Page 84
Section 5-10
Data Link Characteristics Case 3
The following diagram illustrates the data flow that will produce the maximum data link I/O response time when the cycle time of the PC at node #1 t the communications cycle time and the cycle time of the PC at node #7 y the communications cycle time.
Input
I/O refresh Input device Data exchange
Input ON delay
X
1 cycle
(1) Program
PC at node #1
A
X
(2)
SYSMAC LINK Unit transmission processing Data link transmission
Communications cycle time
(3) X
SYSMAC LINK Unit transmission processing
Previous communications cycle data
X
(4) Program
PC at node #7 1 cycle
Output device Data link I/O response time
Output ON delay Output
There are three points shown in the diagram above where processing is delayed, increasing the data link I/O response time.
70
1, 2, 3...
1. The input arrives in the PC just after I/O refreshing, causing a delay of up to one cycle before the input is read into the PC. 2. At point A, data from the previous exchange is still being transferred, so new data cannot be exchanged, causing a delay of one communications cycle time. Furthermore, the data exchange then occurs just after the PC at node #1 passes the token for the polling unit, causing another delay of one communications cycle time before the data is transferred in data link processing. 3. At node #7, data from the previous data exchange is still being transferred, causing a delay of up to one cycle before the input is read into the PC. 4. The data transferred in data link processing arrives at the PC at node #7 after data exchange, so the data will not be read into the PC until the next data exchange, causing a delay of up to one cycle. Up to 1,642 words can be transferred in a single data exchange, so a delay of another cycle will occur if more than 1,642 words are being transferred. The equation for maximum data link I/O response time is as follows: Response time = input ON delay (1.5 ms) + cycle time of PC at node #1 (15 ms) × 2 + communications cycle time (19 ms) × 3 + PC cycle time at node #7 (50 ms) × 3* + output ON delay (15 ms) = 253.5 ms*
Note
1. *If more than 1,642 words are being transferred, 4 cycles of the PC at node #7 are required and the total response time becomes 303.5 ms. 2. Noise may increase I/O delays.
Page 85
Section 5-10
Data Link Characteristics Case 4
The following diagram illustrates the data flow that will produce the maximum data link I/O response time when the cycle time of the PC at node #1 t the communications cycle time and the cycle time of the PC at node #7 t the communications cycle time.
Input I/O refresh Input device Data exchange
Input ON delay
X
1 cycle
(1) Program
PC at node #1
A
X
(2)
SYSMAC LINK Unit transmission processing Data link transmission SYSMAC LINK Unit transmission processing
Communications cycle time
(3)
X Program
PC at node #7 1 cycle
Output device Output ON delay Data link I/O response time
Output
There are three points shown in the diagram above where processing is delayed, increasing the data link I/O response time.
1, 2, 3...
1. The input arrives in the PC just after I/O refreshing, causing a delay of up to one cycle before the input is read into the PC. 2. At point A data from the previous data exchange is still being transferred, so the new data cannot be exchanged, causing a delay of up to one communications cycle time. Furthermore, the data exchange then occurs just after the PC at node #1 passes the token that makes it the polling unit, causing another delay of up to one communications cycle time before the data is transferred in data link processing. 3. The data transferred in data link processing arrives at the PC at node #7 while data exchange is taking place, so the data will not be read into the PC until the next data exchange, causing a delay of up to one cycle. Up to 1,642 words can be transferred in a single data exchange, so a delay of another cycle will occur if more than 1,642 words are being transferred. The equation for maximum data link I/O response time is as follows: Response time = input ON delay (1.5 ms) + cycle time of PC at node #1 (15 ms) × 2 + communications cycle time (19 ms) × 3 + PC cycle time at node #7 (15 ms) × 2* + output ON delay (15 ms) = 133.5 ms*
Note
1. *If more than 1,642 words are being transferred, 3 cycles of the PC at node #7 are required and the total response time becomes 148.5 ms. 2. Noise may increase I/O delays.
