For the Omron C200H-OD212 and Omron C200H-OD218

Page 130

Appendix B

Specifications Circuit Configuration and Maximum Switching Capacity Units manufactured on or before January 28th, 2000 (manufacturing numbers 2810 or earlier*) 4.5 to 26.4 VDC OUT00 OUT07 COM 4.5 to 26.4 VDC

A

100

OUT08 OUT15 Output indicator

COM 4.5 to 26.4 VDC Fuse (3.5 A)

OUT00 OUT07 COM 4.5 to 26.4 VDC

F indicator Fuse blowout detection circuit

B

OUT08 OUT15 COM

Max. Switching Capacity (mA/pt)

Internal Circuit

Output indicator

50

16 0 0

4.5

10 20.4 26.4 Power Supply Voltage (V)

Units manufactured on or after January 31st, 2000 (manufacturing numbers 3110 or later*) 4.5 to 26.4 VDC OUT00 OUT07 Internal Circuit

Output indicator

COM 4.5 to 26.4 VDC

A

OUT08 OUT15 Output indicator

COM 4.5 to 26.4 VDC Fuse (3.5 A)

F indicator

OUT00 OUT07 COM 4.5 to 26.4 VDC

Fuse blowout detection circuit

B

OUT08 OUT15 COM

*Manufacturing Numbers jjY9 Year: Last digit of calendar year; e.g., 1999→9, 2000→0 Month: 1 to 9 (January to September), X (October), Y (November), Z (December) Day: 01 to 31

124

Page 131

Appendix B

Specifications Terminal Connections I/O word “m” L L L L

+

L L L L

I/O word “m+1” 0 1 2 3 4 5 6 7

COM

L L L L

+

L L L L COM

8 9 10 11 12 13 14 15

A

B

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

12

12

13

13

14

14

15

15

16

16

17

17

18

18

19

19

20

20

0

L

1

L

2

L

3

4.5 to 26.4 VDC

L

4

L

5

+

L

6

L

7

L COM

8

L

9

L

10

L

11

L

12

L

13

+

L

14

L

15

L COM

Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. When the fuse blows, the F indicator lights and the error flag in AR 02 corresponding to the I/O number is turned ON. I/O numbers 0 to 9 correspond to AR 0205 to AR 0214. 3. The interruption of power from the external power supply is treated the same as a fuse blowout. 4. Connect power supply wiring to every COM terminal, even though the COM terminals are connected internally. 5. When wiring output circuits, be sure to use the correct polarity for the external power supplies. Wiring with incorrect polarity may result in erroneous operation of the load.

Transistor Output Unit C200H-OD219 (64 Points) Max. Switching Capacity

16 mA 4.5 VDC to 100 mA 26.4 VDC (see below)

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

0.8 V max.

ON Response Time

0.1 ms max.

OFF Response Time

0.4 ms max.

No. of Circuits

2 (32 points/common)

Internal Current Consumption

270 mA 5 VDC max.

Fuses

Weight

Two 3.5 A fuses (1 fuse/common) The fuses are not user-replacable. 220 mA 5 to 24 VDC±10% min. (3.4 mA × number of ON pts) 250 g max.

Dimensions

D-shape

Power for External Supply

125

Page 132

Appendix B

Specifications Circuit Configuration Units manufactured on or before January 28th, 2000 (manufacturing numbers 2810 or earlier*) 4.5 to 26.4 VDC OUT00 Internal Circuit

OUT07 COM Fuse

CN1

4.5 to 26.4 VDC OUT08

Indicator switch/ fuse blowout detection circuit

SW Output indicator

OUT15 COM

CN1 CN2

F indicator 4.5 to 26.4 VDC OUT00

Internal Circuit

OUT07 COM Fuse

CN2

4.5 to 26.4 VDC OUT08 OUT15 COM

Units manufactured on or after January 31st, 2000 (manufacturing numbers 3110 or later*) 4.5 to 26.4 VDC OUT00 Internal Circuit

OUT07 COM Fuse

CN1

4.5 to 26.4 VDC OUT08

Indicator switch/ fuse blowout detection circuit

SW Output indicator

OUT15 COM

CN1 CN2

F indicator 4.5 to 26.4 VDC OUT00

Internal Circuit

OUT07 COM Fuse

CN2

4.5 to 26.4 VDC OUT08 OUT15 COM

*Manufacturing Numbers jjY9 Year: Last digit of calendar year; e.g., 1999→9, 2000→0 Month: 1 to 9 (January to September), X (October), Y (November), Z (December) Day: 01 to 31

