For the Omron C200H-OD212 and Omron C200H-OD218

Page 52

Section 4-3

Maximum Current and Power Supplied Current Drawn from 5-V Supply for Special I/O Units

Unit

Model number

Current consumption 0.13 A

TTL Input

C200H-ID501

DC Input

C200H-ID215

TTL Output

C200H-OD501

Transistor Output

C200H-OD215

TTL I/O DC Input/Transistor Output

C200H-MD501

0.18 A

C200H-MD115 C200H-MD215 C200H-CT001-V1

0.30 A

High-speed Counter

0.22 A

C200H-CT002 C200H-CT021 Position Control

Analog Input Analog Output Temperature Control

C200H-NC111 C200H-NC112 C200H-NC211

0.40 0.15 A 0.50 A

C200H-AD001

0.55 A

C200H-AD002

0.45 A

C200H-DA001

0.65 A

C200H-DA002

0.6 A

C200H-TC001 C200H-TC002 C200H-TC003

0.33 A

C200H-TC101 C200H-TC102 C200H-TC103 Heat/Cool Temperature Control

C200H-TV001 C200H-TV002 C200H-TV003

0.33 A

C200H-TV101 C200H-TV102 C200H-TV103 PID Control

C200H-PID01 C200H-PID02 C200H-PID03

0.33 A

Temperature Sensor

0.45 A

ASCII

C200H-TS001/TS002 C200H-TS101/TS102 C200H-ASC02

Voice

C200H-OV001

0.30 A

ID Sensor

C200H-IDS01-V1

0.25 A

0.20 A

C200H-IDS21

44

Fuzzy Logic

C200H-FZ001

0.30 A

Cam Positioner

C200H-CP114

0.30 A

Page 53

Section 4-3

Maximum Current and Power Supplied Current Drawn from 5-V Supply for Other Units

Unit

Model number C200H-LK101-PV1

Current consumption 0.25 A

C200H-LK201-V1

0.15 A

C200H-LK202-V1

0.25 A

PC Link

C200H-LK401

0.35 A

Remote Master

C200H-RM001-PV1

0.20 A

C200H-RM201

0.25 A 0.8 A

SYSMAC NET Link Unit

C200HW-SLK13/SLK14/SLK23/ SLK24 C200HS-SNT32

Feed Adapter

C200H-APS01/ASP02/ASP03

0A

Host Link

SYSMAC LINK Unit

Current Drawn from 26-V Supply

Unit

Model number

Contact Output

C200H-OC221/OC222/OC223/ OC224/OC225

Transistor Output

C200H-OD216/OD217

ID Sensor

C200H-IDS01-V1/IDS21

1.0 A

Current consumption 0.075 A*

0.12 A

Note *With all eight outputs ON simultaneously. Current Drawn from 24-V Supply

Unit

Model number

No-Voltage Contact Input Units

Calculation Examples

C200H-ID001/ID002

Current consumption 0.06 A

The total power consumption for each Rack can be obtained from the following formulas CPU Rack =

Total power consumption for each Unit + 7 (8) (VA) 0.6 x 0.55 (1)

7 = CPU Unit power consumption, (8) = Power consumption of the CPU21-E/23-E 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when CPU31-E is used.) All other Racks =

Total power consumption for each Unit + 2 0.6 x 0.55 (1)

(VA)

2 = I/O Power Supply Unit (Remote I/O Slave Unit) power consumption 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.) Example 1

Assume that four Contact Output Units, three No-Voltage Contact Input Units, and one Host Link Unit are mounted to a Rack, along with CPU21-E. The following table shows how the total power consumption is calculated. Voltage

Current consumption

Power consumption

5V

(1) 0.01 x 7 + 0.25 = 0.32 A (≤ 3.2 A)

(1) x 5 V = 1.6 W

26 V

(2) 0.075 x 4 = 0.30 A (≤ 0.6 A)

(2) x 26 V = 7.8 W

24 V

(3) 0.06 x 3 + 0.3 = 0.48 A (≤ 0.8 A)

