For the Omron C200H-OD212 and Omron C200H-OD218
Page 27
Section 2-5
I/O Units
2-5
I/O Units I/O Units are divided into three groups based on the way that I/O words they use are allocated. Standard I/O Units are allocated I/O words according to the Unit’s location on the CPU or Expansion I/O Rack. Group-2 High-density I/O Units are allocated I/O words according to I/O number set on each Unit. High-density I/O Units classified as Special I/O Unit are allocated I/O words according to the unit number set on each Unit.
2-5-1 Standard I/O Units Standard I/O Units come in three shapes; A-shape, B-shape, and E-shape. Refer to Appendix B Specifications for the dimensions of each Unit. A-shape I/O Unit I/O Unit lock notch
Nameplate I/O indicators: Indicate ON/OFF status of points
10-terminal terminal block
18
Page 28
Section 2-5
I/O Units B-shape I/O Unit
I/O Unit lock notch
Nameplate I/O indicators: Indicate ON/OFF status of points
19-terminal terminal block
E-shape I/O Unit (10-terminal Terminal Block)
I/O Unit lock notch
Nameplate I/O indicators Indicate ON/OFF status of points
10-terminal terminal block
19
Page 29
Section 2-5
I/O Units
2-5-2 Group-2 High-density I/O Units Group-2 High-density I/O Units come in two varieties; C-shape and D-shape. The shape of the two varieties is the same, but C-shape Units have only one connector, while the D-shape Units have two. C-shape Units have 32 I/O points and D-shape Units have 64 I/O points. Unit DC Input Unit
Transistor Output Unit
Specifications
Shape
Model
12 VDC; 64 pts
D
C200H-ID111
24 VDC; 32 pts 24 VDC; 64 pts
C
C200H-ID216
D
C200H-ID217
4.5 VDC,16 mA to 26.4 VDC,100 mA; 32 pts 4.5 VDC,16 mA to 26.4 VDC,100 mA; 64 pts
C
C200H-OD218
D
C200H-OD219
Note Refer to Optional Products, Appendix A for a list of external connectors. Group-2 High-density I/O Units are allocated I/O words in the IR Area (IR 030 to IR 049) by setting the I/O number switch on the front of each Unit. C-shape Units are allocated 2 words and D-shape Units are allocated 4 words beginning with m, where m = IR 030 + 2 × I/O number. For C-shape Units the 16 I/O bits in m are allocated to the A side of the connector, and the I/O bits in m+1 are allocated to the B side of the connector. For D-shape Units the I/O bits in m are allocated to the A side of connector 1, the I/O bits in m+1 are allocated to the B side of connector 1, the I/O bits in m+2 are allocated to the A side of connector 2, the I/O bits in m+3 are allocated to the B side of connector 2. Refer to the C200H Operation Manual (CPU21-E/23-E/31-E) for more details on I/O word allocation. Always turn the PC power off before changing a Unit’s I/O number. The new I/O number will not be recognized unless the PC has been turned off. Do not set more than one Unit to the same I/O number or set I/O numbers so that the same I/O word is allocated to more than one Unit, e.g., if you set a 64-point Unit to I/O number 0, you cannot use I/O number 1 for any Unit. Refer to Appendix B Specifications for the specifications and dimensions of the Units. C-shape Units (32-point Units) I/O Unit locking notch
Nameplate I/O indicators: Indicate ON/OFF status of points I/O number setting switch
40-pin connector
20
Page 30
Section 2-5
I/O Units D-shape Units (64-point Units)
I/O Unit locking notch
Nameplate I/O indicators: Indicate ON/OFF status of I/O points I/O number setting switch Indicator switch: Determines whether the status of connector 1 or connector 2 I/O points are indicated by the I/O indicators. 40-pin connectors
2-5-3 High-density I/O Units Classified as Special I/O Units Some High-density I/O Units are classified as Special I/O Units. Up to 10 Special I/O Units can be connected to a PC. The Units have two 24-pin connectors. In general, these Units control 32 I/O points, although some Units can control 128 I/O points when set for dynamic operation. Refer to Appendix B Specifications for detailed specifications and dimensions of the Units. Unit
Specifications
Model Number
Remarks
TTL Input Unit
5 VDC, 32 inputs
C200H-ID501
8 pts can be set as high-speed inputs.