126

Page 133

Appendix B

Specifications

Max. Switching Capacity (A/unit)

Max. Switching Capacity (mA/pt)

Maximum Switching Capacity

100

50

16 0 0

4.5 10 20.4 26.4 Power Supply Voltage (V)

6.4 6.0 5.0 4.0 3.0 2.0 1.0 0 0

10 20 30 40 505560 Ambient Temperature (°C)

Terminal Connections CN1 I/O word “m+1”

COM L L L

+

L L L L L

15 14 13 12 11

L L

+

L L L L L

I/O word “m” B

A

20

20

19

19

18

18

17

17

16

16

15

15

14

14

COM

15 14 13 12 11

13

13

10

9

12

12

9

11

11

10

10

8

7 6 5 4 3 2 1 0

9

9

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

I/O word “m+2” L

10

COM L

CN2

8

L

L

L

L

L

+

L L

+

L L L

L

L

L

5 4 3 2 1 0

2 3 4 5 6 7

L

COM

6

1

COM

L

L

7

0

L L

L L

L

+

L L L L L L

+

L L L L COM

8 9 10 11 12 13 14 15

I/O word “m+3” A

B

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9

10

10

11

11

12

12

13

13

14

14

15

15

16

16

17

17

18

18

19

19

20

20

0 1 2 3 4 5 6 7

L L L L L

+

4.5 to 26.4 VDC

L L L COM

8 9 10 11 12 13 14 15

L L L L L

+

L L L COM

Note 1. I/O word “m” is determined by the I/O number setting (m = IR 030 + 2 × I/O number). 2. When either fuse blows, the F indicator lights and the error flag in AR 02 corresponding to the I/O number is turned ON. I/O numbers 0 to 9 correspond to AR 0205 to AR 0214. 3. The interruption of power from the external power supply is treated the same as a fuse blowout. 4. Connect power supply wiring to every COM terminal, even though the COM terminals in each connector are connected internally. 5. When wiring output circuits, be sure to use the correct polarity for the external power supplies. Wiring with incorrect polarity may result in erroneous operation of the load.

127

Page 134

Appendix B

Specifications

Transistor Output Unit C200H-OD21B (32 Points) (Load Short-circuit Protection Provided) Max. Switching Current

0.5 A 24 VDC +10%/–15% (5 A/Unit)

Min. Switching Current

None

Leakage Current

0.1 mA max.

Residual Voltage

0.8 V max.

ON Response Time

0.1 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

32 (32 points/common)

Internal Current Consumption

180 mA 5 VDC max.

Fuses

Weight

One 7 A fuse (1 fuse/common) The fuses are not user-replacable. 160 mA 24 VDC +10%/–15% min. (5 mA × number of ON pts) 180 g max.

Alarm Indicator

Lamp F lights (unless fuse is broken).

Load Short-circuit Prevention (see note 1) Dimensions

Detection current: 0.7 to 2.5 A Automatic restart after error clearance. C-shape

Power for External Supply

Note When the short-circuit/overload protection is activated for a contact point, the output for that point is turned OFF. At the same time, lamp “F” lights up, and the corresponding Flag in the Basic I/O Unit Information Area (AR0205 to AR0214) will turn ON. After the cause of the error has been removed, the alarm will be cleared automatically when the internal temperature of the element drops.

to 0V

Output LED indicator to Alarm LED indicator

0V

Short-circuit protection circuit

Internal circuit

Short-circuit protection circuit

Circuit Configuration to 0V

Output LED indicator to 0V

128

Page 135

Appendix B

Specifications Terminal Connections I/O word “m”

I/O word “m+1”

24 VDC

24 VDC

24 VDC

24 VDC

129

Page 136

Appendix B

Specifications

High-density I/O Units (Special I/O Units) TTL Input Unit C200H-ID501 (32 Points) Rated Input Voltage

5 VDC

Operating Input Voltage

4.5 to 5.5 VDC

Input Impedance

1.1 kΩ

Input Current

3.5 mA (at 5 VDC)

ON Voltage

3.0 VDC min.

OFF Voltage

1.0 VDC max.

ON Response Time

2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)

OFF Response Time

2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)

No. of Circuits

4 (8 points/common)

High-speed Inputs Internal Current Consumption

8 points (connector 2 terminals 8 to 15, when set) Pulse width: 1 ms/4 ms min. (switchable) 130 mA 5 VDC max.