71
Page 86
Page 87
SECTION 6 Data Read/Write Services The data read/write services include the SEND(90) and RECV(98) instructions and CV-mode commands. SYSMAC LINK Units can receive but not transmit CV-mode commands. The data read/write services allow data transmission between nodes and distributed control. 6-1 6-2
6-3
6-4
6-5
6-6
About Data Read/Write Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NETWORK READ/WRITE Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-1 Specifying Destination Nodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-2 Instruction Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-3 NETWORK WRITE - SEND(90) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-4 NETWORK READ - RECV(98) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-5 Response Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-6 Network Instruction Status Flags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-7 Delay Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CV-mode Command/Response Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-1 List of CV-mode Commands for PCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-2 List of CV-mode Commands for SYSMAC LINK Units . . . . . . . . . . . . . . . . . . . 6-3-3 CV-mode Response Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Memory Area Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-1 Word/Bit Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-2 Memory Area Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4-3 Data Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CV-mode Commands for PCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-1 MEMORY AREA READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-2 MEMORY AREA WRITE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-3 MULTIPLE MEMORY AREA READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-4 PARAMETER AREA WRITE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-5 PROGRAM AREA READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-6 PROGRAM AREA WRITE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-7 RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-8 STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-9 CONTROLLER DATA READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-10 CONTROLLER STATUS READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-11 CLOCK READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-12 CLOCK WRITE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-13 ERROR CLEAR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-14 FILE MEMORY INDEX READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-15 FILE MEMORY BLOCK READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-16 FILE MEMORY BLOCK WRITE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-17 FORCED SET/RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-18 FORCED SET/RESET CANCEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5-19 FORCED STATUS READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CV-mode Commands for SYSMAC LINK Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-1 DATA LINK START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-2 DATA LINK HALT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-3 RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-4 CONTROLLER DATA READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-5 CONTROLLER STATUS READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-6 NETWORK STATUS READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-7 DATA LINK STATUS READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-8 INTERNODE ECHO TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-9 BROADCAST TEST RESULTS READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6-10 BROADCAST TEST DATA SEND . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
74 74 74 75 76 77 79 80 84 86 87 87 88 88 89 89 89 90 90 90 91 92 92 93 94 94 95 95 97 97 98 98 99 100 101 102 102 103 103 103 104 104 105 107 108 109 110 110
73
Page 88
Section 6-2
NETWORK READ/WRITE Instructions
6-1
About Data Read/Write Services In addition to SEND(90) and RECV(98) instructions, a C-series PC equipped with a SYSMAC LINK Unit* can receive but not issue CV-mode commands. With these data read/write services, data can be transmitted between PCs and CVSS or CV-series PCs in the network and operation at other nodes can be controlled remotely. The data read/write services use a command/response format. Each time that data or a command from a CVSS or CV-series PC is transmitted, the receiving node returns a response. If responses aren’t needed, the Unit can be set so that responses are not returned. The same transmission can be broadcast simultaneously to all nodes on the network. Note *The SYSMAC LINK Units covered in this manual can receive and process the CV-mode commands issued from a computer or CV-series PC, but the C200H-SLK21 and C1000H-SLK21 SYSMAC LINK Units cannot receive CVmode commands.
Data Read/Write Service Transmissions The data read/write services with the SYSMAC LINK Unit are primarily used in the 4 situations described below. Computer Transmission
Prepare a program in the computer that transmits commands and receives responses. Should the SYSMAC LINK Support Board be used, make sure that the proper drivers and files are installed. (When programming in the C code, transmit commands with slksend and receive responses with slkrecv or slkrcvw.)
PC Transmission
Transfer data using the SEND(90) and RECV(98) instructions. You may need to move data being transferred to/from the location in memory specified in the instruction, but the actual transmission and reception is handled automatically. (No commands can be transmitted other than SEND(90) and RECV(98).)
Computer Reception
A program that returns proper responses for received commands must be prepared in the computer prior to command reception.
PC Reception
The SYSMAC LINK Unit receives and processes SEND(90), RECV(98), and CV-mode commands and returns the proper responses automatically. Since all of the processing is handled automatically, it isn’t necessary to prepare a routine for command reception in the PC program.
6-2
NETWORK READ/WRITE Instructions Data is sent from the PC to other nodes (PCs or computers) using the NETWORK READ/WRITE instructions (SEND(90) or RECV(98)) in the PC user program.
