The text of a manual · part 8 of 25
SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: SECTION 4 System Connections, pages 43 to 51
Pages 43 to 51 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 43
SECTION 4 System Connections In the preceding sections we have covered what all the parts of a PC are and how they should be assembled. This section provides detailed information about the types of considerations involved in making all of the PC connections. Also included in this section are considerations that should be kept in mind when using the C200H-CPU31-E as the CPU Unit. 4-1 4-2 4-3 4-4
I/O Word Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maximum Current and Power Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
36 40 41 47
35
Page 44
Section 4-1
I/O Word Allocation
4-1
I/O Word Allocation
Standard I/O Units
36
Each slot of the Backplane is assigned a fixed word in memory. This word is accessible for I/O use only in the given slot. However, Standard I/O Units are available in 5-, 8-, 12-, and 16-point models. If an I/O Unit other than a 16-point model is mounted, the unused points of that word are accessible only as “work bits” (refer to the C200H Operation Manual). The number of I/O bits available for the entire system, therefore, varies according to the model of I/O Units used, as well as the model of Backplanes used. The figure below shows the relationship between the model of I/O Unit and work bits. The shaded bits can only be used as work bits. 5-point Units
8-point Units
12-point Units
16-point Units
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Page 45
Section 4-1
I/O Word Allocation
The CPU Rack begins with word 000 at the leftmost slot. The first Expansion I/O Rack begins with word 010, and the second Expansion I/O Rack with word 020. The first word of each Rack is fixed, regardless of the model of Backplane used. As with the I/O bits unused by individual I/O Units, the bits of the I/O words unused by a Backplane can be used as work bits. The following figure shows the relationship between the model of Backplane and I/O words. The shaded bits can only be used as work bits. C200H-BC031-V1/V2 Backplane Word
000
001
002
003
004
005
006
007
008
009
00
00
00
00
00
00
00
00
00
00
15
15
15
15
15
15
15
15
15
15
Bits
C200H-BC051-V1/V2 Backplane Word
000
001
002
003
004
005
006
007
008
009
00
00
00
00
00
00
00
00
00
00
15
15
15
15
15
15
15
15
15
15
Bits
C200H-BC081-V1/V2 Backplane Word
000
001
002
003
004
005
006
007
008
009
00
00
00
00
00
00
00
00
00
00
15
15
15
15
15
15
15
15
15
15
Bits
Note The C200H-OC225, C200H-OD212, and C200H-OD21A 16-point Output Units must be mounted to a C200H-BCjj1-V1/V2 Backplane. For example, if a PC consists of three 8-slot Racks with 8-point I/O Units mounted to all I/O Unit mounting positions, the number of I/O points for the entire PC will be: 8 points x 8 slots x 3 Racks = 192 points If a PC consists of three 8-slot Racks with the I/O Unit mounting positions equally divided between 16-point Input Units and 12-point Output Units, the number of I/O points for the entire PC will be: Input points = 16 points x 4 slots x 3 Racks = 192 points Output points = 12 points x 4 slots x 3 Racks = 144 points Total I/O points = 192 + 144 = 336
37
Page 46
Section 4-1
I/O Word Allocation
The following figure shows the word allocation for a fully expanded C200H with three 8-slot Backplanes.
