For the Omron C200H-OD212 and Omron C200H-OD218
Page 160
Appendix B
Specifications ! Caution
Ensure that the external variable resistor connectors are open when using the internal variable resistor.
External variable resistor connector
External variable resistor
Standard B7A Interface Units (C200H-B7AI1/B7AO1) The B7A Interface Unit used with the B7A Link Terminal allows the transmission and reception of 16-point I/O data over two wires. The following B7A Interface Units and B7A Link Terminal models are available. B7A Interface Unit 16-point input: C200H-B7AI1 16-point output: C200H-B7AO1
B7A Link Terminals B7A-T6j1 (Screw terminal models) B7A-T6D2 (Modular models) B7A-R6jj1 (Screw terminal models) B7A-R6A52 (Modular models)
Mount the B7A Interface Unit (C200H-B7AO1) to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. Note 1. The B7A Interface Terminal can be connected only to 16-point B7A Link Terminals and then only if the Terminal has a standard transmission delay (i.e., 19.2 ms) 2. If the B7A Interface Unit is connected to the C200H-CPU23-E or C200H-PS211, supply 24 VDC from an independent power supply to the B7A Interface Unit or use a transformer to separate the power supply line to the B7A Interface Unit from the power supply lines to the CPU Unit and I/O Power Supply Unit.
I/O indicators ERR indicator
Connection terminals Connection terminals for the B7A Link Terminal: Connect this terminal to the SIG terminal of the B7A Link Terminal. Connect this terminal to the negative power terminal of the B7A Link Terminal. Supply 12 to 24 VDC. 12 to 24 VDC
I/O Indicators Indicate the ON or OFF status of inputs from the B7A Link Terminal or the ON and OFF status of outputs to the B7A Link Terminal.
154
Page 161
Appendix B
Specifications
ERR Indicator Incorporated by the B7AI1 and lit when the B7AI1’s data transmission or reception is abnormal. Connection Terminals SIG: Connects to the SIG terminal of the B7A Link Terminal. V–: Connects to the negative power terminal of the B7A Link Terminal. ! Caution
If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be damaged.
Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm2 minimum. 2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit. Input Mode Selector The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can be set. Input mode
15 points + 1 error (switch set up)
16 points (switch set down)
Function
Fifteen-point input from the B7A Link Terminal is effective. Bit 15 is used as transmission error bit.
Sixteen-point input from the B7A Link Terminal is effective.
Switch setting Bit no. allocation
Upper side
Lower side
00 to 14 15 Status of input indicator lamp 15 Status of the ERR indicator
Input 00 to input 14 Transmission error bit Not used
Input 00 to input 14 Input 15 Lit when input 15 is ON. Not lit when input 15 is OFF. Lit when there is a transmission error and OFF during normal transmission
The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next transmission cycle. When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the transmission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is transmitted in the first transmission cycle when the B7A Link Terminal is turned on again. Transmission errors between the C200H-B7AO1 and B7A Link Terminal are detected by the B7A Link Terminal only. Check the ERR indicator and error bit for any error. Performance Specifications Item I/O points
C200H-B7AI1
C200H-B7AO1
Transmission distance
16 points or 15 points and 1 error 16 output points input 500 m max. if power is supplied to the Interface Unit and B7A Link Terminal separately. 100 m max. if power is supplied to the Interface Unit and B7A Link Terminal from a single power supply. (24 VDC±10%)
Transmission delay
Typ. 19.2 ms, 31 ms max.
Minimum input time (see note 1)
---
Internal current consumption
5 VDC, 100 mA max.
External power supply (see note 2)
12 to 24 VDC ±10%, 10 mA min.
Weight
200 g max.
16 ms 12 to 24 VDC ±10%, 30 mA min.
Note 1. The minimum input time is the minimum time required to read input signals from the CPU Unit. The ON/ OFF width of signals from the CPU Unit to the output relays of the B7A Interface Unit must be at least equal to the minimum input time. 2. The capacity of the external power supply does not include the capacity required by the B7A Link Terminal.
155
Page 162
Appendix B
Specifications
Group-2 B7A Interface Units (C200H-B7Ajj) A Group-2 B7A Interface Unit used with two or four B7A Link Terminals allows the transmission and reception of 32-point or 64-point I/O data over two-conductor cables. Group-2 B7A Interface Unit
C200H C200HCPU21-E/22-E/23-E/31-E CPU Unit
Input B7A Link Terminal
Sensor Switch
Transmission distance: 500 m max.
