The text of a manual · part 5 of 25
SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: SECTION 2 Unit Description, pages 18 to 26
Pages 18 to 26 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 18
SECTION 2 Unit Description This section provides information about the individual Units that make up a PC. The names of all the parts of a Unit are given, followed by any details that apply to that Unit alone. For a description of how the Units fit together to become a PC, refer to Section 3 Assembly Instructions. For information about the model numbers of any of the parts described in this section, refer to Appendix A Standard Models. 2-1 2-2 2-3 2-4 2-5
2-6
CPU Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expansion I/O Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-1 Standard I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-2 Group-2 High-density I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-3 High-density I/O Units Classified as Special I/O Units . . . . . . . . . . . . . . . . . . . . Memory Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 11 16 17 18 18 20 21 23
9
Page 19
Section 2-1
CPU Rack
2-1
CPU Rack The following figure shows the names of all the parts of a CPU Rack. There are four models of Backplanes available with 3, 5, 8 and 10 slots for I/O Units. You can use any of these Backplanes to build a CPU or Expansion I/O Rack. The C200H-OC225/OD212/OD21A 16-point Output Unit and the C200H-B7AO1 B7A Interface Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
This connector not used. Cover with a cap. Backplane
I/O Units
I/O Connecting Cable connector: Connects CPU Rack to Expansion I/O Rack. When not used, cover with a cap.
10
CPU Unit
Backplane mounting screws (four, with 4-mm dia. heads)
Page 20
Section 2-2
CPU Units
2-2
CPU Units This guide covers three C200H CPU Unit models: the C200H-CPU21-E, C200H-CPU23-E, and C200H-CPU31-E. The C200H-CPU21-E, CPU23-E, and CPU31-E basically correspond to the earlier C200H-CPU01-E, CPU03-E, and CPU11-E. The C200H-CPU21-E/CPU23-E/CPU31-E CPU Units are based on the C200HCPU11-E CPU Unit, except only the CPU31-E supports Network Instructions. All of the CPU Units covered in this manual also support a group of High-density I/O Units called Group-2 High-density I/O Units. Group-2 High-density I/O Units are classified by themselves and are not classified as Special I/O Units. The following table lists the capabilities of the various C200H CPU Units. Function
CPU01-E CPU03-E CPU11-E CPU21-E CPU23-E CPU31-E
Compatible with Group-2 High-density I/O Units (C200H-ID111/ID216/ID217/OD218/OD219)
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes1
Yes1
Yes2
Yes
Yes
Yes2
No
No
No
Yes
Yes
Yes2
No
No
Yes
Yes
Yes
Yes
Yes3
Yes
Compatible with Group-2 B7A Interface Units. Note: Cannot be mounted to Slave Racks. Can process GROUP-2 HIGH-DENSITY I/O REFRESH – MPRF(61) Compatible with Memory Units: C200H-MR433/MR833/ME432 Compatible with Memory Unit C200H-ME832 Error history Clock/calendar
No
No
Yes
Yes3
Forced Status Hold Bit (SR 25211)
No
No
Yes
Yes
Yes
Yes
Can set TERMINAL mode in Programming Console Additional instructions: REVERSIBLE WORD SHIFT – RWS(17) CYCLE TIME – SCAN(18) MULTI-WORD COMPARE – MCMP(19) LONG MESSAGE – LMSG(47) TERMINAL MODE – TERM(48) SET SYSTEM – SET(49) DOUBLE COMPARE – CMPL(60) COLUMN-TO-WORD – CTW(63) WORD-TO-COLUMN – WTC(64) HOURS-TO-SECONDS – HTS(65) SECONDS-TO-HOURS – STH(66) VALUE CALCULATE – VCAL(69)
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
SYSMAC NET Link/SYSMAC LINK Instructions: NETWORK SEND – SEND(90) NETWORK RECEIVE – RECV(98)
No
No
Yes
No
No
Yes4
Power Supply
AC
DC
AC
AC
DC
AC
Note
1. The C200H-CPU01-E and C200H-CPU03-E cannot use the Memory Units’ clock/calendar. 2. The C200H-CPU11-E and C200H-CPU31-E CPU Units have a built-in clock/calendar. 3. The C200H-CPU21-E and C200H-CPU23-E can use the C200HMR433/MR833/ME432 Memory Units’ clock/calendar. 4. Up to two SYSMAC LINK Unit and/or SYSMAC NET Link Units can be connected to the C200H-CPU31-E CPU Unit. These two Units can be mounted to either of the two slots located directly to the left of the the CPU Unit and connected to the CPU Unit via a bus connector. A separate Unit, the bus connector Unit, is required to connect the SYSMAC NET Link Unit or the SYSMAC LINK Unit to the CPU Unit.
11
Page 21
Section 2-2
CPU Units C200H-CPU21-E/23-E
Indicators
Power fuse (MF51NR, 5.2 dia. x 20 mm) C200H-CPU21-E: 2 A, 250 V C200H-CPU23-E: 5 A, 125 V
Memory Unit connector
Detachable terminal block
Peripheral device mounting hole
Programming Console connector cover storage slot Programming Console connector: (Peripheral device connector) Remove cover to gain access to connector; store cover in cover storage slot.
