For the Omron C200H-OD212 and Omron C200H-OD218
Page 52
Section 4-3
Maximum Current and Power Supplied Current Drawn from 5-V Supply for Special I/O Units
Unit
Model number
Current consumption 0.13 A
TTL Input
C200H-ID501
DC Input
C200H-ID215
TTL Output
C200H-OD501
Transistor Output
C200H-OD215
TTL I/O DC Input/Transistor Output
C200H-MD501
0.18 A
C200H-MD115 C200H-MD215 C200H-CT001-V1
0.30 A
High-speed Counter
0.22 A
C200H-CT002 C200H-CT021 Position Control
Analog Input Analog Output Temperature Control
C200H-NC111 C200H-NC112 C200H-NC211
0.40 0.15 A 0.50 A
C200H-AD001
0.55 A
C200H-AD002
0.45 A
C200H-DA001
0.65 A
C200H-DA002
0.6 A
C200H-TC001 C200H-TC002 C200H-TC003
0.33 A
C200H-TC101 C200H-TC102 C200H-TC103 Heat/Cool Temperature Control
C200H-TV001 C200H-TV002 C200H-TV003
0.33 A
C200H-TV101 C200H-TV102 C200H-TV103 PID Control
C200H-PID01 C200H-PID02 C200H-PID03
0.33 A
Temperature Sensor
0.45 A
ASCII
C200H-TS001/TS002 C200H-TS101/TS102 C200H-ASC02
Voice
C200H-OV001
0.30 A
ID Sensor
C200H-IDS01-V1
0.25 A
0.20 A
C200H-IDS21
44
Fuzzy Logic
C200H-FZ001
0.30 A
Cam Positioner
C200H-CP114
0.30 A
Page 53
Section 4-3
Maximum Current and Power Supplied Current Drawn from 5-V Supply for Other Units
Unit
Model number C200H-LK101-PV1
Current consumption 0.25 A
C200H-LK201-V1
0.15 A
C200H-LK202-V1
0.25 A
PC Link
C200H-LK401
0.35 A
Remote Master
C200H-RM001-PV1
0.20 A
C200H-RM201
0.25 A 0.8 A
SYSMAC NET Link Unit
C200HW-SLK13/SLK14/SLK23/ SLK24 C200HS-SNT32
Feed Adapter
C200H-APS01/ASP02/ASP03
0A
Host Link
SYSMAC LINK Unit
Current Drawn from 26-V Supply
Unit
Model number
Contact Output
C200H-OC221/OC222/OC223/ OC224/OC225
Transistor Output
C200H-OD216/OD217
ID Sensor
C200H-IDS01-V1/IDS21
1.0 A
Current consumption 0.075 A*
0.12 A
Note *With all eight outputs ON simultaneously. Current Drawn from 24-V Supply
Unit
Model number
No-Voltage Contact Input Units
Calculation Examples
C200H-ID001/ID002
Current consumption 0.06 A
The total power consumption for each Rack can be obtained from the following formulas CPU Rack =
Total power consumption for each Unit + 7 (8) (VA) 0.6 x 0.55 (1)
7 = CPU Unit power consumption, (8) = Power consumption of the CPU21-E/23-E 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when CPU31-E is used.) All other Racks =
Total power consumption for each Unit + 2 0.6 x 0.55 (1)
(VA)
2 = I/O Power Supply Unit (Remote I/O Slave Unit) power consumption 0.6 = 60% efficiency 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.) Example 1
Assume that four Contact Output Units, three No-Voltage Contact Input Units, and one Host Link Unit are mounted to a Rack, along with CPU21-E. The following table shows how the total power consumption is calculated. Voltage
Current consumption
Power consumption
5V
(1) 0.01 x 7 + 0.25 = 0.32 A (≤ 3.2 A)
(1) x 5 V = 1.6 W
26 V
(2) 0.075 x 4 = 0.30 A (≤ 0.6 A)
(2) x 26 V = 7.8 W
24 V
(3) 0.06 x 3 + 0.3 = 0.48 A (≤ 0.8 A)
(3) x 24 V = 11.52 W
Total
---
20.92 W (≤ 23 W)
45
Page 54
Section 4-3
Maximum Current and Power Supplied Example 2
Assume that six DC Input Units and two High-speed Counter Units are mounted to a Rack, along with the PS221 Power Supply. The following table shows how the total power consumption is calculated. Voltage
