SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide: Appendix, pages 160 to 169

Pages 160 to 169 of 186, from SYSMAC C200H Programmable Controllers (CPU21-E/23-E/31-E) Installation Guide

The original document is the PDF (1.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OD212 and Omron C200H-OD218

Page 160

Appendix B

Specifications ! Caution

Ensure that the external variable resistor connectors are open when using the internal variable resistor.

External variable resistor connector

External variable resistor

Standard B7A Interface Units (C200H-B7AI1/B7AO1) The B7A Interface Unit used with the B7A Link Terminal allows the transmission and reception of 16-point I/O data over two wires. The following B7A Interface Units and B7A Link Terminal models are available. B7A Interface Unit 16-point input: C200H-B7AI1 16-point output: C200H-B7AO1

B7A Link Terminals B7A-T6j1 (Screw terminal models) B7A-T6D2 (Modular models) B7A-R6jj1 (Screw terminal models) B7A-R6A52 (Modular models)

Mount the B7A Interface Unit (C200H-B7AO1) to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. Note 1. The B7A Interface Terminal can be connected only to 16-point B7A Link Terminals and then only if the Terminal has a standard transmission delay (i.e., 19.2 ms) 2. If the B7A Interface Unit is connected to the C200H-CPU23-E or C200H-PS211, supply 24 VDC from an independent power supply to the B7A Interface Unit or use a transformer to separate the power supply line to the B7A Interface Unit from the power supply lines to the CPU Unit and I/O Power Supply Unit.

I/O indicators ERR indicator

Connection terminals Connection terminals for the B7A Link Terminal: Connect this terminal to the SIG terminal of the B7A Link Terminal. Connect this terminal to the negative power terminal of the B7A Link Terminal. Supply 12 to 24 VDC. 12 to 24 VDC

I/O Indicators Indicate the ON or OFF status of inputs from the B7A Link Terminal or the ON and OFF status of outputs to the B7A Link Terminal.

154

Page 161

Appendix B

Specifications

ERR Indicator Incorporated by the B7AI1 and lit when the B7AI1’s data transmission or reception is abnormal. Connection Terminals SIG: Connects to the SIG terminal of the B7A Link Terminal. V–: Connects to the negative power terminal of the B7A Link Terminal. ! Caution

If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be damaged.

Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm2 minimum. 2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit. Input Mode Selector The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can be set. Input mode

15 points + 1 error (switch set up)

16 points (switch set down)

Function

Fifteen-point input from the B7A Link Terminal is effective. Bit 15 is used as transmission error bit.

Sixteen-point input from the B7A Link Terminal is effective.

Switch setting Bit no. allocation

Upper side

Lower side

00 to 14 15 Status of input indicator lamp 15 Status of the ERR indicator

Input 00 to input 14 Transmission error bit Not used

Input 00 to input 14 Input 15 Lit when input 15 is ON. Not lit when input 15 is OFF. Lit when there is a transmission error and OFF during normal transmission

The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next transmission cycle. When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the transmission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is transmitted in the first transmission cycle when the B7A Link Terminal is turned on again. Transmission errors between the C200H-B7AO1 and B7A Link Terminal are detected by the B7A Link Terminal only. Check the ERR indicator and error bit for any error. Performance Specifications Item I/O points

C200H-B7AI1

C200H-B7AO1

Transmission distance

16 points or 15 points and 1 error 16 output points input 500 m max. if power is supplied to the Interface Unit and B7A Link Terminal separately. 100 m max. if power is supplied to the Interface Unit and B7A Link Terminal from a single power supply. (24 VDC±10%)

Transmission delay

Typ. 19.2 ms, 31 ms max.

Minimum input time (see note 1)

---

Internal current consumption

5 VDC, 100 mA max.

External power supply (see note 2)

12 to 24 VDC ±10%, 10 mA min.

Weight

200 g max.

16 ms 12 to 24 VDC ±10%, 30 mA min.

Note 1. The minimum input time is the minimum time required to read input signals from the CPU Unit. The ON/ OFF width of signals from the CPU Unit to the output relays of the B7A Interface Unit must be at least equal to the minimum input time. 2. The capacity of the external power supply does not include the capacity required by the B7A Link Terminal.

155

Page 162

Appendix B

Specifications

Group-2 B7A Interface Units (C200H-B7Ajj) A Group-2 B7A Interface Unit used with two or four B7A Link Terminals allows the transmission and reception of 32-point or 64-point I/O data over two-conductor cables. Group-2 B7A Interface Unit

C200H C200HCPU21-E/22-E/23-E/31-E CPU Unit

Input B7A Link Terminal

Sensor Switch

Transmission distance: 500 m max.