Allocation for Special I/O Units and Slave Racks
Wd 000
Wd 001
Wd 002
Wd 003
Wd 004
Wd 005
Wd 006
Wd 007
CPU Unit
Wd 010
Wd 011
Wd 012
Wd 013
Wd 014
Wd 015
Wd 016
Wd 017
Power Supply
Wd 020
Wd 021
Wd 022
Wd 023
Wd 024
Wd 025
Wd 026
Wd 027
Power Supply
Up to ten Special I/O Units may be mounted in any slot of the CPU Rack or Expansion I/O Racks. Up to five Slave Racks may be used, whether one or two Masters are used. IR area words are allocated to Special I/O Units and Slave Racks by the unit number on the Unit, as shown in the following tables. Special I/O Units
Slave Racks
Unit number IR address 0 100 to 109 1 110 to 119 2 120 to 129 3 130 to 139 4 140 to 149 5 150 to 159 6 160 to 169 7 170 to 179 8 180 to 189 9 190 to 199
Unit number IR address 0 050 to 059 1 060 to 069 2 070 to 079 3 080 to 089 4 090 to 099
The C500-RT001/002-(P)V1 Remote I/O Slave Rack may be used, but it requires 20 I/O words, not 10, and therefore occupies the I/O words allocated to 2 C200H Slave Racks, both the words allocated to the unit number set on the rack and the words allocated to the following unit number. When using a C200H CPU Unit, do not set the unit number on a C500 Slave Rack to 4, because there is no unit number 5. I/O words are allocated only to installed Units, from left to right, and not to slots as in the C200H system. Allocation for Optical I/O Units
I/O words between IR 200 and IR 231 are allocated to Optical I/O Units by unit number. The I/O word allocated to each Unit is IR 200+n, where n is the unit number set on the Unit.
Allocation for Remote I/O Master and Link Units
Remote Master I/O Units, SYSMAC LINK Units, SYSMAC NET Link Units, and Host Link Units do not use I/O words, and the PC Link Units use the LR area, so words allocated to the slots in which these Units are mounted are available as work words.
38
Page 47
I/O Word Allocation
Section 4-1
Allocation for Group-2 High-density I/O Units
Group-2 High-density I/O Units are allocated words between IR 030 and IR 049 according to I/O number settings made on them and do not use the words allocated to the slots in which they are mounted. For 32-point Units, each Unit is allocated two words; for 64-point Units, each Unit is allocated four words. The words allocated for each I/O number are in the following tables. Any words or part of words not used for I/O can be used as work words or bits in programming. 32-point Units
64-point Units
Words
I/O number
I/O number
Words
0
IR 30 to IR 31
0
IR 30 to IR 33
1
IR 32 to IR 33
1
IR 32 to IR 35
2
IR 34 to IR 35
2
IR 34 to IR 37
3
IR 36 to IR 37
3
IR 36 to IR 39
4
IR 38 to IR 39
4
IR 38 to IR 41
5
IR 40 to IR 41
5
IR 40 to IR 43
6
IR 42 to IR 43
6
IR 42 to IR 45
7
IR 44 to IR 45
7
IR 44 to IR 47
8
IR 46 to IR 47
8
IR 46 to IR 49
9
IR 48 to IR 49
9
Cannot be used.
When setting I/O numbers on the High-density I/O Units, be sure that the settings will not cause the same words to be allocated to more than one Unit. For example, if I/O number 0 is allocated to a 64-point Unit, I/O number 1 cannot be used for any Unit in the system. Group-2 High-density I/O Units are not considered Special I/O Units and do not affect the limit to the number of Special I/O Units allowed in the System, regardless of the number used. The words allocated to Group-2 High-density I/O Units correspond to the connectors on the Units as shown in the following table. Unit 32-point Units 64-point Units
Word First Second First Second Third Forth
Connector/row Row A Row B CN1, row A CN1, row B CN2, row A CN2, row B
Note Group-2 High-density I/O Units cannot be mounted to Slave Racks and cannot be used with the C200H-CPU01-E, C200H-CPU03-E, and C200H-CPU11-E.