Example 3
Current consumption
5V
(1) 0.01 x 6 + 0.3 x 2 = 0.66 A (≤ 2.7 A)
(1) x 5 V = 3.3 W
26 V
(2) 0
(2) 0
24 V
(3) Service power supply = 0.8 A (≤ 0.8A)
(3) x 24 V = 19.2 W
Total
---
22.5 W (≤ 28 W)
Assume that the following Units are mounted to a Rack to which a C200HCPU31-E is mounted. The following table shows how the total power consumption is calculated. • SYSMAC LINK Units (SLK23): 1 • Contact Output Units (OC221): 4 • High-density Input Units (ID217): 1 • High-density Output Units (OD219): 1 • High-speed Counter Units (CT002): 1 • Current for ID217: 0.3 A Voltage
Example 4
Current consumption
Power consumption
5V
(1) 0.6 + 0.01 x 4 + 0.12 + 0.27 + 0.3 = 1.33 A (≤ 3.0 A)
(1) x 5 V = 6.65 W
26 V
(2) 0.075 x 4=0.30 A (≤0.6 A)
(2) x 26 V = 7.8 W
24 V
(3) Service power supply = 0.3 A (≤ 0.8A)
(3) x 24 V = 7.2 W
Total
---
21.65 W (≤ 22 W)
Assume that the following Units are mounted to a rack to which is mounted the C200H-CPU31-E. The following table shows how the total power consumption is calculated. • SYSMAC NET Link Units (SNT32): 1 • Central Power Supply Adapter (Current 0): 1 • Contact Output Units (OC221): 2 • DC Input Units (ID212): 3 • High-speed Counter Units (CT002): 1 • Current for ID212: 0.4 A Voltage
46
Power consumption
Current consumption
Power consumption
5V
(1) 1.0 + 0.01 x 5 + 0.3 = 1.35 A (≤ 3.0 A)
(1) x 5 V = 6.75 W
26 V
(2) 0.075 x 2=0.15 A (≤0.6 A)
(2) x 26 V = 3.9 W
24 V
(3) Current=0.4 A(≤0.8 A)
(3) x 24 V = 9.6 W
Total
---
20.25 W (≤ 22 W)
Page 55
Section 4-4
I/O Connections Calculation of Power Consumption for Each Rack (Examples)
The total power consumption for each Rack can be obtained from the following formulas: • CPU Rack: Total power consumption for each Unit + 7 (8) 0.6 x 0.55 (1)
(VA)
Where: 7 = Power consumption of the CPU Unit, (8) = Power consumption of the CPU21-E/23-E, 0.6 = 60% efficiency, and 0.55 (1) = Power rate (Number in parentheses: when CPU31-E is used.)
• Expansion I/O Power Supply/Remote I/O Slave Unit: Total power consumption for each Unit + 2 0.6 x 0.55 (1)
(VA)
Where: 2 = Power consumption of the I/O Power Supply or Remote I/O Slave Unit, 0.6 = 60% efficiency, and 0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.)
4-4
I/O Connections Connect the I/O Devices to the I/O Units using AWG 22 (cross-sectional area of 0.3 mm2) for 19-terminal terminal blocks and AWG 22 to AWG 18 lead wire (cross-sectional area of 0.3 to 0.75 mm2) for 10-terminal terminal blocks. The terminals have screws with 3.5-mm diameter heads and self-raising pressure plates. Connect the lead wires to the terminals as shown below. Tighten the screws with a torque of 0.8 N S m.
Power Supply Wiring
Use 1.25-mm2 cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit. Tighten the terminals on the terminal blocks to the torque of 0.8 N S m.
47
Page 56
Section 4-4
I/O Connections Terminal Block
The terminal block of an I/O Unit can be removed by loosening the mounting screws. You do not have to remove the lead wires from the terminal block in order to remove it from an I/O Unit.
Locks for terminal block. Unlock to remove the terminal block from the I/O Unit. Make sure the terminal block is locked securely after wiring is complete.
