supply

ON Response Time

0.1 ms max.

Alarm Output (see note)

No. of outputs: 1 (2 kΩ internal resistor) Connectable Units: Only the following DC Input Units and alarm output LED indicators can be connected: C200H-ID001, ID211, ID212, IM211 (DC), IM212 (DC), ID215, ID501, MD115, MD215, MD501

Weight Dimensions

400 g max. B-shape

0.1 mA max.

OFF Response Time 0.3 ms max.

Detection current: 1.2 A min (1.6 A typical) 35 mA 24 VDC +10%/–15% min.

Internal Circuit

Output LED indicator

Short-circuit protection circuit

Circuit Configuration to 0V 2 kΩ

Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM output becomes active (low level). The problem can be detected externally by connecting a DC Input Unit to the ALARM output or by connecting an alarm output indicator. It’s not possible to connect both the Input Unit and the indicator at the same time.

114

Page 121

Appendix B

Specifications Terminal Connections +24 VDC

24 VDC

Note When the ALARM output turns ON, remove the cause of the high current and then shut off the external power supply for approx. 1 second. After confirming that the cause has been removed, turn ON the power supply again to reset the output. As shown in the diagram, it is recommended that a relay or switch that turns ON or OFF only the external power supply be connected right before the B9 (+V). Check that this relay or switch has a contact capacity higher than the external power supply current consumption (35 mA + load current min.).

115

Page 122

Appendix B

Specifications

Group-2 High-density I/O Units In the following diagrams, “m” is the first word allocated to the Unit in PC memory.

DC Input Unit C200H-ID111 (64 Points) Rated Input Voltage

12 VDC

Operating Input Voltage

10.2 to 13.2 VDC

Input Impedance

2.7 kW

Input Current

4.1 mA (at 12 VDC)

ON Voltage

8.0 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time

1.0 ms max.

OFF Response Time

1.0 ms max.

No. of Circuits

2 (32 points/common)

Internal Current Consumption

120 mA 5 VDC max.

Weight

250 g max.

Dimensions

D-shape

Circuit Configuration COM 1000 pF Internal Circuit

IN00 A

IN07 COM IN08

820 W 2.7 kW CN1

IN15 COM IN00

CN1

B

CN2

IN07 COM IN08

1000 pF

IN07 COM IN08

820 W 2.7 kW

IN15 COM IN00

CN2

B

IN07 COM IN08 IN15

116

Indicator switch circuit

Input indicator

IN15 COM IN00 A

SW

Internal Circuit

Page 123

Appendix B

Specifications Terminal Connections

CN1 I/O word “m+1” A

NC

20

20

NC

NC

19

19

NC

15

+

0 1 2

COM

18

18

17

17

15

4

16

16

13

15

15

13

12 VDC

14

12

+

13

11

12

14 13

3

12 VDC

14

+

5 6 7 COM

10

12

12

10

9

11

11

9

8

10

10

8

9

9

9

8 COM

7

+

I/O word “m+2”

14

11

12 VDC

I/O word “m” B

COM

12 VDC

CN2

8

COM

10

8

7

11

12 VDC

12

6

7

7

6

5

6

6

5

12 VDC

5

5

4

+

4

3

15 COM

4 3

4

2

3

3

2

1

2

2

1

1

0

0

1

+

I/O word “m+3” A

B

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

12

12

13

13

0 1 2 3

5

7 COM

8 9 10 11

12 VDC

12

14

15

15

16

16

17

17

18

18

NC

19

19

NC

NC

20

20

NC

14

+

6

14

13

12 VDC

4

13

+

14 15 COM

Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in each connector. Connect power supply wiring to every COM terminal, even though the COM terminals in each connector are connected internally.

DC Input Unit C200H-ID216 (32 Points) Rated Input Voltage

24 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA (at 24 VDC)

ON Voltage

14.4 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

1.0 ms max.

OFF Response Time

1.0 ms max.

No. of Circuits

1 (32 points/common)

Internal Current Consumption

All 32 points cannot be turned ON simultaneously at high temperatures. Refer to the graph below. 100 mA 5 VDC max.

Weight

180 g max.

Dimensions

C-shape

117

Page 124

Appendix B

Specifications Circuit Configuration and Simultaneously Usable Points

32 30

COM

Input Voltage: 26.4 VDC

1000 pF IN00 IN07 COM IN08

25

680 Ω

Simultaneously Usable Points

A

5.6 kΩ Input indicator

IN15

Internal circuit COM 1000 pF IN00 B

IN07 COM IN08

680 Ω

20 15 10 5

5.6 kΩ Input indicator

0

IN15

0

10

20

30

40

50 55 60

Ambient Temperature (°C)

Terminal Connections I/O word “m” 0 1 2 3

24 VDC

4

+

5 6 7 COM

8 9 10 11

24 VDC

12

+

I/O word “m+1” A

B

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

12

12

13

13

0 1 2 3

5

7 COM

8 9 10 11

14 15

16

16

17

17

18

18

NC

19

19

NC

NC

20

20

NC

15 COM

24 VDC

12

15

14

+

6

14

13

24 VDC

4

13

+

14 15 COM

Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals. Connect power supply wiring to every COM terminal, even though the COM terminals are connected internally.

118

Page 125

Appendix B

Specifications

DC Input Unit C200H-ID217 (64 Points) Rated Input Voltage

24 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA (at 24 VDC)

ON Voltage

14.4 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

1.0 ms max.

OFF Response Time

1.0 ms max.

No. of Circuits

2 (32 points/common)

Internal Current Consumption

All 64 points cannot be turned ON simultaneously at high temperatures. Refer to the graph below. 120 mA 5 VDC max.