Output B7A Link Terminal
Lamps and other loads
Group-2 B7A Interface Units can be mounted to a CPU Rack containing a C200H-CPU21-E/22-E/23-E/31-E CPU Unit or an I/O Expansion Rack for one of these CPU Units. They cannot be mounted to Slave Racks or to Racks controlled by any other CPU Units. The words allocated to Group-2 B7A Interface Units are determined by I/O number set on the Units. Units with 32 I/O points are allocated two words; Units with 64 I/O points are allocated four words. Refer to the B7A Link Terminals Datasheet for more information on B7A Link Terminals.
Models The following Group-2 B7A Interface Units are available. B7A Interface Unit
Inputs
Outputs
C200H-B7A12
32 points
None
C200H-B7A02
None
32 points
C200H-B7A21
16 points
16 points
C200H-B7A22
32 points
32 points
156
Page 163
Appendix B
Specifications
Connectable B7A Link Terminals Input Terminals Type Screw terminals
Modular PC connectors
Model B7A-T6j1 B7AS-T6j1 B7A-T6j6 B7AS-T6j6 B7A-T6D2 B7A-T6D7 B7A-TjE3 B7A-TjE8
Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)
Output Terminals Type Screw terminals
Modular PC connectors
Model B7A-R6jj1 B7AS-R6jj1 B7A-R6jj6 B7AS-R6jj6 B7A-R6A52 B7A-R6A57 B7A-RjAj3 B7A-RjAj8
Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)
Note 1. Do not connect Terminals with different transmission delays to the same Interface Unit. Doing so will cause a transmission error. 2. 10-point B7A Link Terminals and Mixed I/O (8 inputs/8 outputs) B7A Link Terminals cannot be connected to a B7A Interface Unit. 16-point B7A Link Terminals, 32-point B7A Link Terminals with a two-circuit configuration, and Mixed I/O B7A Link Terminals with a 16-point input/output configuration can be connected.
Comparison between Standard and Group-2 B7A Interface Units Type
Standard
Models
C200H-B7AI1 C200H-B7AO2
Group-2
C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22
CPU Unit
Word allocations
Any C200H CPU Unit
Same as I/O Units (in order mounted).
C200H-CPU21E/22-E/23-E/ 31-E CPU Unit only
Words 030 to 049 allocated according to I/O number setting (see note 3) (same as Group-2 High-density I/O Units)
Connectable B7A Link Terminals Transmission delay Standard types only (19.2 ms)
Transmission errors Input status held automatically
Standard (19.2 ms) and high-speed (3 ms) types (set via switch)
Switch setting to hold or reset Input status.
Points (see note 2) 16-point Terminals only (10-point, 32-point, and mixed I/O Terminals cannot be connected.
Note 1. Mount the B7A Interface Unit (C200H-B7AO1) to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. 2. 10-point B7A Link Terminals and Mixed I/O B7A Link Terminals with an 8 input-8 output configuration cannot be connected to a B7A Interface Unit. 16-point B7A Link Terminals, 32-point B7A Link Terminals with a two-circuit configuration, and Mixed I/O B7A Link Terminals with a 16-point input or output configuration can be connected. 3. Words IR 030 to IR 049 (Group-2 High-density I/O Unit and B7A Interface Unit Area) are allocated to the inputs/outputs of Group-2 B7A Interface Units according to the setting of the I/O number switch on the front of the Unit, in the way shown in the following table (for Mixed I/O Units, words are allocated in the order output → input for each Unit).
157
Page 164
Appendix B
Specifications Unit
Models
32 inputs
C200H-B7A12
32 outputs
C200H-B7A02
16 outputs, 16 inputs
C200H-B7A21
32 outputs, 32 inputs
C200H-B7A22
Words allocated per Unit 2
4
Allocation order 2 words allocated to inputs 2 words allocated to outputs 1 word allocated to outputs → 1 word allocated to inputs 2 words allocated to outputs → 2 words allocated to inputs
Words allocated when I/O number = 0 IR 030: input IR 030: output IR 030: output IR 031: input IR 030: output IR 031: output IR 032: input IR 033: input
Parts and Names (C200H-B7A22 shown below) Front
I/O number switch This switch determines the words allocated to the Unit. Status indicators The indicators depend on the model of B7A Interface Unit.