(3) x 24 V = 11.52 W

Total

---

20.92 W (≤ 23 W)

45

Page 54

Section 4-3

Maximum Current and Power Supplied Example 2

Assume that six DC Input Units and two High-speed Counter Units are mounted to a Rack, along with the PS221 Power Supply. The following table shows how the total power consumption is calculated. Voltage

Example 3

Current consumption

5V

(1) 0.01 x 6 + 0.3 x 2 = 0.66 A (≤ 2.7 A)

(1) x 5 V = 3.3 W

26 V

(2) 0

(2) 0

24 V

(3) Service power supply = 0.8 A (≤ 0.8A)

(3) x 24 V = 19.2 W

Total

---

22.5 W (≤ 28 W)

Assume that the following Units are mounted to a Rack to which a C200HCPU31-E is mounted. The following table shows how the total power consumption is calculated. • SYSMAC LINK Units (SLK23): 1 • Contact Output Units (OC221): 4 • High-density Input Units (ID217): 1 • High-density Output Units (OD219): 1 • High-speed Counter Units (CT002): 1 • Current for ID217: 0.3 A Voltage

Example 4

Current consumption

Power consumption

5V

(1) 0.6 + 0.01 x 4 + 0.12 + 0.27 + 0.3 = 1.33 A (≤ 3.0 A)

(1) x 5 V = 6.65 W

26 V

(2) 0.075 x 4=0.30 A (≤0.6 A)

(2) x 26 V = 7.8 W

24 V

(3) Service power supply = 0.3 A (≤ 0.8A)

(3) x 24 V = 7.2 W

Total

---

21.65 W (≤ 22 W)

Assume that the following Units are mounted to a rack to which is mounted the C200H-CPU31-E. The following table shows how the total power consumption is calculated. • SYSMAC NET Link Units (SNT32): 1 • Central Power Supply Adapter (Current 0): 1 • Contact Output Units (OC221): 2 • DC Input Units (ID212): 3 • High-speed Counter Units (CT002): 1 • Current for ID212: 0.4 A Voltage

46

Power consumption

Current consumption

Power consumption

5V

(1) 1.0 + 0.01 x 5 + 0.3 = 1.35 A (≤ 3.0 A)

(1) x 5 V = 6.75 W

26 V

(2) 0.075 x 2=0.15 A (≤0.6 A)

(2) x 26 V = 3.9 W

24 V

(3) Current=0.4 A(≤0.8 A)

(3) x 24 V = 9.6 W

Total

---

20.25 W (≤ 22 W)

Page 55

Section 4-4

I/O Connections Calculation of Power Consumption for Each Rack (Examples)

The total power consumption for each Rack can be obtained from the following formulas: • CPU Rack: Total power consumption for each Unit + 7 (8) 0.6 x 0.55 (1)

(VA)

Where: 7 = Power consumption of the CPU Unit, (8) = Power consumption of the CPU21-E/23-E, 0.6 = 60% efficiency, and 0.55 (1) = Power rate (Number in parentheses: when CPU31-E is used.)

• Expansion I/O Power Supply/Remote I/O Slave Unit: Total power consumption for each Unit + 2 0.6 x 0.55 (1)

(VA)

Where: 2 = Power consumption of the I/O Power Supply or Remote I/O Slave Unit, 0.6 = 60% efficiency, and 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.)

4-4

I/O Connections Connect the I/O Devices to the I/O Units using AWG 22 (cross-sectional area of 0.3 mm2) for 19-terminal terminal blocks and AWG 22 to AWG 18 lead wire (cross-sectional area of 0.3 to 0.75 mm2) for 10-terminal terminal blocks. The terminals have screws with 3.5-mm diameter heads and self-raising pressure plates. Connect the lead wires to the terminals as shown below. Tighten the screws with a torque of 0.8 N S m.

Power Supply Wiring

Use 1.25-mm2 cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit. Tighten the terminals on the terminal blocks to the torque of 0.8 N S m.

47

Page 56

Section 4-4

I/O Connections Terminal Block

The terminal block of an I/O Unit can be removed by loosening the mounting screws. You do not have to remove the lead wires from the terminal block in order to remove it from an I/O Unit.

Locks for terminal block. Unlock to remove the terminal block from the I/O Unit. Make sure the terminal block is locked securely after wiring is complete.

