SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: SECTION 5 Installation Environment

Pages 60 to 65 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide

The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OD212 and Omron C200H-OD218

Page 60

SECTION 5 Installation Environment This section details the necessary environment and conditions for installation of the PC. For specific instructions on mounting Units and wiring for I/O and power, refer to 2-4 Power Supply and 3-3 System Configurations. 5-1 5-2 5-3 5-4

Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Duct Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preventing Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

54 55 57 58

53

Page 61

Section 5-1

Installation Environment

5-1

Installation Environment This section details the necessary environmental conditions for installing the PC. ! Caution

Ambient Conditions

Static electricity can damage PC components. Your body can carry an electrostatic charge, especially when the humidity is low. Before touching the PC, be sure to first touch a grounded metallic object, such as a metal water pipe, in order to discharge any static build-up.

Do not install the PC in any of the following locations. Doing so will affect PC life and may affect operating performance. • Locations subject to ambient temperatures lower than 0°C or higher than 55°C. • Locations subject to drastic temperature changes or condensation. • Locations subject to ambient humidity lower than 10% or higher than 90%. • Locations subject to corrosive or flammable gases. • Locations subject to excessive dust (especially iron dust) or chloride. • Locations that would subject the CPU Unit to direct shock or vibration. • Locations that would subject the PC to water, oil, or chemical reagents. • Locations exposed to direct sunlight.

Cooling

There are two points to consider in order to ensure that the PC does not overheat. The first is the clearance between Racks, and the second is installation of a cooling fan.

Clearance Between Racks

The Racks need to have sufficient room between each other to allow for I/O wiring, and additional room to ensure that the I/O wiring does not hamper cooling. However, the Racks must be mounted close enough to each other that the length of the Connecting Cable between any two Racks does not exceed 10 m, and the total length of the Connecting Cables between all Racks does not exceed 12 m. As a general rule, about 70 to120 mm should be left between any two Racks.

Cooling Fan

A cooling fan is not always necessary, but may be needed in some installations. Try to avoid mounting the PC in a warm area, or over a source of heat. A cooling fan is needed if the ambient temperature may become higher than that specified (refer to Appendix B Specifications). If the PC is mounted in an enclosure, a cooling fan may need to be installed, as shown below, to maintain the ambient temperature within specifications. Fan

PC Control Panel

54

Page 62

Section 5-2

Mounting Requirements

5-2

Mounting Requirements The PC consists of from one to three Racks. Each Rack must be mounted vertically, that is with the printing on the front panels oriented as it would normally be read. The Racks should be mounted one above the other with the CPU Rack uppermost as shown below.

CPU Rack

These connectors are not used. Cover them with caps.

Expansion Rack

Expansion Rack

The C200H is approved by Underwriters Laboratories under the condition that, “The device must be mounted vertically for ventilation purposes.” DIN Track Mounting

The PC may be mounted using DIN Track if desired. This type of mounting is not required, and the PC may be directly mounted to any sturdy support meeting the environmental specifications (refer to Appendix B Specifications). If you want to mount the PC on DIN Track, you can order a DIN Track from OMRON (refer to Appendix A Standard Models). DIN Tracks come in the two heights shown below.

7.3-mm Height

16-mm Height

55

Page 63

Section 5-2

Mounting Requirements DIN Track Mounting Bracket

The DIN Track Mounting Bracket shown below is necessary for mounting the PC to the DIN Track.

Specification DIN Track Mounting Bracket DIN

Model

One set (two brackets)

C200H-DIN01

50 cm long, 7.3 mm high 1 m long, 7.3 mm high 1 m long, 16 mm high

PFP-50N PFP-100N PFP-100N2

Procedure 1, 2, 3...

1. The following diagram is a view of the back of the Backplane. Attach one Mounting Bracket to the left and right sides of the Backplane as shown below. Backplane

DIN Track Mounting Bracket

There are two Backplane mounting screws each on the left and right sides of the Backplane. Use these screws to attach the DIN Track Mounting Brackets to the Backplane.

2. Mount the Backplane to the DIN Track so that the claws on the Mounting Brackets fit into the upper portion of the DIN Track as shown below. This claw fits into the DIN track

DIN track

Backplane DIN Track Mounting Bracket

56

Page 64

Section 5-3

Duct Work

3. Loosen the screws attaching the Mounting Brackets to the Backplane. Slide the Backplane upward as shown below so that the Mounting Bracket and Backplane clamp securely onto the DIN Track. Tighten the screws.

DIN Track Mounting Bracket

DIN track

Hold-down bracket

Projections

5-3

Slide this screw to the top of the projection and then tighten it.

Duct Work If power cables carrying more than 10 A 400 V, or 20 A 220 V must be run alongside the I/O wiring (that is, in parallel with it), at least 300 mm must be left between the power cables and the I/O wiring as shown below.

Low current cable 1 300 mm min. Control cable 2

Power cable

300 mm min.

3

Grounding at resistance of less than 100 Ω

Where:

1 = I/O wiring 2 = General control wiring 3 = Power cables

57

Page 65

Section 5-4

Preventing Noise

If the I/O wiring and power cables must be placed in the same duct (for example, where they are connected to the equipment), they must be shielded from each other using grounded metal plates. Metal plate (iron) 200 mm min. 1

2

3

Grounding at resistance of less than 100 Ω

Where:

5-4

1 = I/O wiring 2 = General control wiring 3 = Power cables

Preventing Noise In order to prevent noise from interfering with the operation of the PC, use AWG 14 twisted-pair cables (cross-sectional area of at least 2 mm2). Avoid mounting the PC close to high-power equipment, and make sure the point of installation is at least 200 mm away from power cables as shown in the following diagram. Power lines

200 mm min. PC 200 mm min.

Whenever possible, use wiring conduit to hold the I/O wiring. Standard wiring conduit should be used, and it should be long enough to completely contain the I/O wiring and keep it separated from other cables.

58