Weight

250 g max.

Dimensions

D-shape

Circuit Configuration and Simultaneously Usable Points COM 1000 pF Internal circuit

IN00 IN07 COM IN08

680 Ω

B

CN1

IN07 COM IN08

1000 pF 680 Ω 5.6 kΩ

IN15 COM IN00

CN2

Indicator switch circuit

Input indicator

IN07 COM IN08

Input Voltage: 26.4 VDC

SW

CN2

IN15 COM IN00 A

64 60

5.6 kΩ

IN15 COM IN00

CN1

Input Voltage: 24.0 VDC

Internal circuit

Simultaneously Usable Points

A

50 40 30 20 10 0 0

B

IN07 COM IN08

10

20 30 40 50 55 60 Ambient Temperature (°C)

IN15

119

Page 126

Appendix B

Specifications Terminal Connections

CN1 I/O word “m+1” NC NC COM

15 24 VDC

+

A

20

20

19

19

18

18

17

I/O word “m+2” 0

NC

1

NC COM

2

17

15

3

24 VDC

4

16

16

14

13

15

15

13

24 VDC

14

14

12

+

13

11

12

13

11

11

12

12

13

13

14

14

15

15

16

16

17

17

18

18

NC

19

19

NC

NC

20

20

NC

COM

10 11

7

7

6

5

6

6

5

24 VDC

5

5

4

+

4

12

+

13 14

3

4

4

3

15

2

3

3

2

COM

1

2

2

1

1

0

0

1

24 VDC

4

10

8

6

3

10

9

24 VDC

4

9

8

7

4

2

9

9

8

3

8

11

8

3

1

8

COM

7

2

7

7

11

9

2

0

7

6

9

9

1

6

10

COM

1

5

12

10

B

6

5

12

10

I/O word “m+3” A

5

+

10

8

+

I/O word “m” B

14

11

24 VDC

CN2

5

+

6 7 COM

8 9 10 11

24 VDC

12 13

+

14 15 COM

Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in each connector. Connect power supply wiring to every COM terminal, even though the COM terminals in each connector are connected internally.

C200H-ID218 DC Input Unit (32 Points) Rated Input Voltage

24 VDC +10%/–15%

Input Impedance

3.9 kΩ

Input Current

6 mA (at 24 VDC)

ON Voltage/ON Current

15.4 VDC min./3.5 mA min.

OFF Voltage/OFF Current

5.0 VDC max./1 mA max.

ON Response Time

1.0 ms max.

OFF Response Time

1.0 ms max.

No. of Circuits

32 (32 points/common) Note The number of points that can be ON simultaneously is limited according to the ambient temperature. Refer to the following diagram for details.

120

Internal Current Consumption

100 mA 5 VDC max.

Weight

180 g max.

Page 127

Appendix B

Specifications Circuit Configuration

Ambient Temperature for Simultaneously ON Points 0.01 µF

Input voltage: 24.0 VDC

Internal circuit

470 Ω 3.9 kΩ to Input LED indicator 0.01 µF to 470 Ω

Simultaneously ON points to

Input voltage: 26.4 VDC

3.9 kΩ to Input LED indicator Ambient temperature

Terminal Connections m words m + 1 words

24 VDC

24 VDC

24 VDC

24 VDC

Note 1. The polarity of the input power supply can be either positive or negative. The polarity of all commons, however, must be the same. 2. COM terminals must all be wired even though they are connected internally.

121

Page 128

Appendix B

Specifications

C200H-ID219 DC Input Unit (64 Points) Rated Input Voltage

24 VDC +10%/–15%

Input Impedance

3.9 kΩ

Input Current

6 mA (at 24 VDC)

ON Voltage/ON Current

15.4 VDC min./3.5 mA min.

OFF Voltage/OFF Current

5.0 VDC max./1 mA max.

ON Response Time

1.0 ms max.

OFF Response Time

1.0 ms max.

No. of Circuits

64 (32 points/common) Note The number of points that can be ON simultaneously is limited according to the ambient temperature. Refer to the following diagram for details.

Internal Current Consumption

120 mA 5 VDC max.

Weight

250 g max.

470 Ω 3.9 kΩ to to

Input LED indicator 0.01 µF to 470 Ω to

3.9 kΩ

Internal circuit to

Input LED indicator Ambient Temperature for Simultaneously ON Points Input voltage: 20.4 VDC

Simultaneously ON points

0.01 µF to

Internal circuit

Circuit Configuration

Input voltage: 24.0 VDC

Input voltage: 26.4 VDC to to

Ambient temperature

122

Page 129

Appendix B

Specifications Terminal Connections (m + 1) words

(m + 1) words

(m + 2) words

(m + 3) words

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

24 VDC

Note 1. The polarity of the input power supply can be either positive or negative. The polarity of all commons for CN1 and CN2, however, must be the same. 2. COM terminals for CN1 and CN2 must all be wired even though they are connected internally.

Transistor Output Unit C200H-OD218 (32 Points) Max. Switching Capacity

16 mA 4.5 VDC to 100 mA 26.4 VDC (see below)

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

0.8 V max.

ON Response Time

0.1 ms max.

OFF Response Time

0.4 ms max.

No. of Circuits

1 (32 points/common)

Internal Current Consumption

180 mA 5 VDC max.

Fuse Rating

3.5 A (The fuse is not user-replacable.)

Power for External Supply Weight

110 mA 5 to 24 VDC±10% min. (3.4 mA × number of ON pts) 180 g max.

Dimensions

C-shape

123