Page 110

Appendix B

Specifications

Contact Output Unit C200H-OC224 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (16 A/Unit) 10 mA 5 VDC

Relay

G6B-1174-P-FD-US (24 VDC) w/socket

Service Life of Relay

Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

10 ms max.

OFF Response Time

10 ms max.

No. of Circuits

8 independent contacts

Internal Current Consumption Weight

10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 300 g max.

Dimensions

B-shape

Circuit Configuration

Output indicator OUT L Internal circuit OUTc 250 VAC, 24 VDC max.

Terminal Connections c0 c1

B0 A0 A1 c2

A2 c3

24 VDC, 250 VAC max. (inductive load: 2 A, resistive load: 2 A) (16 A/Unit)

A3 c4

A4 c5

A5 c6

A6 c7

A7 NC

104

A8

B1 B2 B3 B4 B5 B6 B7

0 1 2 3 4 5 6

L L L L L L L

7

B8 NC B9 NC

L

Page 111

Appendix B

Specifications

Contact Output Unit C200H-OC225 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC

Relay

G6B-1174P-FD-US (24 VDC) w/socket

Service Life of Relay

Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

10 ms max.

OFF Response Time

10 ms max.

No. of Circuits

Weight

1 (16 points/common) 8 points max. can be ON simultaneously. 50 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 400 g max.

Dimensions

B-shape

Internal Current Consumption

Circuit Configuration OUT L Output indicator OUT L Internal circuit

COM 250 VAC, 24 VDC max.

Terminal Connections B0 0 A0 2 3 A1 B1 L 4 B2 5 A2 L 6 B3 7 A3 L 8 B4 9 A4 L 10 B5 11 A5 L 12 13 A6 B6 L 14 15 A7 B7 L B8 NC A8 COM B9 NC L

1

L L L L L L L L

24 VDC, 250 VAC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)

Note 1. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane. 2. This Unit might overheat if more than 8 output points are turned ON simultaneously.

105

Page 112

Appendix B

Specifications

Transistor Output Unit C200H-OD211 Max. Switching Capacity

0.3 A 24 VDC +10%/–15% (2 A/Unit)

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

1.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

1 (12 points/common)

Internal Current Consumption

160 mA 5 VDC max.

Fuse Rating

5 A 125 V (5.2-dia.x20)

Power for External Supply

25 mA 24 VDC +10%/–15% min.

Weight

300 g max.

Dimensions

B-shape

Circuit Configuration OUT L +V Output indicator OUT L Internal circuit

24 VDC Fuse

COM

Fuse: GGS (Nagasawa) 5 A 125 V 5.2-dia × 20

Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output.

Terminal Connections

L L L

24 VDC (0.3 A max., 2 A/Unit)

L L L

1 3 5 7 9 11

A0 A1 A2 A3 A4 A5

NC

A6

NC

A7

COM (OV)

A8

B0

0

L

B1

2

L

B2

4

L

B3

6

B4

8

B5 10

L L L

B6

NC

B7

NC

B8

NC + 24 VDC

B9

Note Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF.

106

Page 113

Appendix B

Specifications

Transistor Output Unit C200H-OD212 Max. Switching Capacity

0.3 A 24 VDC +10%/–15% (4.8 A/Unit)

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

1.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

1 (16 points/common)

Internal Current Consumption

180 mA 5 VDC max.

Fuse Rating

8 A 125 V (5.2-dia.x20)

Power for External Supply

35 mA 24 VDC +10%/–15% min.

Weight

350 g max.

Dimensions

B-shape

Circuit Configuration OUT L +V Output indicator OUT L Internal Circuit

24 VDC Fuse

COM

Fuse: UL-TSC-8A-N1 (Nagasawa) 8 A 125 V 5.2-dia 20

Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output.

Terminal Connections

L L L

24 VDC (0.3 A max )

L

1 3 5 7 9

A0 A1 A2 A3 A4

B0

0

L

B1

2

L

B2

4

L

B3

6

B4

8

L L

B5 10 L 11 A5 L B6 12 L 13 A6 L B7 14 L 15 A7 L B8 NC A8 + 24 VDC COM (OV) B9 L

Note 1. Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF. 2. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.

107

Page 114

Appendix B

Specifications

Transistor Output Unit C200H-OD213 Max. Switching Capacity

2.1 A 24 VDC +10%/–15% (5.2 A/Unit) NPN output

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

1.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

140 mA 5 VDC max.

Fuse Rating

8 A 125 V (5.2-dia.x20)

Power for External Supply

30 mA 24 VDC +10%/–15% min.

Weight

250 g max.

Dimensions

A-shape

Circuit Configuration OUT L +V Output indicator

Internal Circuit

OUT L 24 VDC Fuse Fuse blowout detection circuit

COM

Fuse: UL-TSC-8A-N1 (Nagasawa) 8 A 125 V 5.2-dia 20

F indicator

Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.

Terminal Connections 0

L

1

L

2

L

3

L

24 VDC (2.1 A max., 5.2 A/Unit)

L

4 5

L L

6 7

L

A0 A1 A2 A3 A4 A5 A6 A7

COM (OV)

A8

24 VDC

A9

Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.

108

Page 115

Appendix B

Specifications

Transistor Output Unit C200H-OD214 (Load Short-circuit Protection Provided)

Min. Switching Capacity

24 VDC +10%/–15% 0.8 A (2.4 A/Unit) surge current 2 A (source type) PNP output None

Leakage Current

1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

1 ms max.

