SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: SECTION 6 Power Considerations
Pages 66 to 69 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 66
SECTION 6 Power Considerations Use a commercially available 100 to 120 VAC, 200 to 240 VAC, or 24 VDC power source, according to the model of PC you are using (refer to Appendix B Specifications). Expansion I/O Racks, if used, must also be connected to the power source. If possible, use independent power sources for the PC, input devices, and output devices. All Racks of the PC may be connected to one power source. 6-1 6-2 6-3 6-4
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Emergency Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60 60 60 61
59
Page 67
Section 6-3
Emergency Stop
6-1
Grounding To avoid electrical shock, attach a grounded (earth ground) AWG 14 wire (crosssectional area of at least 2 mm2) to the GR terminal. The resistance to ground must be less than 100 Ω. Do not use a wire longer than 20 m. Care must be taken, because ground resistance is affected by environmental conditions such as soil composition, water content, time of year, and the length of time since the wire was laid underground. The Line Ground (LG) terminal is a noise-filtered neutral terminal that does not normally require grounding. If electrical noise is a problem, however, this terminal should be connected to the Ground (GR) terminal. PC operation may be adversely affected if the ground wire is shared with other equipment, or if the ground wire is attached to the metal structure of a building. When using an Expansion I/O Rack, the Rack must also be grounded to the GR terminal. The same ground can be used for all connections.
6-2
Insulation If a separate ground is being supplied to different Racks, Backplane Insulating Plates must be used to insulate the Racks from each other. Insulating Plates are supplied as an accessory (refer to Appendix B Specifications).
6-3
Emergency Stop An external relay should be used to form an emergency stop circuit that turns the power to the PC OFF in the event of an emergency. An emergency stop routine in the PC program is not sufficient to ensure safety. The circuit shown below is an example of an emergency stop circuit. MCB1 Power section
MCB2
CR1 Control section
Transformer or noise filter PC Twisted
DC voltage regulator PC RUN output
60
-
DC input/output
CR1
Power Failure
+
Surge suppressor
A sequential circuit is built into the PC to handle power interruptions. This circuit prevents malfunctions due to momentary power loss or voltage drops. A timing diagram for the operation of this circuit is shown below.
Page 68
Section 6-4
Wiring
The PC ignores all momentary power failures if the interruption lasts no longer than 10 ms. If the interruption lasts between 10 and 25 ms, the interruption may or may not be detected. If the supply voltage drops below 85% of the rated voltage for longer that 25 ms (less for the DC Power Supply), the PC will stop operating and the external outputs will be automatically turned OFF. Operation is resumed automatically when the voltage is restored to more than 85% of the rated value.
6-4
Wiring The following diagrams show the proper way to connect the power source to the PC. The terminals marked “NC” are not connected internally.
C200H-CPU21-E/CPU31-E Screw (3.5 mm head with self-raising pressure plate)
Breaker 1:1 isolation transformer
Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC leave them open. C200H-PS221 Screw (3.5 mm head with self-raising pressure plate) Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC, leave them open.
AC Power Supply Wiring
! Caution
Isolation transformer • Noise between the PC and ground can be significantly reduced by connecting a 1-to-1 isolation transformer. Do not ground the secondary coil of the transformer.
AC power source
• Supply 100 to 120 or 200 to 240 VAC • Keep voltage fluctuations within the specified range (refer to Appendix B Specifications)
Power line • Use AWG 14 twisted pair cable (cross-sectional area of 2 mm2 min).
Use 1.25-mm2 cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit.
Tighten the AC Power Supply terminals on the terminal blocks to the torque of 0.8 N S m. Insufficient tightening may cause short-circuiting, malfunction, or burning.
61
Page 69
Section 6-4
Wiring C200H-CPU23-E Screw (3.5 mm head with self-raising pressure plate)
Breaker
• Supply 24 VDC • Keep voltage fluctuations within the specified range (refer to Appendix B Specifications)
C200H-PS211 Screw (3.5 mm head with self-raising pressure plate) Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC, leave them open.
Power Supply Wiring
62
Power line • Use AWG 14 twisted pair cable (cross-sectional area of 2 mm2 min).
Use 1.25-mm2 cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit. Tighten the terminals on the terminal blocks to the torque of 0.8 N S m.