Output B7A Link Terminal

Lamps and other loads

Group-2 B7A Interface Units can be mounted to a CPU Rack containing a C200H-CPU21-E/22-E/23-E/31-E CPU Unit or an I/O Expansion Rack for one of these CPU Units. They cannot be mounted to Slave Racks or to Racks controlled by any other CPU Units. The words allocated to Group-2 B7A Interface Units are determined by I/O number set on the Units. Units with 32 I/O points are allocated two words; Units with 64 I/O points are allocated four words. Refer to the B7A Link Terminals Datasheet for more information on B7A Link Terminals.

Models The following Group-2 B7A Interface Units are available. B7A Interface Unit

Inputs

Outputs

C200H-B7A12

32 points

None

C200H-B7A02

None

32 points

C200H-B7A21

16 points

16 points

C200H-B7A22

32 points

32 points

156

Page 163

Appendix B

Specifications

Connectable B7A Link Terminals Input Terminals Type Screw terminals

Modular PC connectors

Model B7A-T6j1 B7AS-T6j1 B7A-T6j6 B7AS-T6j6 B7A-T6D2 B7A-T6D7 B7A-TjE3 B7A-TjE8

Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)

Output Terminals Type Screw terminals

Modular PC connectors

Model B7A-R6jj1 B7AS-R6jj1 B7A-R6jj6 B7AS-R6jj6 B7A-R6A52 B7A-R6A57 B7A-RjAj3 B7A-RjAj8

Transmission delay Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms) Standard (19.2 ms) High-speed (3 ms)

Note 1. Do not connect Terminals with different transmission delays to the same Interface Unit. Doing so will cause a transmission error. 2. 10-point B7A Link Terminals and Mixed I/O (8 inputs/8 outputs) B7A Link Terminals cannot be connected to a B7A Interface Unit. 16-point B7A Link Terminals, 32-point B7A Link Terminals with a two-circuit configuration, and Mixed I/O B7A Link Terminals with a 16-point input/output configuration can be connected.

Comparison between Standard and Group-2 B7A Interface Units Type

Standard

Models

C200H-B7AI1 C200H-B7AO2

Group-2

C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22

CPU Unit

Word allocations

Any C200H CPU Unit

Same as I/O Units (in order mounted).

C200H-CPU21E/22-E/23-E/ 31-E CPU Unit only

Words 030 to 049 allocated according to I/O number setting (see note 3) (same as Group-2 High-density I/O Units)

Connectable B7A Link Terminals Transmission delay Standard types only (19.2 ms)

Transmission errors Input status held automatically

Standard (19.2 ms) and high-speed (3 ms) types (set via switch)

Switch setting to hold or reset Input status.

Points (see note 2) 16-point Terminals only (10-point, 32-point, and mixed I/O Terminals cannot be connected.

Note 1. Mount the B7A Interface Unit (C200H-B7AO1) to the C200H-BCjj1-V1 or C200H-BCjj1-V2 Backplane. 2. 10-point B7A Link Terminals and Mixed I/O B7A Link Terminals with an 8 input-8 output configuration cannot be connected to a B7A Interface Unit. 16-point B7A Link Terminals, 32-point B7A Link Terminals with a two-circuit configuration, and Mixed I/O B7A Link Terminals with a 16-point input or output configuration can be connected. 3. Words IR 030 to IR 049 (Group-2 High-density I/O Unit and B7A Interface Unit Area) are allocated to the inputs/outputs of Group-2 B7A Interface Units according to the setting of the I/O number switch on the front of the Unit, in the way shown in the following table (for Mixed I/O Units, words are allocated in the order output → input for each Unit).

157

Page 164

Appendix B

Specifications Unit

Models

32 inputs

C200H-B7A12

32 outputs

C200H-B7A02

16 outputs, 16 inputs

C200H-B7A21

32 outputs, 32 inputs

C200H-B7A22

Words allocated per Unit 2

4

Allocation order 2 words allocated to inputs 2 words allocated to outputs 1 word allocated to outputs → 1 word allocated to inputs 2 words allocated to outputs → 2 words allocated to inputs

Words allocated when I/O number = 0 IR 030: input IR 030: output IR 030: output IR 031: input IR 030: output IR 031: output IR 032: input IR 033: input

Parts and Names (C200H-B7A22 shown below) Front

I/O number switch This switch determines the words allocated to the Unit. Status indicators The indicators depend on the model of B7A Interface Unit.

