The text of a manual · part 17 of 25
SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: Appendix, pages 110 to 119
Pages 110 to 119 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 110
Appendix B
Specifications
Contact Output Unit C200H-OC224 Max. Switching Capacity Min. Switching Capacity
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (16 A/Unit) 10 mA 5 VDC
Relay
G6B-1174-P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
8 independent contacts
Internal Current Consumption Weight
10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 300 g max.
Dimensions
B-shape
Circuit Configuration
Output indicator OUT L Internal circuit OUTc 250 VAC, 24 VDC max.
Terminal Connections c0 c1
B0 A0 A1 c2
A2 c3
24 VDC, 250 VAC max. (inductive load: 2 A, resistive load: 2 A) (16 A/Unit)
A3 c4
A4 c5
A5 c6
A6 c7
A7 NC
104
A8
B1 B2 B3 B4 B5 B6 B7
0 1 2 3 4 5 6
L L L L L L L
7
B8 NC B9 NC
L
Page 111
Appendix B
Specifications
Contact Output Unit C200H-OC225 Max. Switching Capacity Min. Switching Capacity
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC
Relay
G6B-1174P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
Weight
1 (16 points/common) 8 points max. can be ON simultaneously. 50 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 400 g max.
Dimensions
B-shape
Internal Current Consumption
Circuit Configuration OUT L Output indicator OUT L Internal circuit
COM 250 VAC, 24 VDC max.
Terminal Connections B0 0 A0 2 3 A1 B1 L 4 B2 5 A2 L 6 B3 7 A3 L 8 B4 9 A4 L 10 B5 11 A5 L 12 13 A6 B6 L 14 15 A7 B7 L B8 NC A8 COM B9 NC L
1
L L L L L L L L
24 VDC, 250 VAC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)
Note 1. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane. 2. This Unit might overheat if more than 8 output points are turned ON simultaneously.
105
Page 112
Appendix B
Specifications
Transistor Output Unit C200H-OD211 Max. Switching Capacity
0.3 A 24 VDC +10%/–15% (2 A/Unit)
Min. Switching Capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
160 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
25 mA 24 VDC +10%/–15% min.
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration OUT L +V Output indicator OUT L Internal circuit
24 VDC Fuse
COM
Fuse: GGS (Nagasawa) 5 A 125 V 5.2-dia × 20
Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output.
Terminal Connections
L L L
24 VDC (0.3 A max., 2 A/Unit)
L L L
1 3 5 7 9 11
A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM (OV)
A8
B0
0
L
B1
2
L
B2
4
L
B3
6
B4
8
B5 10
L L L
B6
NC
B7
NC
B8
NC + 24 VDC
B9
Note Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF.
106
Page 113
Appendix B
Specifications
Transistor Output Unit C200H-OD212 Max. Switching Capacity
0.3 A 24 VDC +10%/–15% (4.8 A/Unit)
Min. Switching Capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (16 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
8 A 125 V (5.2-dia.x20)
Power for External Supply
35 mA 24 VDC +10%/–15% min.
Weight
350 g max.
Dimensions
B-shape
Circuit Configuration OUT L +V Output indicator OUT L Internal Circuit
24 VDC Fuse
COM
Fuse: UL-TSC-8A-N1 (Nagasawa) 8 A 125 V 5.2-dia 20
Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output.
Terminal Connections
L L L
24 VDC (0.3 A max )
L
1 3 5 7 9
A0 A1 A2 A3 A4
B0
0
L
B1
2
L
B2
4
L
B3
6
B4
8
L L
B5 10 L 11 A5 L B6 12 L 13 A6 L B7 14 L 15 A7 L B8 NC A8 + 24 VDC COM (OV) B9 L
Note 1. Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF. 2. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
107
Page 114
Appendix B
Specifications
Transistor Output Unit C200H-OD213 Max. Switching Capacity
2.1 A 24 VDC +10%/–15% (5.2 A/Unit) NPN output
Min. Switching Capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
8 A 125 V (5.2-dia.x20)
Power for External Supply
30 mA 24 VDC +10%/–15% min.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration OUT L +V Output indicator
Internal Circuit
OUT L 24 VDC Fuse Fuse blowout detection circuit
COM
Fuse: UL-TSC-8A-N1 (Nagasawa) 8 A 125 V 5.2-dia 20
F indicator
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.
Terminal Connections 0
L
1
L
2
L
3
L
24 VDC (2.1 A max., 5.2 A/Unit)
L
4 5
L L
6 7
L
A0 A1 A2 A3 A4 A5 A6 A7
COM (OV)
A8
24 VDC
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
108
Page 115
Appendix B
Specifications
Transistor Output Unit C200H-OD214 (Load Short-circuit Protection Provided)
Min. Switching Capacity
24 VDC +10%/–15% 0.8 A (2.4 A/Unit) surge current 2 A (source type) PNP output None
Leakage Current
1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
1 ms max.
OFF Response Time
1 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
Short-circuit protection
Power for External Supply
150 mA 24 VDC +10%/
Weight
250 g max.
Dimensions
A-shape
Max. Switching Capacity
Overcurrent protection Thermal protection
–15% min.
