SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: Appendix, pages 170 to 177
Pages 170 to 177 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide
The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OD212 and Omron C200H-OD218
Page 170
Appendix B
Specifications Separate Power Supplies
B7A Link Terminal
B7A Interface Unit 12 to 24 VDC Transmission distance: 500 m max.
B7A Link Terminal 12 to 24 VDC
Transmission cable: VCTF 0.75 mm2 or higher 12 to 24 VDC
High-speed Transmission Delays (3 ms): Shielded Cable B7A Link Terminal
Common Power Supply B7A Interface Unit
Transmission distance: 50 m max.
B7A Link Terminal Shielded cable: 0.75 mm2 or higher GND
Shielded cable: 0.75 mm2 or higher 24 VDC±10%
GND
Separate Power Supplies
B7A Link Terminal
B7A Interface Unit 12 to 24 VDC Transmission distance: 100 m max.
Shielded cable: 0.75 mm2 or higher
B7A Link Terminal
GND 12 to 24 VDC
12 to 24 VDC
Shielded cable: 0.75 mm2 or higher GND
Note 1. We recommend grounding the shielded cable. 2. If shielded cable is not used, the maximum transmission distance is 10 m regardless of whether a common or separate power supplies are used. Use 0.75 mm2 or higher VCTF cable. 3. To prevent noise on the transmission cable, do not lay it near power cables or high-voltage lines.
164
Page 171
Appendix B
Specifications
Specifications Item
C200H-B7A12
C200H-B7A02
I/O points
32 input points or 30 input points and 2 error inputs
32 output points
Transmission method Transmission distance (see note 1)
One-way distributed multiplex transmission Standard:
500 m max.
High-speed:
100 m max.
Transmission delay
Standard:
Typ. 19.2 ms, 31 ms max.
High-speed:
Typ. 3 ms, 5 ms max.
Minimum input time (see note 2)
Standard:
16 ms
High-speed:
2.4 ms
Internal current consumption External power supply (see note 3)
5 VDC, 100 mA max.
Weight
300 g max.
Dimensions
35 x 130 x 128 mm (W x H x D)
C200H-B7A21
C200H-B7A22
16 output points and 16 input points or 15 input points + 1 error input
32 output points and 32 input points or 30 input points + 2 error inputs
0.05 A min.
0.08 A min.
12 to 24 VDC ±10% 0.05 A min.
0.06 A min.
Note 1. The transmission distance also depends on whether a common or separate power supplies are used. 2. The minimum input time is the minimum time required to read input signals from the CPU Unit. The ON/ OFF width of signals from the CPU Unit to the output relays of the B7A Interface Unit must be at least equal to the minimum input time. 3. The capacity of the external power supply does not include the capacity required by the B7A Link Terminal.
165
Page 172
Appendix B
Specifications
Dimensions Racks The dimensions shown below are for both the CPU Rack and Expansion I/O Rack. The C dimension for the Programming Console will increase by 30mm when the Programming Console Adapter C200H-BP001 is used, and will increase by 50 mm when the Programming Console Adapter C200H-BP002 is used.
M-4 screws 130 118
A W
6.5
7.5
C200H-BC101-V2 505 491 270.5
Model
A
W
C200H-BC031-V2
246
260
C200H-BC051-V2
316
330
C200H-BC081-V2
421
435
C200H-BC101-V2
491
505
CPU Units
135 Peripheral device
D C
CPU Unit
166
D
C200H-CPU21-E/23-E
118
C200H-CPU31-E
143
Page 173
Appendix B
Specifications Peripheral Unit
C CPU21-E/23-E
CPU31-E
Programming Console
148
173
Other peripheral device
160
185
B-shape I/O Unit
145
145
E-shape I/O Unit
138
138
Standard I/O Units The dimensions shown below are for the two shapes of Standard I/O Units mentioned throughout these specifications. 10-terminal Terminal Block (A-shape I/O Units)
19-terminal Terminal Block (B-shape I/O Units)
x x x x
Backplane
130 x x x x 128
35
145
167
Page 174
Appendix B
Specifications 10-terminal Terminal Block (E-shape I/O Units)
Backplane x x 130 x x 121 35
138
Terminal Dimensions M3.5
7.3 8.5
Group-2 High-density I/O Units The dimensions shown below are for the Group-2 High-density I/O Units. Dimensions with Unit Mounted
Backplane
Group-2 High-density I/O Units (C and D Types)
130
35
168
101
118 Approx. 143
Page 175
Appendix B
Specifications
High-density I/O Units (Special I/O Units) The dimensions shown below are for the High-density I/O Units classified as Special I/O Units.
130
34.5
100.5
Dimensions with Unit Mounted
Connecting cable
G79-jC Connecting Cable is Used
G79-jC Connecting Cable
Backplane
Backplane
Fujitsu’s Connector is Used
118
118 145
Approx. 163
Backplane
Standard B7A Interface Unit The dimensions shown below are for the B7A Interface Unit classified as Special I/O Units.
130
35
101 118
169
Page 176
Appendix B
Specifications
The dimensions shown below are for the Group-2 B7A Interface Units.
Backplane
Group-2 B7A Interface Units
Backplane
Analog Timer Unit The dimensions shown below are for the Analog Timer Unit classified as Special I/O Units.
130
35
101 118
170
Page 177
Appendix B
Specifications
Backplane Insulation Plates The dimensions shown below are for Backplane Insulation Plates. PC mounting screws Four screws with 4-mm diameter heads are provided.
Insulation plate mounting screws Four screws with 5-mm diameter shafts are provided. B
135
118 110
C D A E
6 5 dia
12 dia
10
Specifications
Model
D
E
C
A
B
3 slots
C200H-ATT31
210
261
---
246
---
5 slots
C200H-ATT51
280
331
---
316
---
8 slots
C200H-ATT81
385
436
---
421
---
10 slots
C200H-ATTA1
455
506
227.5
491
270.5
I/O Connecting Cables The dimensions shown below are for I/O Connecting Cables. L
Cable
Length (L)
C200H-CN311
30 cm
C200H-CN711
70 cm
C200H-CN221
2m
C200H-CN521
5m
C200H-CN131
10 m
171