Connection terminals Connect to the SIG terminal of the B7A Link Terminal and to the negative power terminal of the B7A Link Terminal. The actual use of these terminals depends on the B7A Interface Unit.

External Power Supply Terminals Supply 12 to 24 VDC.

12 VDC 12toto2424 VDC

158

Page 165

Appendix B

Specifications Back

DIP switch Used to set the transmission delay, transmission error processing mode, input mode, and ERROR indicator operation.

Indicator Operation The indicators depend on the model of B7A Interface Unit, as shown below.

Name

Color

Function

ERROR 1 ERROR 2 ERROR

Input transmission error

Red

Lights when an error occurs in transmissions from an Input B7A Link Terminal. For the B7A12/22, ERROR 1 is for the first word allocated to the B7A Interface Unit; ERROR 2 is for the second word.

3ms

Transmission delay setting

Orange

Lit when the transmission delay is set to the high-speed setting (3 ms).

LOAD OFF

Transmission error process

Orange

15IN+ERR

Input mode setting

Orange

Not lit when the transmission delay is set to the standard setting (19.2 ms). Lit when the processing for transmission errors is set to reset input status. Not lit when the processing for transmission errors is set to hold input status. Lit when the input mode mode is set to use 15 inputs and 1 error input. Not lit when the input mode mode is set to use 16 inputs.

I/O Number Setting The setting of the I/O number determines the words allocated to the Interface Unit. Set the I/O number to between 0 and 9.

Setting in direction of notch

Note 1. Turn off the power supply to the PC before changing the I/O number setting. Any new setting will not be effective until the next time the power supply is turned on.

159

Page 166

Appendix B

Specifications

2. Use a flat-blade screw driver to change the I/O number setting. Be careful not to leave the switch halfway between settings and be careful not to damage the switch. The following table shows the words allocated according to the I/O number. The 32-point Units are the C200H-B7A12, C200H-B7A02, and C200H-B7A21. The 64-point Unit is the C200H-B7A22. Words

I/O No. 0

32-point Units IR 030 and IR 031

64-point Unit IR 030 to IR 033

1

IR 032 and IR 033

IR 032 to IR 035

2

IR 034 and IR 035

IR 034 to IR 037

3

IR 036 and IR 037

IR 036 to IR 039

4

IR 038 and IR 039

IR 038 to IR 041

5

IR 040 and IR 041

IR 040 to IR 043

6

IR 042 and IR 043

IR 042 to IR 045

7

IR 044 and IR 045

IR 044 to IR 047

8

IR 046 and IR 047

IR 046 to IR 049

9

IR 048 and IR 049

Do not use.

Note 1. Be sure that the same words are not allocated to more than one Unit. For example, if you set a 64-point Unit to I/O number 0, you cannot use I/O number 1 for any Unit. 2. The above words are also allocated to Group-2 High-density I/O Units. Be sure that the same words are not allocated to more than one Unit.

DIP Switch Settings Set the DIP switch as described before for the various models of B7A Interface Units. C200H-B7A22/12 Pin

Factory setting (pins 4 and 5 ON)

Function

OFF

ON

1

Transmission delay

Standard (19.2 ms)

High-speed (3 ms)

2

Transmission error process

Hold status

Reset Inputs

3

Input mode

16 inputs

15 inputs + error input

4

ERROR 1 indicator enable

Disabled

Enabled

5

ERROR 2 indicator enable

Disabled

Enabled

6

Not used.

NA

NA

C200H-B7A21 Pin

Factory setting (pin 5 ON)

Function

OFF

ON

1

Transmission delay

Standard (19.2 ms)

High-speed (3 ms)

2

Transmission error process

Hold status

Reset Inputs

3

Input mode

16 inputs

15 inputs + error input

4

ERROR indicator enable

Disabled

Enabled

5

Not used.

NA

NA

6

Not used.

NA

NA

C200H-B7A02 Pin

Factory setting (all pins OFF)

Function

OFF

ON

1

Transmission delay

Standard (19.2 ms)

High-speed (3 ms)

2

Not used.

NA

NA

3

Not used.

NA

NA

4

Not used.

NA

NA

5

Not used.

NA

NA

6

Not used.

NA

NA

Transmission Delay Pin 1 is used to set the transmission delay. The same delay is used for all words allocated to the Unit.