Handheld Programming Console connector: Remove cover to gain access to connector.
C200H-CPU31-E
Indicators
Power fuse (MF51NR, 5.2 dia. x 20 mm): 2 A, 250 V Memory Unit connector
Power supply terminals (on removeable terminal block) Battery compartment
Bus connector: Available only with the C200H-CPU31-E. Used to connect this Unit to a SYSMAC LINK Unit or SYSMAC NET Link Unit.
Handheld Programming Console connector
Programming Console connector cover storage slot
Programming Console connector (Peripheral device connector)
12
Page 22
Section 2-2
CPU Units CPU Unit Indicators
The following figure shows the indicators that are located on the front panel of the three CPU Unit models. POWER (green): Lights when power is supplied to the CPU Unit.
RUN indicator (green): Lights when the PC is operating normally.
ALARM (flashes red): Flashes if an error occurs that does not stop the CPU Unit.
OUT INHIBIT (red): Lights when the Load OFF flag (SR bit 25215) turns ON, at which time all the outputs are turned OFF.
ERROR (solid red): Lights if an error occurs that stops the CPU Unit, at which time the RUN indicator turns OFF and the outputs are turned OFF.
Peripheral Device Connectors
All three CPU Unit models are equipped with two connectors for peripheral devices. One is used for the Handheld Programming Console or the Data Access Console; the other is used for the CPU Unit-mounting Programming Console. The C200H-CPU31-E, however, has a third connector that is used for connecting the SYSMAC LINK Unit or the SYSMAC NET Link Unit to the CPU Unit. To connect the Handheld Programming Console to the CPU Unit, a Connecting Cable is required, as shown in the following diagram. Note If you are using the SYSMAC LINK Unit or SYSMAC NET Link Unit in your system, you must use model C200H-CPU31-E as the CPU Unit. The other two models mentioned above are not equipped with the appropriate connectors.
13
Page 23
Section 2-2
CPU Units Cable Connection
Connecting Cable
Hand-held Programming Console
The CPU Unit-mounting Programming Console can be mounted directly to the CPU Unit and does not require a Connecting Cable. To mount the CPU Unitmounting Programming Console (or any other peripheral device) directly to the CPU Unit, follow the steps below. Direct Mounting
14
The CPU Unit-mounting Programming Console, when mounted to the CPU Unit, covers the two I/O Units located directly to the left of the CPU Unit. For this reason it is important to know which shapes can be mounted to these slots. Notice, in the following diagram, that the two I/O Units mounted directly to the left of the CPU Unit are A-shape Units. The CPU Unit-mounting Programming Console can be mounted to the CPU Unit provided A-shape I/O Units are mounted to these two slots. Make sure the protective covers of the two I/O Units are in place to avoid electrical interference with the CPU Unit. Because the surface of B-shape and E-shape I/O Units protrudes a few centimeters from surface of the CPU Unit, B-shape and E-shape I/O Units cannot be mounted to the two slots to the left of the CPU Unit unless a Programming Console Base Unit is first mounted to the CPU Unit to increase the mounting height of the Programming Console.
Page 24
Section 2-2
CPU Units
If you are using the C200H-CPU31-E, a SYSMAC LINK Unit or a SYSMAC LINK Unit can be mounted to either of the two slots to the left of the CPU Unit. They are then connected to the CPU Unit with the Bus Connector Unit.
Peripheral device
CPU Rack
A-shape I/O Units
1, 2, 3...
1. Remove the cover from the peripheral device connector with a standard screwdriver. 2. Connect the CPU Unit-mounting Programming Console to the peripheral device connector. 3. Attach the CPU Unit-mounting Programming Console to the CPU Unit by tightening the mounting screws.
15
Page 25
Section 2-3
Expansion I/O Rack
2-3
Expansion I/O Rack The Backplane used to construct a CPU Rack is also used to construct an Expansion I/O Rack. An Expansion I/O Rack is identical to a CPU Rack, except the CPU Unit has been replaced with a Power Supply. The parts of an Expansion I/O Rack are shown in the following diagram. I/O Connecting Cable connector: Connects Expansion I/O Rack to preceding Expansion I/O Rack or to CPU Unit. Backplane
I/O Connecting Cable connector: Connects Expansion I/O Rack to next Expansion I/O Rack. When not used, cover with a cap.
16
Power Supply
I/O Units Backplane mounting screws (four, with 4-mm dia. heads)
Page 26
Section 2-4
Power Supplies
2-4
Power Supplies The Power Supply used for Expansion I/O Racks is available in two models. One runs on 100 to 120 or 200 to 240 VAC, and the other runs on 24 VDC.
AC Power Supply POWER indicator (green): Lights when power is supplied to Power Supply
Power fuse: 2 A 250 V (5.2-dia. x 20) MF51NR
AC Input Voltage selector terminals Short: 100 to 120 VAC Open: 200 to 240 VAC LG
Terminals for external connections
GR +
24 VDC 0.3 output NC NC
DC Power Supply POWER indicator (green): Lights when power is supplied to Power Supply
Power fuse: 5 A 125 V (5.2-dia. x 20) MF51NR
+
24 VDC
NC Terminals for external connections
+
NC
NC NC NC NC
17