Connection terminals Connect to the SIG terminal of the B7A Link Terminal and to the negative power terminal of the B7A Link Terminal. The actual use of these terminals depends on the B7A Interface Unit.
External Power Supply Terminals Supply 12 to 24 VDC.
12 VDC 12toto2424 VDC
158
Page 165
Appendix B
Specifications Back
DIP switch Used to set the transmission delay, transmission error processing mode, input mode, and ERROR indicator operation.
Indicator Operation The indicators depend on the model of B7A Interface Unit, as shown below.
Name
Color
Function
ERROR 1 ERROR 2 ERROR
Input transmission error
Red
Lights when an error occurs in transmissions from an Input B7A Link Terminal. For the B7A12/22, ERROR 1 is for the first word allocated to the B7A Interface Unit; ERROR 2 is for the second word.
3ms
Transmission delay setting
Orange
Lit when the transmission delay is set to the high-speed setting (3 ms).
LOAD OFF
Transmission error process
Orange
15IN+ERR
Input mode setting
Orange
Not lit when the transmission delay is set to the standard setting (19.2 ms). Lit when the processing for transmission errors is set to reset input status. Not lit when the processing for transmission errors is set to hold input status. Lit when the input mode mode is set to use 15 inputs and 1 error input. Not lit when the input mode mode is set to use 16 inputs.
I/O Number Setting The setting of the I/O number determines the words allocated to the Interface Unit. Set the I/O number to between 0 and 9.
Setting in direction of notch
Note 1. Turn off the power supply to the PC before changing the I/O number setting. Any new setting will not be effective until the next time the power supply is turned on.
159
Page 166
Appendix B
Specifications
2. Use a flat-blade screw driver to change the I/O number setting. Be careful not to leave the switch halfway between settings and be careful not to damage the switch. The following table shows the words allocated according to the I/O number. The 32-point Units are the C200H-B7A12, C200H-B7A02, and C200H-B7A21. The 64-point Unit is the C200H-B7A22. Words
I/O No. 0
32-point Units IR 030 and IR 031
64-point Unit IR 030 to IR 033
1
IR 032 and IR 033
IR 032 to IR 035
2
IR 034 and IR 035
IR 034 to IR 037
3
IR 036 and IR 037
IR 036 to IR 039
4
IR 038 and IR 039
IR 038 to IR 041
5
IR 040 and IR 041
IR 040 to IR 043
6
IR 042 and IR 043
IR 042 to IR 045
7
IR 044 and IR 045
IR 044 to IR 047
8
IR 046 and IR 047
IR 046 to IR 049
9
IR 048 and IR 049
Do not use.
Note 1. Be sure that the same words are not allocated to more than one Unit. For example, if you set a 64-point Unit to I/O number 0, you cannot use I/O number 1 for any Unit. 2. The above words are also allocated to Group-2 High-density I/O Units. Be sure that the same words are not allocated to more than one Unit.
DIP Switch Settings Set the DIP switch as described before for the various models of B7A Interface Units. C200H-B7A22/12 Pin
Factory setting (pins 4 and 5 ON)
Function
OFF
ON
1
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
2
Transmission error process
Hold status
Reset Inputs
3
Input mode
16 inputs
15 inputs + error input
4
ERROR 1 indicator enable
Disabled
Enabled
5
ERROR 2 indicator enable
Disabled
Enabled
6
Not used.
NA
NA
C200H-B7A21 Pin
Factory setting (pin 5 ON)
Function
OFF
ON
1
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
2
Transmission error process
Hold status
Reset Inputs
3
Input mode
16 inputs
15 inputs + error input
4
ERROR indicator enable
Disabled
Enabled
5
Not used.
NA
NA
6
Not used.
NA
NA
C200H-B7A02 Pin
Factory setting (all pins OFF)
Function
OFF
ON
1
Transmission delay
Standard (19.2 ms)
High-speed (3 ms)
2
Not used.
NA
NA
3
Not used.
NA
NA
4
Not used.
NA
NA
5
Not used.
NA
NA
6
Not used.