39
Page 48
Section 4-2
Remote I/O Allocation for Group-2 B7A Interface Units
Group-2 B7A Interface Units are allocated words between IR 030 and IR 049 according to I/O number settings made on them and do not use the words allocated to the slots in which they are mounted. For 32-point Units, each Unit is allocated two words; for 64-point Units, each Unit is allocated four words. The words allocated for each I/O number are in the following tables. Any words or part of words not used for I/O can be used as work words or bits in programming. 32-point Units I/O number
Words
64-point Units I/O number
Words
0
IR 30 to IR 31
0
IR 30 to IR 33
1
IR 32 to IR 33
1
IR 32 to IR 35
2
IR 34 to IR 35
2
IR 34 to IR 37
3
IR 36 to IR 37
3
IR 36 to IR 39
4
IR 38 to IR 39
4
IR 38 to IR 41
5
IR 40 to IR 41
5
IR 40 to IR 43
6
IR 42 to IR 43
6
IR 42 to IR 45
7
IR 44 to IR 45
7
IR 44 to IR 47
8
IR 46 to IR 47
8
IR 46 to IR 49
9
IR 48 to IR 49
9
Cannot be used.
When setting I/O numbers on the B7A Interface Units, be sure that the settings will not cause the same words to be allocated to more than one Unit. For example, if I/O number 0 is allocated to a 64-point Unit, I/O number 1 cannot be used for any Unit in the system. Group-2 B7A Interface Units are not considered Special I/O Units and do not affect the limit to the number of Special I/O Units allowed in the System, regardless of the number used.
4-2
Remote I/O There are limits to how long the normal wiring between the PC and its Expansion I/O Racks can be. A Remote I/O Unit can extend this distance greatly, so that the PC and its Expansion I/O Racks can even be located in separate buildings. There are two types of Remote I/O Systems, optical and wired. By locating a Rack farther from the CPU Rack, a Remote I/O System eliminates the time and mess in wiring (or changing wiring) to many devices that are separated from the CPU Rack. Although all I/O points must ultimately be wired individually, the question is one of distance: Do you want to wire dozens of terminals all the way across a factory complex or do you want to run a single cable for most of the distance and then wire individual terminals locally? A PC with an Expansion I/O System is called an Expanded PC.
40
Page 49
Section 4-3
Maximum Current and Power Supplied
I/O words 100 through 199 and DM words 1000 through 1999 are allocated to Special I/O Units. There are limitations to the number and model of Special I/O Units that can be mounted to a Remote I/O Slave Rack. For example, Group-2 High-density I/O Units and B7A Interface Units cannot be mounted to a Remote I/O Slave Rack. Provided no other models of Special I/O Units are mounted to a Remote I/O Slave Rack, the maximum number of Special I/O Units that can be mounted is shown below for each model. Group
Units
Total number
A
High-speed Counter, Position Control (NC111/NC112), ASCII, Analog I/O, ID Sensor, Fuzzy Logic Unit
4 Units
B
High-density and Mixed I/O, Cam Positioner, Temperature Control, PID Control, Heat/Cool Temperature Control
8 Units
C
Temperature Sensor, Voice
6 Units
D
Position Control (NC221)
2 Units
When using a combination of A, B, C, and D Units on a Remote I/O Slave Rack, the number of each model of Unit being used must satisfy the following two formulas. 3A + B + C + 6D 12 A+B+C+D 8 In addition, when PC Link Units are used, a maximum of ten Special I/O Units and PC Link Units total can be mounted to one Expanded PC. When a High-density I/O Unit is mounted to a Remote I/O Slave Rack, the RM001-PV1 or RM201 Remote I/O Master Unit must be used.
4-3
Maximum Current and Power Supplied The power supplies, including those built in the CPU Units, are limited in the total current they can supply to I/O Units. The table below shows the maximum currents supplied by each power supply. There are three categories in the “Maximum current supplied”: 1, 2, 3...
1. The 5-V internal logic current powers I/O Cards and communications cards. 2. The 26-V relay current powers relay output cards and ID Sensor Units. 3. Finally, the external 24-VDC power supply on the CPU Unit powers external input devices. The total wattage of all three categories cannot exceed the wattage listed in the last column, “Maximum power.” You should not exceed any of the individual current ratings for the voltage supplied by any single Unit, nor should you exceed the total maximum power output.