I/O Unit Cover
A C200H-COV11 Cover is provided as an I/O Unit cover for Units that use 10P terminal block connectors. After the I/O wiring has been completed, slide the cover up from the bottom, as shown in the illustration below.
Attach
Remove
DC Two-wire Sensor Connection Precautions
48
I/O Unit cover
If a two-wire sensor is used with a 12-VDC or 24-VDC input device, make sure that the following conditions are satisfied. Malfunctions will occur if these conditions are not satisfied. • The relationship between the PC ON voltage and the sensor residual voltage is as follows: VON VCC – VR • The relationship between the PC ON current and the sensor control output (load current) is as follows: IOUT (min) ION IOUT (max) ION = (VCC – VR – 1.5 (PC internal residual voltage))/RIN Connect R bleeder resistance if ION is less than IOUT (min). The constant for bleeder resistance is determined by the following equation. R (VCC – VR)/(IOUT (min) – ION) Power W (VCC – VR)2/R 4 (margin) • The relationship between the PC OFF current and sensor leakage current is as follows:
Page 57
Section 4-4
I/O Connections
IOFF Ileak Refer to the information on input and output leakage current shown below. The value of IOFF depends on the Unit used. For Input Units that have an unspecified OFF current, however, the value of IOFF is always 1.8 mA. DC Input Unit VR
Two-wire sensor
R
RIN
VCC
VCC:
Power supply voltage
VR:
Sensor output residual voltage
VON:
PC ON voltage
IOUT:
Sensor control output (load current)
ION:
PC OFF current
Ileak:
Sensor leakage current
IOFF:
PC OFF current
R:
Bleeder resistance
RIN:
PC input impedance
Input Leakage Current
When two-wire sensors, such as photoelectric sensors, proximity sensors, or limit switches with LEDs, are connected to the PC as input devices, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below. Input power supply
Bleeder resistor
R
PC
Sensor
If the leakage current is less than 1.3 mA, there should be no problem. If the leakage current is greater than 1.3 mA, determine the value and rating for the bleeder resistor using the following formulas. I = leakage current in mA 7.2 kW max. R = –––––– 2.4 x I – 3 2.3 W = ––– W min. R Output Leakage Current
If there is a possibility of leakage current causing a transistor or triac to malfunction, connect a bleeder resistor across the output as shown below. OUT
L
R Load power supply
PC Bleeder resistor COM
Determine the value and rating for the bleeder resistor using the following formula. R
Eon ––– I
49
Page 58
Section 4-4
I/O Connections Where Eon = ON voltage of the load I = leakage current in mA R = bleeder resistance Wiring Examples
The following are examples of how to connect I/O devices to I/O Units. During wiring, work slowly and carefully. If an input device is connected to an Output Unit, damage may result. Check all I/O devices to make sure they meet the specifications (refer to Appendix B Specifications).
DC Input Units Contact output
IN
DC input
COM
When using the NPN-current-output configuration shown below, the sensor and Input Unit should receive their power from the same supply. NPN current output + Current regulator
IN
Output 7 mA 0V
Sensor Power Supply
DC input
COM
NPN open-collector output +
Sensor Power Supply IN
Output 7 mA
DC input
COM
0V PNP current output +
Sensor Power Supply
Output
IN
7 mA 0V
AC/DC input
COM
0V
The circuit below should be used for I/O devices having a voltage output. Voltage output + COM Output 0V
50
IN Sensor Power Supply
DC input
Page 59
Section 4-4
I/O Connections
The circuit below should NOT be used for I/O devices having a voltage output. Voltage output + Output 0V
Sensor Power Supply IN
DC input
COM
AC Input Units Contact output
IN
AC input
COM
AC Switching IN Proximity switch main circuit
AC input
COM
Note When using a reed switch as an input contact for an AC Input Unit, the allowable current of the switch must be 1 A or greater. The contacts will be fused due to inrush current if reed switches with a lower current capacity are used. Output Units
A fuse placed in the output circuit will protect the output element, circuit board, etc., in the event of a short circuit in the output circuit. Although some Units have a built-in fuse, it is recommended that you connect an external fuse to each Output Unit for extra safety and ease of maintenance.
51