DC Input Unit TTL Output Unit
24 VDC; 32 inputs 5 VDC, 32 outputs
C200H-ID215 C200H-OD501
Can be set for 128 dynamic outputs.
Transistor Output Unit
24 VDC; 32 outputs
C200H-OD215
TTL I/O Unit DC Input/Transistor Output Unit
5 VDC, 16 inputs, 16 outputs 12 VDC; 16 inputs, 16 outputs 24 VDC; 16 inputs, 16 outputs
C200H-MD501 C200H-MD115 C200H-MD215
8 pts can be set as high-speed inputs. Can be set for 128 dynamic inputs.
Note Refer to Optional Products, Appendix A for a list of external connectors. Setting the Unit Number
High-density I/O Units are each allocated 10 I/O words in the IR Area (IR 100 to IR 199) by setting the unit number switch on the front of each Unit. The 10 words begin with n, where n = IR 100 + 10 × unit number. For example, a Special I/O Unit with a unit number of 3 would be allocated IR 130 to IR 139. Always turn the PC power off before changing a Unit’s unit number. The new unit number (0 to 9) will not be recognized unless the PC has been turned off.
21
Page 31
Section 2-5
I/O Units Setting the DIP Switch
Pin
The operation of High-density I/O Units is controlled by setting the pins of the DIP switch on the back panel. The following table shows the function of each pin and applicable Units.
Function
Setting
Applicable Units ON
1
Operating mode
2
High-speed input1
OFF
C200H-OD501/OD215
128 dynamic outputs
32 outputs
C200H-MD501/MD115/MD215
128 dynamic inputs
16 inputs, 16 outputs
C200H-ID501/ID215
Inputs 08 to 15 of CN2 are high-speed inputs.
Normal inputs
C200H-MD501/MD115/MD215
Inputs 08 to 15 of CN2 are high-speed inputs.
Normal inputs
High-speed input C200H-ID501/ID215 minimum pulse width2 C200H-MD501/MD115/MD215 Input response time3 C200H-ID501/ID215 C200H-MD501/MD115/MD215
4 ms
1 ms
15 ms max.
2.5 ms max.
5
Data output mode4
C200H-OD501/OD215
Positive logic
Negative logic
6
Not used.
---
---
---
3 4
Note
1. Used in the C200H-MD501/MD115/MD215 only when pin 1 is OFF, setting the Unit to static mode. 2. Used in the C200H-ID501/215, C200H-MD501/MD215/MD115/MD215 only when pin 2 is ON, setting the Unit to High-speed input mode. 3. Sets the input response time for normal inputs. When pin 2 is ON, CN2 08 to 15 are pulse-catch inputs. Other inputs can be used as normal inputs. 4. Used when pin 1 is ON, setting the C200H-OD501/OD215 to dynamic output mode.
I/O Unit locking notch
Nameplate
I/O indicators: Indicate ON/OFF status of points Unit number setting switch
24-pin connectors
22
Page 32
Section 2-6
Memory Units
2-6
Memory Units There are three types of Memory Units, having three different types of memory. The three types of memory are EPROM, EEPROM, and RAM. Memory
Model
Capacity
EPROM
C200H-MP831
8K words
Maximum program size 6,974 words
EEPROM
C200H-ME431 C200H-ME831
4K words 8K words
2,878 words 6,974 words
C200H-ME432 RAM
Note
4K words
2,878 words
C200H-ME8322 8K words
6,974 words
C200H-MR431
4K words
2,878 words
C200H-MR831
8K words
6,974 words
C200H-MR432
4K words
2,878 words
C200H-MR832
8K words
6,974 words
C200H-MR433
4K words
2,878 words
C200H-MR833
8K words
6,974 words
Backup
Clock1
---
NO
Battery
YES
Battery
NO
Capacitor Battery
YES
1. With the C200H-CPU21-E and C200H-CPU23-E CPU Units, a Memory Unit with the clock must be installed to use the clock/calendar and error history functions. 2. The C200H-ME832 Memory Unit cannot be used with the C200HCPU01-E/03-E/11-E CPU Units. 3. The C200H-CPU31-E CPU Unit has a built-in clock.
