The text of a manual · part 12 of 25
SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: SECTION 7 Safety Considerations
Pages 70 to 73 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 70
SECTION 7 Safety Considerations There are certain safety requirements to be considered when installing the PC. Some of these, such as the emergency stop circuit (refer to Section 6 Power Considerations), are part of the initial wiring. The considerations described below should be kept in mind when operating the PC and when connecting I/O devices to the PC. 7-1 7-2 7-3 7-4 7-5
Interlock Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Supply Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64 64 64 65 66
63
Page 71
Section 7-3
Input Circuits
7-1
Interlock Circuits When the PC controls an operation such as the clockwise and counterclockwise operation of a motor, provide an external interlock such as the one shown below to prevent both the forward and reverse outputs from turning ON at the same time. Interlock circuit
00501
MC2 MC1 Motor clockwise
PC 00502
MC1 MC2 Motor counterclockwise
This circuit prevents outputs MC1 and MC2 from ever both being ON at the same time. Even if the PC is programmed improperly or malfunctions, the motor is protected.
7-2
Power Supply Output
Power Supply Output
7-3
The 12 or 24 VDC output of the CPU Unit and Expansion I/O Power Supply may be used to power other devices. The output current of these supplies is limited to 0.3 A. A separate power supply must be provided if the devices being powered require a higher current.
Input Circuits
Input Leakage Current
When two-wire sensors, such as photoelectric sensors, proximity sensors, or limit switches with LEDs, are connected to the PC as input devices, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below. Input power supply
Bleeder resistor
R
PC
Sensor
If the leakage current is less than 1.3 mA, there should be no problem. If the leakage current is greater than 1.3 mA, determine the resistance and power rating for the bleeder resistor using the following formulas. For standard I/O Units: I = leakage current in mA 7.2 kΩ max. R = –––––– 2.4 x I – 3 2.3 W = ––– W min. R
64
Page 72
Section 7-4
Output Circuits For High-density I/O Units: I = leakage current in mA 29.3 R = –––––––– kΩ max. 5.9 x I – 5 2.3 W = ––– W min. R
7-4
Output Circuits
Output Leakage Current
If there is a possibility of leakage current causing a transistor or triac to malfunction, connect a bleeder resistor across the output as shown below. OUT
PC
L
R
Bleeder resistor
Load power supply
COM
Determine the value and rating for the bleeder resistor using the following formula. R
Eon ––– I
Where Eon = ON voltage of the load in V I = leakage current in mA R = bleeder resistance in kΩ Output Surge Current
When connecting a transistor or triac Output Unit to an output device having a high surge current (such as an incandescent lamp), care must be taken to avoid damage to the Output Unit. The transistor and triac Output Units are capable of withstanding a surge current of ten times the rated current. If the surge current for a particular device exceeds this amount, use the circuit shown below to protect the Output Unit.
L
OUT
+ R COM
Another way of protecting the Output Unit lets the load draw a small current (about one third the rated current) while the output is OFF, significantly reducing the surge current. This circuit (shown below) not only reduces the surge current, but also reduces the voltage across the load at the same time. R OUT
L
+ COM
65
Page 73
Section 7-5
Electrical Noise Transistor Output Residual Voltage
When connecting TTL circuits to transistor Output Units, it is necessary to connect a pull-up resistor and a CMOS IC between the two. This is because of the residual voltage left on the transistor output after the output turns OFF.
Inductive Load Surge Suppressor
When an inductive load is connected to an I/O Unit, it is necessary to connect a surge suppressor or diode in parallel with the load as shown below. This is so that the back EMF generated by the load will be absorbed. OUT
L
Relay Output Unit, Triac Output Unit Surge suppressor COM OUT
L
+
Relay Output Unit, Transistor Output Unit Diode COM
7-5
Electrical Noise Be sure to take appropriate measures when any electrical device likely to produce noise is connected to the PC as a load. Devices generating noise of more than 1,200 V (such as electromagnetic relays and valves) require noise suppression. For noise sources running off of AC power, connect a diode in parallel with the coil of each device. When mounting a CPU Rack and an Expansion I/O Rack together on a mounting plate, be sure to provide a solid ground the mounting plate. The mounting plate must be plated with a highly conductive surface in order to ensure noise immunity.
66