160

Page 167

Specifications

Appendix B

Set the transmission delay to match that of the B7A Link Terminal. A transmission error will occur if the same transmission delay is not set. The “3ms” indicator will be lit whenever the high-speed (3 ms) transmission delay is set. Transmission Error Process Pin 2 is used to turned ON to specify resetting input status when transmission errors occur. If pin 2 is turned OFF, input status will be held when transmission errors occur. The LOAD OFF indicator will be lit whenever pin 2 is turned ON. Input Mode Pin 3 is turned ON to specify use of only 15 inputs and the use of bit 15 as a Transmission Error Flag. If pin 3 is OFF, 16 normal inputs can be used. The “15IN+ERR” indicator will be lit whenever pin 3 is turned ON. ERROR Indicators Pin 4 or pins 4 and 5 are turned ON to enable the ERROR, ERROR 1, and/or ERROR 2 indicators. These indicators will not light even if a transmission error occurs if the corresponding pin is turned OFF.

Transmission Error Precautions Startup The Transmission Error Flag for the B7A Interface Unit will be OFF when power is turned on to the C200H. If normal transmissions with the B7A Link Terminal are not possible within about 10 ms, the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). All input bits will remain OFF until normal transmissions are achieved. Inputs When a transmission error occurs, input status will be either held or all inputs will be reset according to the setting for the transmission error process, and the Transmission Error Flag (bit 15) will turn ON (i.e., if its operation is enabled by the input mode setting). The Transmission Error Flag will go OFF and the input status will return to normal when normal transmissions are achieved again. Outputs Transmission errors for Output B7A Link Terminals are not detected at the B7A Interface Unit and must be confirmed using the error indicators or error outputs on the Link Terminal.

161

Page 168

Appendix B

Specifications

Wiring Terminal Names and Allocations The use of the terminals depends on the model of the B7A Interface Unit. “m” indicates the first word allocated to the Unit according to the I/O number setting and can be calculated as follows: m = 030 + (2 x I/O number) C200H-B7A22 Name

Function

B0 B1

Terminal

SIG OUT1 – OUT1

B2 B3

SIG OUT2 – OUT2

B4 B5

SIG IN1 – IN1

B6 B7

SIG IN2 – IN2

B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m m+1 m+2 m+3

NA

C200H-B7A21 Terminal

Name

Function

B0 B1

SIG OUT1 – OUT1

B2, B3

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.

B4 B5

SIG IN1 – IN1

B6 to B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m

NA m+1

NA

C200H-B7A12 Terminal

162

Name

Function

B0 B1

SIG IN1 – IN1

Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

B2, B3

NC

B4 B5

SIG IN2 – IN2

B6 to B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Input B7A Link Terminal. Connect to – power supply terminal on Input B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m

NA m+1

NA

Page 169

Appendix B

Specifications C200H-B7A02 Name

Function

B0 B1

Terminal

SIG OUT1 – OUT1

B2, B3

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.

B4 B5

SIG OUT2 – OUT2

B6 to B8 A0 to A7 B9 A8

NC

Connect to SIG terminal on Output B7A Link Terminal. Connect to – power supply terminal on Output B7A Link Terminal. Not used.

+V –V

Connect to + terminal on external power supply. Connect to – terminal on external power supply.

Word m

NA m+1

NA

Recommended Cables and Transmission Distance The following cables are recommended to connect the B7A Interface Unit to B7A Link Terminals. The wiring method and transmission distance depend on the transmission delay and on whether or not a common power supply is being used for the B7A Link Terminal and the Interface Unit. Standard Transmission Delays (19.2 ms): Cap-tire Cable Power supply

Cable

Transmission distance

Common

VCTF, 0.75 mm2 x 3 conductors

100 m max.

Separate

VCTF ,0.75 mm2 x 2 conductors

500 m max.

High-speed Transmission Delays (3 ms): Shielded Cable Power supply

Cable

Transmission distance

Common

Shielded cable, 0.75 mm2 x 3 conductors

50 m max.

Separate

Shielded cable, 0.75 mm2 x 2 conductors

100 m max.

Terminal Construction Use hook-type crimp connectors with a line thickness of 0.25 to 1.65 mm2. The construction of the terminals is shown in the illustration.

Wiring Method Standard Transmission Delays (19.2 ms) Common Power Supply B7A Link Terminal

B7A Interface Unit

Transmission distance: 100 m max. B7A Link Terminal

Transmission cable: VCTF 0.75 mm2 or higher 24 VDC±10%

163