NA
NA
Transmission Delay Pin 1 is used to set the transmission delay. The same delay is used for all words allocated to the Unit.
160
Page 167
Specifications
Appendix B
Set the transmission delay to match that of the B7A Link Terminal. A transmission error will occur if the same transmission delay is not set. The “3ms” indicator will be lit whenever the high-speed (3 ms) transmission delay is set. Transmission Error Process Pin 2 is used to turned ON to specify resetting input status when transmission errors occur. If pin 2 is turned OFF, input status will be held when transmission errors occur. The LOAD OFF indicator will be lit whenever pin 2 is turned ON. Input Mode Pin 3 is turned ON to specify use of only 15 inputs and the use of bit 15 as a Transmission Error Flag. If pin 3 is OFF, 16 normal inputs can be used. The “15IN+ERR” indicator will be lit whenever pin 3 is turned ON. ERROR Indicators Pin 4 or pins 4 and 5 are turned ON to enable the ERROR, ERROR 1, and/or ERROR 2 indicators. These indicators will not light even if a transmission error occurs if the corresponding pin is turned OFF.
Transmission Error Precautions Startup The Transmission Error Flag for the B7A Interface Unit will be OFF when power is turned on to the C200H. If normal transmissions with the B7A Link Terminal are not possible within about 10 ms, the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). All input bits will remain OFF until normal transmissions are achieved. Inputs When a transmission error occurs, input status will be either held or all inputs will be reset according to the setting for the transmission error process, and the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). The Transmission Error Flag will go OFF and the input status will return to normal when normal transmissions are achieved again. Outputs Transmission errors for Output B7A Link Terminals are not detected at the B7A Interface Unit and must be confirmed using the error indicators or error outputs on the Link Terminal.
161
Page 168
Appendix B
Specifications
Wiring Terminal Names and Allocations The use of the terminals depends on the model of the B7A Interface Unit. “m” indicates the first word allocated to the Unit according to the I/O number setting and can be calculated as follows: m = 030 + (2 x I/O number) C200H-B7A22 Name
Function
B0 B1
Terminal
SIG OUT1 – OUT1
B2 B3
SIG OUT2 – OUT2
B4 B5
SIG IN1 – IN1
B6 B7
SIG IN2 – IN2
B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m m+1 m+2 m+3
NA
C200H-B7A21 Terminal
Name
Function
B0 B1
SIG OUT1 – OUT1
B2, B3
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.
B4 B5
SIG IN1 – IN1
B6 to B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m
NA m+1
NA
C200H-B7A12 Terminal
162
Name
Function
B0 B1
SIG IN1 – IN1
Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
B2, B3
NC
B4 B5
SIG IN2 – IN2
B6 to B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m
NA m+1
NA
Page 169
Appendix B
Specifications C200H-B7A02 Name
Function
B0 B1
Terminal
SIG OUT1 – OUT1
B2, B3
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.
B4 B5
SIG OUT2 – OUT2
B6 to B8 A0 to A7 B9 A8
NC
Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.
+V –V
Connect to + terminal on external power supply. Connect to – terminal on external power supply.
Word m
NA m+1
NA
Recommended Cables and Transmission Distance The following cables are recommended to connect the B7A Interface Unit to B7A Link Terminals. The wiring method and transmission distance depend on the transmission delay and on whether or not a common power supply is being used for the B7A Link Terminal and the Interface Unit. Standard Transmission Delays (19.2 ms): Cap-tire Cable Power supply
Cable
Transmission distance
Common
VCTF, 0.75 mm2 x 3 conductors
100 m max.
Separate
VCTF ,0.75 mm2 x 2 conductors
500 m max.
High-speed Transmission Delays (3 ms): Shielded Cable Power supply
Cable
Transmission distance
Common
Shielded cable, 0.75 mm2 x 3 conductors
50 m max.
Separate
Shielded cable, 0.75 mm2 x 2 conductors
100 m max.
Terminal Construction Use hook-type crimp connectors with a line thickness of 0.25 to 1.65 mm2. The construction of the terminals is shown in the illustration.
Wiring Method Standard Transmission Delays (19.2 ms) Common Power Supply B7A Link Terminal
B7A Interface Unit
Transmission distance: 100 m max. B7A Link Terminal
Transmission cable: VCTF 0.75 mm2 or higher 24 VDC±10%
163