Contents for Memory Unit Registration
Fixed DM area (DM 1000 to DM 1999)
I/O table (see note)
UM (ladder program area)
Note I/O tables are also saved in the Memory Unit at the time of creation. Therefore, if the Memory Unit is set to write-protect, it will be impossible to create an I/O table. EPROM Unit
The data that you wish to store in an EPROM Unit must first be written to an EPROM Chip, using the PROM Writer. Then the EPROM Chip must be mounted to the inside of the EPROM Unit.
EEPROM Unit
Data can be stored in the EEPROM Unit while the Unit is mounted to the PC. The data is retained indefinitely when the power is turned OFF.
23
Page 33
Section 2-6
Memory Units RAM Unit
Data can be randomly written to and read from the RAM Unit. However, the Unit requires battery or capacitor back-up in order to retain the information when the power is OFF. Units with battery back-up can retain their data for approximately five years at room temperature (25°C). Units with capacitor back-up retain their data for approximately 20 days at room temperature, but the length of time varies with temperature as shown below.
20 Capacitor back-up time (days)
10 7 1 25
! Caution
50 80 Ambient temperature (°C)
Be sure to turn off the power when mounting or dismounting a Memory Unit, or an error will result and the internal circuitry may be damaged.
Note A memory error might occur when a RAM Unit is installed in a C200HCPU21-E/23-E/31-E CPU Unit with data written using a C200HCPU01-E/03-E/11-E CPU Unit or a GPC and C500-PRW06 PROM Writer. Turn the PC power off and on again to clear the error. Switches on Memory Units
Two switches are provided on Memory Units, as shown below.
1 2
Write-enable switch (SW1)
ON OFF
Initial mode selector (SW2)
SW1 (the write-enable switch) only has an effect if the Unit is a RAM Unit or EEPROM Unit. Peripheral devices can only write data to these Memory Units if SW1 is ON. When you wish to write data to this Memory Unit, make sure SW1 is set to the ON position. After you have finished writing the data to the Memory Unit, turn SW1 to the OFF position so that the data will be protected from any further changes. If you try to write data to the Memory Unit while SW1 is in the OFF position, the message “DISABLED ROM” will appear on the Programming Console. SW2 Selects what operating mode the PC will be in when power is applied to the System. If there is no peripheral device connected to the CPU Unit, the PC will enter RUN mode when power is applied. If a Programming Console is connected to the CPU Unit, the PC will enter the mode that the Programming Console is set to. If a peripheral device other than the Programming Console is connected to the CPU Unit, the PC will enter the mode specified by SW2.
24
Page 34
Section 2-6
Memory Units Battery Failure Flag
The C200H-CPU31-E, unlike the other two CPU Unit models, has an additional battery connected to the CPU Unit. A flag, assigned to the bits listed in the following table, indicates where battery failure occurred (in the RAM Unit, EEPROM Unit, or in the CPU Unit) and in which Unit. Model
Bit
C200H-CPU21-E/23-E
25308
C200H-CPU31-E
25308 AR2404
Function Battery failure in RAM/EEPROM Unit Battery failure in RAM/EEPROM Unit or CPU Unit Battery failure in CPU Unit
In the following table, the ON/OFF status of the bits indicate where battery failure took place in the C200H-CPU31-E. For example, when bit 25308 is ON the battery in the CPU Unit failed. 25308
AR2404
Unit in which the battery failed
ON
ON
CPU Unit
ON
OFF
RAM/EEPROM Unit
25