SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: SECTION 3 Assembly Instructions
Pages 35 to 42 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 35
SECTION 3 Assembly Instructions When we speak of a PC, we usually think of it as a single object. But actually even the simplest PCs are usually composed of several different devices. In fact a single PC can be physically spread throughout a building, but we still call it one PC. 3-1 3-2 3-3
Mounting the Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Memory Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28 30 33
27
Page 36
Section 3-1
Mounting the Units
3-1
Mounting the Units There is no single Unit that can be said to constitute a Rack PC. To build a Rack PC, we start with a Backplane. The Backplane for the C200H is shown below.
C200H Backplane
The Backplane is a simple device having two functions. The first is to provide physical support for the Units to be mounted to it. The second is to provide the connectors and electrical pathways necessary for connecting the Units mounted to it. The core of the PC is the CPU Unit. The CPU Unit contains the program consisting of the series of steps necessary for the control task. The CPU Unit has a builtin power supply, and fits into the rightmost position of the Backplane.
The CPU Unit of the C200H has no I/O points built in. So, in order to complete the PC we need to mount one or more I/O Units to the Backplane. Mount the I/O Unit to the Backplane by locking the top of the I/O Unit into the slot on the Backplane and rotating the I/O Unit downwards as shown in the following diagram. Press down on the yellow tab at the bottom of the slot, press the I/O Unit firmly into position, and then release the yellow tab.
28
Page 37
Mounting the Units
Section 3-1 The figure below shows one I/O Unit mounted directly to the left of the CPU Unit.
I/O Units are where the control connections are made from the PC to all the various input devices and output devices. As you can see from the figure above, there is still some space available on the left side of the Backplane. This space is for any additional I/O Units that may be required.
The figure above shows a total of eight I/O Units mounted to the Backplane. I/O Units come in five shapes; A-, B-, C-, D-, and E-shapes (refer to Appendix B Specifications for dimensions). Normally, only A-shape I/O Units can be mounted to the two rightmost I/O Unit positions on the Backplane (the ones next to the CPU Unit). This is so that there will be enough room to mount peripheral devices such as a Programming Console to the CPU Unit. However, if you use a Programming Console Base Unit to increase the mounting height of the Programming Console, you will be able to mount the Programming Console to the CPU Unit even if there are other-shape I/O Units mounted to the two rightmost slots. When using 16-point Output Units (C200H-OC225/OD212/OD21A) and B7A Interface Unit (C200H-B7AO1), mount them to a C200H-BCjj1-V1/V2 Backplane. If a Backplane other than this model is used, the Units will not operate properly. Backplanes are available in different lengths (three, five, eight, ten slots), and can hold a different number of I/O Units accordingly (refer to Appendix B Specifications for dimensions). Of course, not all I/O Units look exactly alike, but the ones in the figure show their typical appearance. This configuration of Backplane, CPU Unit, and I/O Units is called a CPU Rack. This term refers to the Backplane and all the Units mounted to it. However, if we want to include more than eight I/O Units in our configuration we can add an additional Backplane.
29
Page 38
Section 3-2
Memory Units
This Backplane has I/O Units mounted to it, but it has no CPU Unit of its own. The additional Backplane must also have an Expansion I/O Power Supply mounted to its rightmost position. This configuration of additional Backplane, Expansion I/O Power Supply, and I/O Units is called an Expansion I/O Rack.
The CPU Rack and Expansion I/O Rack shown above are connected by a Connecting Cable (the length of Cable between individual Racks can be up to 10 m, but the total length of Cable between all Racks must be within 12 m). Remember that this whole configuration is still referred to as one PC. It is possible to add up to two Expansion I/O Racks to one CPU Rack. When installing I/O Connecting Cables, cover any unused connectors with the caps provided.
3-2
Memory Units The CPU Unit has a removable Memory Unit that stores the user program. Memory Units are available with three types of memory; EPROM, EEPROM, and RAM (refer to Section 2-6 Memory Units). If this is your first C200H, then you must have a RAM Unit in order to write and test the program you are going to use. If this is not your first C200H and you have a complete, tested program already, you can copy the program to an EPROM or EEPROM Unit for use on this C200H. The EEPROM chip can be written to without removing the chip from the Memory Unit by using an appropriate peripheral device (refer to Appendix A Standard Models). The EPROM Chip may be programmed using a PROM Writer or a FIT Ladder Unit. Then the EPROM Chip must be mounted inside the EPROM Unit. Note Only PROM Writer Model C500-PRW06 may be used with the C200H.
30
Page 39
Section 3-2
Memory Units How to Mount an EPROM Chip to the Memory Unit 1, 2, 3...
After the data has been written to the EPROM Chip, mount it to the inside of the EPROM Unit by following these steps. 1. Remove the cover of the EPROM Unit as shown below.