OFF Response Time

1 ms max.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

140 mA 5 VDC max.

Fuse Rating

Short-circuit protection

Power for External Supply

150 mA 24 VDC +10%/

Weight

250 g max.

Dimensions

A-shape

Max. Switching Capacity

Overcurrent protection Thermal protection

–15% min.

Circuit Configuration OUT L

Output indicator Source Driver Internal circuit Reset

+V OUT L

+

24 VDC button COM Alarm output indicator

Terminal Connections 0

L

1

L

2

L L

24 VDC (2.1 A max., 5.2 A/Unit)

L L L L

3 4 5 6 7

A0 A1 A2 A3 A4 A5 A6 A7

COM (OV)

A8

24 VDC

A9

Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.

109

Page 116

Appendix B

Specifications C200H-OD214 Short-Circuit Protection

The C200H-OD214 Output Unit is equipped with two types of short-circuit protection: overcurrent protection and thermal protection. Any short-circuit must be eliminated immediately in order to avoid damage to the Unit. Overcurrent Protection When the output current reaches 2 A, the alarm output turns ON, and the alarm indicator lights. Make sure the surge current of the load does not exceed 2 A, or the alarm may be activated. Thermal Protection When the junction temperature of the output transistor reaches its upper limit, the output turns OFF, the alarm output turns ON, and the alarm indicator blinks. But the output transistor is provided with a heat sink. So in some cases, when the output is short-circuited the thermal protection may not activate because the extra heat is dissipated by the heat sink. However, the alarm indicator will still light and the alarm output will still turn ON. How It Works When the short-circuit protection activates, the output displays the characteristic shown below. Output voltage

Overcurrent limit alarm output point

Output current: 2 A (minimum value)

0

Each pair of outputs share one alarm indicator and one alarm output bit as shown below (bits 12 through 15 cannot be used as IR bits) Output No.

0

1

2

3

4

5

6

7

Alarm indicator No.

0

2

4

6

Alarm Output Point No.

08

09

10

11

Both the alarm indicator and alarm output bit for the short-circuited output turn ON even if only one of the outputs is short-circuited. Both outputs should be disconnected until the short-circuit can be traced. Clearing the Alarm When the short-circuit has been eliminated, reset the Unit by pressing the reset button. The alarm indicator will go out, the alarm output will turn OFF, and the output will be reset. Output indicator

Alarm indicator Reset button (use a screwdriver or other similar object to press it).

Programming Example If there is a short-circuit in an output, we want the program to turn that output OFF. Assume that the Unit is mounted at word 000. A program to turn OFF output bits 00 and 01 is shown below. A

00008 00000

B

00008 00001

Since alarm output bit 08 covers both output bits 00 and 01, both these outputs are forced OFF as soon as output bit 08 turns ON (bits A and B can be any other bits required in the program).

110

Page 117

Appendix B

Specifications

Transistor Output Unit C200H-OD216 Max. Switching Capacity

0.3 A 5 to 24 VDC

Min. Switching Capacity

10 mA 5 VDC

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

1.5 ms max.

OFF Response Time

2 ms max.

No. of Circuits

Fuse Rating

1 (8 points/common) positive common (source type) 10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) None

Power for External Supply

N/A

Weight

250 g max.

Dimensions

A-shape

Internal Current Consumption

Circuit Configuration

OUT

L

Output indicator OUT

L

Internal circuit

5 to 24 VDC COM

Terminal Connections L L L L

5 to 24 VDC

L L L L

0 1 2 3 4 5 6 7

A0 A1 A2 A3 A4 A5 A6 A7

COM A8 NC A9

111

Page 118

Appendix B

Specifications

Transistor Output Unit C200H-OD217 Max. Switching Capacity

0.3 A 5 to 24 VDC

Min. Switching Capacity

10 mA 5 VDC

Leakage Current

0.1 mA max.

Residual Voltage

1.5 V max.

ON Response Time

1.5 ms max.

OFF Response Time

2 ms max.

No. of Circuits

Fuse Rating

1 (12 points/common) positive common (source type) 10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) None

Power for External Supply

N/A

Weight

300 g max.

Dimensions

B-shape

Internal Current Consumption

Circuit Configuration

OUT L

Output indicator OUT L

Internal circuit

5 to 24 VDC COM

Terminal Connections

L L

5 to 24 VDC

L L L L

1 3 5 7 9 11

A0 A1 A2 A3 A4 A5

NC A6 NC A7 COM A8

B0

0

B1

2

B2

4

B3

6

B4

8

B5 10 B6 NC B7 NC B8 NC B9 NC

112

L L L L L L

Page 119

Appendix B

Specifications

Transistor Output Unit C200H-OD411 Max. Switching Capacity

12 to 48 VDC 1 A (3 A/Unit)

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

1.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

140 mA 5 VDC max.

Fuse Rating

5 A 125 V (5.2-dia.x20)

Power for External Supply

30 mA 12 to 48 VDC min.

Weight

250 g max.

Dimensions

A-shape

Circuit Configuration OUT

L

V Output indicator OUT L Internal circuit

Fuse

COM 12 to 48 VDC

Fuse blowout detection circuit

Fuse: GGS (Nagasawa) 5 A 125 V 5.2-dia × 20

F indicator

Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.

Terminal Connections L L L L

12 to 48 VDC (1 A max., 3 A/Unit)

L L L L

0 1 2 3 4 5 6 7

A0 A1 A2 A3 A4 A5 A6 A7

COM (OV)

A8

12 to 48 VDC

A9

Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.

113