I/O Unit Cover

A C200H-COV11 Cover is provided as an I/O Unit cover for Units that use 10P terminal block connectors. After the I/O wiring has been completed, slide the cover up from the bottom, as shown in the illustration below.

Attach

Remove

DC Two-wire Sensor Connection Precautions

48

I/O Unit cover

If a two-wire sensor is used with a 12-VDC or 24-VDC input device, make sure that the following conditions are satisfied. Malfunctions will occur if these conditions are not satisfied. • The relationship between the PC ON voltage and the sensor residual voltage is as follows: VON VCC – VR • The relationship between the PC ON current and the sensor control output (load current) is as follows: IOUT (min) ION IOUT (max) ION = (VCC – VR – 1.5 (PC internal residual voltage))/RIN Connect R bleeder resistance if ION is less than IOUT (min). The constant for bleeder resistance is determined by the following equation. R (VCC – VR)/(IOUT (min) – ION) Power W (VCC – VR)2/R 4 (margin) • The relationship between the PC OFF current and sensor leakage current is as follows:

Page 57

Section 4-4

I/O Connections

IOFF Ileak Refer to the information on input and output leakage current shown below. The value of IOFF depends on the Unit used. For Input Units that have an unspecified OFF current, however, the value of IOFF is always 1.8 mA. DC Input Unit VR

Two-wire sensor

R

RIN

VCC

VCC:

Power supply voltage

VR:

Sensor output residual voltage

VON:

PC ON voltage

IOUT:

Sensor control output (load current)

ION:

PC OFF current

Ileak:

Sensor leakage current

IOFF:

PC OFF current

R:

Bleeder resistance

RIN:

PC input impedance

Input Leakage Current

When two-wire sensors, such as photoelectric sensors, proximity sensors, or limit switches with LEDs, are connected to the PC as input devices, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below. Input power supply

Bleeder resistor

R

PC

Sensor

If the leakage current is less than 1.3 mA, there should be no problem. If the leakage current is greater than 1.3 mA, determine the value and rating for the bleeder resistor using the following formulas. I = leakage current in mA 7.2 kW max. R = –––––– 2.4 x I – 3 2.3 W = ––– W min. R Output Leakage Current

If there is a possibility of leakage current causing a transistor or triac to malfunction, connect a bleeder resistor across the output as shown below. OUT

L

R Load power supply

PC Bleeder resistor COM

Determine the value and rating for the bleeder resistor using the following formula. R

Eon ––– I

49

Page 58

Section 4-4

I/O Connections Where Eon = ON voltage of the load I = leakage current in mA R = bleeder resistance Wiring Examples

The following are examples of how to connect I/O devices to I/O Units. During wiring, work slowly and carefully. If an input device is connected to an Output Unit, damage may result. Check all I/O devices to make sure they meet the specifications (refer to Appendix B Specifications).

DC Input Units Contact output

IN

DC input

COM

When using the NPN-current-output configuration shown below, the sensor and Input Unit should receive their power from the same supply. NPN current output + Current regulator

IN

Output 7 mA 0V

Sensor Power Supply

DC input

COM

NPN open-collector output +

Sensor Power Supply IN

Output 7 mA

DC input

COM

0V PNP current output +

Sensor Power Supply

Output

IN

7 mA 0V

AC/DC input

COM

0V

The circuit below should be used for I/O devices having a voltage output. Voltage output + COM Output 0V

50

IN Sensor Power Supply

DC input

Page 59

Section 4-4

I/O Connections

The circuit below should NOT be used for I/O devices having a voltage output. Voltage output + Output 0V

Sensor Power Supply IN

DC input

COM

AC Input Units Contact output

IN

AC input

COM

AC Switching IN Proximity switch main circuit

AC input

COM

Note When using a reed switch as an input contact for an AC Input Unit, the allowable current of the switch must be 1 A or greater. The contacts will be fused due to inrush current if reed switches with a lower current capacity are used. Output Units

A fuse placed in the output circuit will protect the output element, circuit board, etc., in the event of a short circuit in the output circuit. Although some Units have a built-in fuse, it is recommended that you connect an external fuse to each Output Unit for extra safety and ease of maintenance.

51