41
Page 50
Section 4-3
Maximum Current and Power Supplied Current Supplied Name
CPU Rack
Expansion I/O Rack Slave Rack
Model number
Max. current supplied (See note 1)
Maximum
5V (internal logic current)
26 V (relay current)
24 V (No-voltage contact current)
C200H-CPU21-E
3.2 A
0.6 A
0.8 A
C200H-CPU23-E
1.6 A
0.6 A
---
C200H-CPU31-E
3.0 A
0.6 A
0.8 A
C200H-PS221 C200H-PS211 C200H-RT001-P
2.7 A
0.6 A
2.7 A
0.6 A
0.8 A --0.8 A
19 to 22 W (See note 2) 28 W 23 W 28 W
C200H-RT002-P
---
23 W
C200H-RT201
0.8 A
28 W
C200H-RT202
---
23 W
Note power
20 to 23 W (See note 2) 18 W
1. The figures shown in the “maximum current supplied” and “maximum power supplied” columns are computed with the power consumed by the Backplanes, CPU Unit, Memory Cassettes, Peripheral Devices, I/O Power Supply Units, and Slave Units already calculated. Design the system so that the following two conditions are satisfied. Condition 1 (1) (Total current consumption of all Units in the 5-V system) ≤ (the figure in the 5-V column) (2) (Total current consumption of all Units in the 26-V system) ≤ (the figure in the 26-V column) (3) (Total current consumption of all Units in the 24-V system) ≤ (the figure in the 24-V column) Condition 2 (1) x 5 V + (2) x 26 V + (3) x 24 ≤ (maximum power supplied) 2. In the C200H-CPU21-E and C200H-CPU31-E, the maximum power drawn from the 5-V supply depends upon the current, as shown below.
Max. Power vs. Current Supplied
23
22
20
0 0
42
C200H-CPU31-E (W)
Total Power Consumption (W)
Total Power Consumption (W)
C200H-CPU21-E (W)
1.6 Current Drawn from 5-V Supply (A)
3.2 (A)
19
0 0
1.4 Current Drawn from 5-V Supply (A)
3.0 (A)
Page 51
Section 4-3
Maximum Current and Power Supplied Current Drawn from 5-V Supply (Standard I/O Units)
Unit DC Input
Model number C200H-ID211
Current consumption 0.01 A each
C200H-ID212 No-Voltage Contact Input AC Input
C200H-ID001 C200H-ID002 C200H-IA121 C200H-IA122/IA122V C200H-IA221 C200H-IA222/IA222V
AC/DC Input
C200H-IM211 C200H-IM212
Contact Output
C200H-OC221 C200H-OC222 C200H-OC223 C200H-OC224
Transistor Output
C200H-OC225
0.05 A
C200H-OD411
0.14 A
C200H-OD211
0.16 A
C200H-OD212
0.18 A
C200H-OD213
0.14 A
C200H-OD214 C200H-OD216
0.01 A each
C200H-OD217 Triac Output
Analog Timer Unit B7A Interface Unit (Standard Units)
Current Drawn from 5-V Supply for Group-2 High-density I/O Units
Unit DC Input
Transistor Output
Current Drawn from 5-V Supply for Group-2 B7A Interface Units
Unit B7A Interface Unit (Group-2 Units)
C200H-OD21A
0.16 A
C200H-OA121-E
0.14 A
C200H-OA122-E
0.18 A
C200H-OA221
0.14 A
C200H-OA223
0.18 A
C200H-OA222V
0.20 A
C200H-OA224
0.27 A
C200H-TM001
0.06 A
C200H-B7AI1 C200H-B7AO1
0.10 A
Model number C200H-ID111 C200H-ID216 C200H-ID217 C200H-ID218 C200H-ID219 C200H-OD218 C200H-OD219 C200H-OD21B
Model number C200H-B7A12/02 C200H-B7A21/22
Current consumption 0.12 A 0.1 A 0.12 A 0.1 A 0.12 A 0.18 A 0.27 A 0.18 A
Current consumption 0.10 A
43