SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: SECTION 8 Inspection and Maintenance

Pages 74 to 79 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide

The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OD212 and Omron C200H-OD218

Page 74

SECTION 8 Inspection and Maintenance Certain consumable items in a PC (such as fuses, Relays, or batteries) need occasional replacement. This section explains how to replace each of these items. Refer to Appendix B for the specifications of individual consumable items. Always keep spare items on hand so that they can be used as immediate replacements when needed. 8-1 8-2 8-3 8-4

CPU Unit and Power Supply Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Unit Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Unit Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

68 68 69 71

67

Page 75

Section 8-2

Output Unit Fuses

8-1

CPU Unit and Power Supply Fuses

Turn counterclockwise to remove, clockwise to attach.

Standard screwdriver

To replace a fuse, follow the steps below: 1, 2, 3...

1. Turn OFF the power to the PC. 2. Remove the fuse holder by turning it approximately 50° counterclockwise with a standard screwdriver. 3. Remove the fuse from the holder. 4. Insert a new fuse. 5. Reattach the fuse holder by turning it approximately 50° clockwise with a standard screwdriver.

8-2

Output Unit Fuses To replace a fuse, follow the steps below. Use only UL/CSA certified replacement fuses. Fuse Specifications (5.2-dia. x 20) Model

1, 2, 3...

C200H-OD411

F indicator (fuse blowout detection circuit) Yes

Rating

C200H-OD211

No

C200H-OD212

No

C200H-OD213

Yes

C200H-OA121-E

Yes

C200H-OA122-E

Yes

C200H-OA221

Yes

5 A 250 V

C200H-OA222V

No

3 A 250 V

C200H-OA223

Yes

5 A 250 V

C200H-OA224

No

3.15 A 250 V

5 A 125 V 8 A 125 V 5 A 125 V

1. Turn OFF the power to the PC. 2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block.

68

Page 76

Section 8-3

Output Unit Relays

3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.

4. Using a Phillips screwdriver, remove the screw from the top of the Unit. 5. Using a flat-blade screwdriver, detach the case from the Unit.

6. Pull out the printed circuit board. 7. Insert a new fuse. A spare fuse is provided inside the rear of the case when the Unit is delivered. 8. Reassemble in reverse order of assembly. Note

1. In North America, use UL or CSA approved fuses. 2. Fuses in High-density I/O Units cannot be replaced by the user. Refer to your OMRON dealer for service.

8-3

Output Unit Relays To replace a Relay, follow the steps below: 1, 2, 3...

1. Turn OFF the power to the PC. 2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block.

69

Page 77

Section 8-3

Output Unit Relays

3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.

4. Using a Phillips screwdriver, remove the screw from the top of the Unit. 5. Using a flat-blade screwdriver, detach the case from the Unit.

6. Pull out the printed circuit board. The Relays are placed on the PC boards of individual Units as shown in the figures below. OC221/OC224

0 1 2 3 4 5 6 7

OC222

5 7 9 11

70

0 1 2 3 4 6 8 10

Page 78

Section 8-4

Batteries OC223

0 1 2 3 4

OC225

1 0 3 2 5 4 7 6 9 8 11 10 13 12 15 14

7. A Relay puller is provided inside the rear of the case when the Unit is delivered. Use the Relay puller to pull out the Relay as shown below. Insert a new Relay.

Relay puller Using the Relay puller, pull the relay up and out of the socket.

Printed circuit board

8. Reassemble in reverse order of assembly.

8-4

Batteries Some RAM Units use a battery (refer to Appendix B for specifications). When the battery is nearly discharged, the ALARM indicator blinks and the message “BATT FAIL” appears on the Programming Console. When this occurs, replace the battery within one week to avoid loss of data. The battery comes together with its connector as a set. To replace the Battery Set, follow the steps below. The entire replacement must be completed within five minutes to ensure that the data will not be lost. If you are using model C200H-CPU31-E as the CPU Unit, the battery is installed in the Unit upon delivery. 1, 2, 3...

1. Turn OFF the power to the PC. (If the power was not already ON, turn the power ON for at least one minute before turning the power OFF.)

71

Page 79

Section 8-4

Batteries

2. Remove the cover from the battery compartment of the RAM Unit. 3. Remove the old Battery Set. 4. Install the new Battery Set as shown shown in the following diagram.

Battery connector Battery Set

5. Replace the cover of the battery compartment. 6. Press CLR, FUN, MONTR, MONTR or just turn the power to the PC OFF and then ON again to clear the error message on the Programming Console.

72