Weight

300 g max.

Dimensions

130×34.5×100.5 (H×W×D, in millimeters)

Circuit Configuration COM0

CN1

IN00

2.4 kΩ

IN07 COM1 IN08

1.1 kΩ

IN15 Internal circuit COM2

CN2

IN00

2.4 kΩ

IN07 COM3 IN08

1.1 kΩ

IN15

130

Page 137

Appendix B

Specifications Terminal Connections CN1

CN2

I/O word “n”

I/O word “n+1”

NC

+ +

A 12

NC

0

NC

11

11

NC

1

NC

10

10

NC

2

COM1

5 VDC

B 12

9

9

COM0

15

8

8

7

14

7

7

6 5 VDC

+

13

6

6

5

12

5

5

4

11

4

4

3

10

3

3

2

9

2

2

1

8

1

1

0

5 VDC

3

+

4 5

+

6 7

+

COM2 NC

A

B

1

1

2

2

3

3

4

4

5

5

6

6

8 9 10 11

5 VDC

12

+

13

+

14

7

7

8

8

9

9

10

10

NC

15 COM3

NC

11

11

NC

NC

12

12

NC

Note 1. I/O word “n” is determined by the unit number setting (n = IR 100 + 10 × unit number). 2. When pin 2 of the Unit’s DIP switch is ON, input points 08 to 15 in connector 2 are high-speed inputs.

DC Input Unit C200H-ID215 (32 Points) Rated Input Voltage

24 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Input Impedance

5.6 kΩ

Input Current

4.1 mA (at 24 VDC)

ON Voltage

14.4 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)

OFF Response Time

2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)

No. of Circuits

4 (8 points/common)

High-speed Inputs Internal Current Consumption

8 points (connector 2 terminals 8 to 15, when set) Pulse width: 1 ms/4 ms min. (switchable) 130 mA 5 VDC max.

Weight

300 g max.

Dimensions

130×34.5×100.5 (H×W×D, in millimeters)

131

Page 138

Appendix B

Specifications Circuit Configuration COM0 1000 pF IN00 CN1

IN07 COM1 IN08

620 Ω 5.6 kΩ

IN15 Internal circuit COM2 1000 pF IN00 CN2

IN07 COM3 IN08

620 Ω 5.6 kΩ

IN15

Terminal Connections CN1

CN2

I/O word “n”

I/O word “n+1”

NC

B 12

A 12

NC

0

NC

11

11

NC

1

NC

2

NC COM1

10

10

9

9

COM0

15

8

8

7

14

7

7

6 24 VDC

+

24 VDC

13

+

6

6

5

12

5

5

4

+

11

4

4

3

10

3

3

2

9

2

2

1

1

0

8

1

24 VDC

3

+

4

+

5 6

B

1

1

2

2

3

3

4

4

5

5

6

6

8 9 10 11

24 VDC

12

+

13

7

8

8

9

9

NC

10

10

NC

NC

11

11

NC

NC

12

12

NC

COM2

+

14

7

7

+

A

15 COM3

Note 1. I/O word “n” is determined by the unit number setting (n = IR 100 + 10 × unit number). 2. When pin 2 of the Unit’s DIP switch is ON, input points 08 to 15 in connector 2 are high-speed inputs. 3. At high temperatures, the number of inputs that can be turned ON simultaneously is limited. Refer to the graphs on page 150 for details.

132

Page 139

Appendix B

Specifications

TTL Output Unit C200H-OD501 (Used as a 32-point Output Unit) Max. Switching Capacity Min. Switching Capacity

5 VDC 35 mA (280 mA/common, 1.12 A/Unit; output resistance 4.7 kΩ) None

Leakage Current

0.1 mA max.

Residual Voltage

0.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

4 (8 points/common)

Internal Current Consumption

220 mA 5 VDC max.

Fuses

4 (1 fuse/common; fuses are not user-replacable.)

Power for External Supply

39 mA 5 VDC min. (1.2 mA × no. of outputs ON)

Weight

300 g max.

Dimensions

130×34.5×100.5 (H×W×D, in millimeters)

Circuit Configuration 5 VDC 4.7 kΩ OUT00 OUT07 CN1 COM0 Fuse 5 VDC OUT08 OUT15 COM1 5 VDC

Internal circuit 4.7 kΩ

OUT00 OUT07 CN2 COM2 Fuse 5 VDC OUT08 OUT15 COM3

133