Circuit Configuration OUT L
Output indicator Source Driver Internal circuit Reset
+V OUT L
+
24 VDC button COM Alarm output indicator
Terminal Connections 0
L
1
L
2
L L
24 VDC (2.1 A max., 5.2 A/Unit)
L L L L
3 4 5 6 7
A0 A1 A2 A3 A4 A5 A6 A7
COM (OV)
A8
24 VDC
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
109
Page 116
Appendix B
Specifications C200H-OD214 Short-Circuit Protection
The C200H-OD214 Output Unit is equipped with two types of short-circuit protection: overcurrent protection and thermal protection. Any short-circuit must be eliminated immediately in order to avoid damage to the Unit. Overcurrent Protection When the output current reaches 2 A, the alarm output turns ON, and the alarm indicator lights. Make sure the surge current of the load does not exceed 2 A, or the alarm may be activated. Thermal Protection When the junction temperature of the output transistor reaches its upper limit, the output turns OFF, the alarm output turns ON, and the alarm indicator blinks. But the output transistor is provided with a heat sink. So in some cases, when the output is short-circuited the thermal protection may not activate because the extra heat is dissipated by the heat sink. However, the alarm indicator will still light and the alarm output will still turn ON. How It Works When the short-circuit protection activates, the output displays the characteristic shown below. Output voltage
Overcurrent limit alarm output point
Output current: 2 A (minimum value)
0
Each pair of outputs share one alarm indicator and one alarm output bit as shown below (bits 12 through 15 cannot be used as IR bits) Output No.
0
1
2
3
4
5
6
7
Alarm indicator No.
0
2
4
6
Alarm Output Point No.
08
09
10
11
Both the alarm indicator and alarm output bit for the short-circuited output turn ON even if only one of the outputs is short-circuited. Both outputs should be disconnected until the short-circuit can be traced. Clearing the Alarm When the short-circuit has been eliminated, reset the Unit by pressing the reset button. The alarm indicator will go out, the alarm output will turn OFF, and the output will be reset. Output indicator
Alarm indicator Reset button (use a screwdriver or other similar object to press it).
Programming Example If there is a short-circuit in an output, we want the program to turn that output OFF. Assume that the Unit is mounted at word 000. A program to turn OFF output bits 00 and 01 is shown below. A
00008 00000
B
00008 00001
Since alarm output bit 08 covers both output bits 00 and 01, both these outputs are forced OFF as soon as output bit 08 turns ON (bits A and B can be any other bits required in the program).
110
Page 117
Appendix B
Specifications
Transistor Output Unit C200H-OD216 Max. Switching Capacity
0.3 A 5 to 24 VDC
Min. Switching Capacity
10 mA 5 VDC
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
1.5 ms max.
OFF Response Time
2 ms max.
No. of Circuits
Fuse Rating
1 (8 points/common) positive common (source type) 10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) None
Power for External Supply
N/A
Weight
250 g max.
Dimensions
A-shape
Internal Current Consumption
Circuit Configuration
OUT
L
Output indicator OUT
L
Internal circuit
5 to 24 VDC COM
Terminal Connections L L L L
5 to 24 VDC
L L L L
0 1 2 3 4 5 6 7
A0 A1 A2 A3 A4 A5 A6 A7
COM A8 NC A9
111
Page 118
Appendix B
Specifications
Transistor Output Unit C200H-OD217 Max. Switching Capacity
0.3 A 5 to 24 VDC
Min. Switching Capacity
10 mA 5 VDC
Leakage Current
0.1 mA max.
Residual Voltage
1.5 V max.
ON Response Time
1.5 ms max.
OFF Response Time
2 ms max.
No. of Circuits
Fuse Rating
1 (12 points/common) positive common (source type) 10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) None
Power for External Supply
N/A
Weight
300 g max.
Dimensions
B-shape
Internal Current Consumption
Circuit Configuration
OUT L
Output indicator OUT L
Internal circuit
5 to 24 VDC COM
Terminal Connections
L L
5 to 24 VDC
L L L L
1 3 5 7 9 11
A0 A1 A2 A3 A4 A5
NC A6 NC A7 COM A8
B0
0
B1
2
B2
4
B3
6
B4
8
B5 10 B6 NC B7 NC B8 NC B9 NC
112
L L L L L L
Page 119
Appendix B
Specifications
Transistor Output Unit C200H-OD411 Max. Switching Capacity
12 to 48 VDC 1 A (3 A/Unit)
Min. Switching Capacity
None
Leakage Current
0.1 mA max.
Residual Voltage
1.4 V max.
ON Response Time
0.2 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
30 mA 12 to 48 VDC min.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration OUT
L
V Output indicator OUT L Internal circuit
Fuse
COM 12 to 48 VDC
Fuse blowout detection circuit
Fuse: GGS (Nagasawa) 5 A 125 V 5.2-dia × 20
F indicator
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.
Terminal Connections L L L L
12 to 48 VDC (1 A max., 3 A/Unit)
L L L L
0 1 2 3 4 5 6 7
A0 A1 A2 A3 A4 A5 A6 A7
COM (OV)
A8
12 to 48 VDC
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
113