2. Unlock the holding bracket and slide it upward to remove it as shown below
3. Pull the printed circuit board out of the EPROM Unit.
31
Page 40
Section 3-2
Memory Units
4. On the printed circuit board there is a socket for the EPROM Chip. On the socket you will find a notch. Align the notch on the socket with the notch on the EPROM Chip and mount the EPROM Chip to the socket as shown below.
Notch
5. Reassemble the EPROM Unit in the reverse order of disassembly. During reassembly, ensure that the circuit board is inserted along the guides on the top and bottom of the Unit housing and that the projections on the housing fit into the holes in the holding bracket. Be sure to lock the holding bracket into the right side of the housing. When reassembled, the Unit should appear as shown below.
Circuit board guide Bracket Hole Holding bracket
Circuit board
Circuit board guide
32
Page 41
Section 3-3
System Configurations How to Mount the Memory Unit to the CPU Unit 1, 2, 3... ! Caution
Mount the Memory Unit to the CPU Unit by following the steps below. 1. Turn OFF the power to the PC. Do not attempt to mount the Memory Unit to the CPU Unit while the power to the PC is ON. Doing so may cause data to be lost, or may damage the CPU Unit or Memory Unit. 2. Set the selector switches on the Memory Unit to the desired positions (refer to 2-6 Memory Units). 3. Insert the Memory Unit into its compartment as shown below. As you do this, you will feel a slight resistance as the connector on the Memory Unit mates with the connector on the CPU Unit. Continue pushing on the Memory Unit until it is inserted completely into the CPU Unit.
Guide Guide
3-3
System Configurations When building your C200H system there may be some restrictions depending on the Unit you are using and the Rack you are mounting it to. The following figure shows an assembled CPU Rack, Expansion I/O Rack, and Remote I/O Slave Rack. Use it as a quick reference when assembling your PC. For details about the individual Units, refer to that Unit’s operation manual. The items listed below should be kept in mind. • The SYSMAC LINK Unit and the SYSMAC NET Link Unit are always mounted to either of the two slots to the left of the C200H-CPU31-E CPU Unit. When using SYSMAC NET, an Auxiliary Power Supply Unit is mounted to the left of the Units. • The 16-point Output Units (C200H-OC225/OD212/OD21A) and B7A Interface Unit (C200H-B7AO1) can only be mounted to a C200H-BCjj1-V1/V2 Backplane. • Group-2 High-density I/O Units and Group-2 B7A Interface Units can be mounted only to a C200H-CPU21-E/23-E/31-E or Expansion I/O Rack. They cannot be mounted to a Slave Rack.
33
Page 42
Section 3-3
System Configurations Special I/O Units •Up to ten Special I/O Units can be mounted. •Mount Special I/O Units to any slot on the CPU Rack (except the two slots to the left of the CPU Unit), the Expansion I/O Rack, or Slave Rack.
Host Link Unit and Remote I/O Master Unit •Up to two Units can be mounted. •Host Link Units and Remote I/O Master Units can be mounted to any slot on the CPU Rack (except the two slots to the left of the CPU Unit) or the the Expansion I/O Rack.
Group-2 High-density I/O Units and Group-2 B7A Interface Units
•Up to ten 32-point or five 64-point Units can be mounted. •Mount the Units to any slot on the CPU Rack (except the two slots to the left of the CPU Unit) or the Expansion I/O Rack. SYSMAC NET LINK Unit and SYSMAC LINK Unit
• Use up to two Units, mounted to either of the two slots to the left of the CPU Unit. •When using either of these two Units the use of peripheral devices is limited. Refer to Section 4-3 Maximum Current and Power Supplied.
I/O Units •I/O Units with 5, 8, 12, or 16 points. Standard B7A Interface Units available also. •Units with 10- or 19-terminal terminal blocks. •Units with 5 and 8 points have 10-terminal terminal blocks and Units with 10 and 12 points have 19-terminal terminal blocks. •There are some restrictions on the mounting position of 19-terminal I/O Units (refer to Appendix B Specifications).
Memory Units
•RAM, EPROM, or EEPROM Units available. •EEPROM requires an optional EEPROM Chip. •EPROM requires a separately available EPROM Chip.
CPU Unit Built-in power supply I/O Unit cover For 10-terminal block I/O Units Backplane 3-, 5-, 8-, 10-slot types available
Expansion I/O Racks Up to two Expansion I/O Racks can be connected to one CPU Rack.
Expansion I/O Power Supply I/O Connecting Cable
•Available in lengths from 30 cm to 10 m. •Total length of I/O Connecting Cables between all Racks must not exceed 12 m.
Slave Rack Up to five Racks can be connected. Group-2 High-density I/O Units and Group-2 B7A Interface Units cannot be mounted to Slave Racks. Backplane 3-, 5-, 8-, or 10-slot types available Remote I/O Slave Unit Power supply built-in
Optical Fiber Cable or Wire Cable
34