6-2-1 Specifying Destination Nodes The following two types of communications, based on specifying destination nodes, are possible. Sending and Receiving Data Between Specific Nodes
The SEND(90) and RECV(98) instructions can be used to transfer control data to or from a node specified by node address. Send data
Receive data Node 1
74
Node 2
Node 3
Node 4
Node 5
Page 89
Section 6-2
NETWORK READ/WRITE Instructions Broadcasting Data
It is possible to transfer the same data to all nodes in a network simultaneously by designating the destination node as 00. This transmission is called broadcasting. No responses are returned to broadcasts. (Broadcasting cannot be performed with the RECV(98) instruction.) Broadcast data
Node 1
Node 2
Node 3
Node 4
Node 5
Note With C200HX/HG/HE PCs, two Communications Units can be connected but the bridge function and gateway function cannot be used. C200HX/HG/HE
CS, CVM1/CV
6-2-2 Instruction Specifications The NETWORK READ/WRITE instructions (SEND(90)/RECV(98)) enable data to be sent and received between nodes within a single network under control of a user program. The user can specify that a receiving node send a response to the sending node to acknowledge receipt of the data. The basic specifications of these instructions are given in the following table. Transmission format Packet length Data content
Response time-out parameters
Number of retries
Data Transfer Area
1:1 data transfer 1:N data transmit only (broadcast mode; no response) 256 words max. (within the same memory area only) When SEND(90) is executed, command/response data for a data transmission request is transferred. When RECV(98) is executed, command/response data for a data reception request is transferred. 00: 2 seconds FF: Response time-out ignored. 01 to FE: user-definable (in increments of 100 ms, 100 to 25,400 ms) 0 to 15
The data transfer area, which is used for data transmission and reception using the SEND and RECV instructions, varies with the PC.
Area
C200HX/HG/HE
C200HS
IR and SR
000 to 511 (SEND) 000 to 252, 256 to 511 (RECV)
000 to 511 (SEND) 000 to 252, 256 to 511 (RECV)
LR
00 to 63
HR AR
C200H
C1000H
C2000H
000 to 255 (SEND) 000 to 252 (RECV)
000 to 255 (SEND) 000 to 252 (RECV)
000 to 255 (SEND) 000 to 252 (RECV)
00 to 63
00 to 63
00 to 63
00 to 63
00 to 99
00 to 99
00 to 99
00 to 99
00 to 99
00 to 27
00 to 27
00 to 27
00 to 27
00 to 27
T/C
000 to 511
000 to 511
000 to 511
000 to 511
000 to 511
DM
0000 to 6655
0000 to 6655
0000 to 1999 (SEND) 0000 to 0999 (RECV)
0000 to 4095
0000 to 6655
EM
0000 to 6143
None
Unit: word
75
Page 90
Section 6-2
NETWORK READ/WRITE Instructions Note The data transfer area must not exceed the above ranges.
6-2-3 NETWORK WRITE - SEND(90) The ladder diagram programming symbols, operand names, and allowable data areas for SEND(90) are shown below. Operand Data Areas
Ladder Symbols
S: Source beginning word SEND(90)
@SEND(90)
S
S
D
D
C
C
IR, SR, AR, DM, HR, TC, LR D: Destination beginning word IR, AR, DM, HR, TC, LR C: First control data word IR, AR, DM, HR, TC, LR
Limitations
C through C+2 must be within the same data area and must be within the values specified below. The first and last source word must be within the same data area.
Description
When executed with an ON execution condition, SEND(90) transfers data beginning at word S, to addresses specified by D in the designated node on the SYSMAC LINK System. The control words, beginning with C, specify the number of words to be sent, the destination node, and other parameters. Bit 15 of C+1 determines whether the instruction is for a SYSMAC NET Link System or a SYSMAC LINK System.
Control Data
Set the destination node number to 00 to broadcast the data to all nodes in the network. Word
Bits 00 to 07
C
Number of words (0 to 256 in 4-digit hexadecimal, i.e., 0000hex to 0100hex)
C+1
Response time limit (0.1 and 25.4 seconds in 2-digit hexadecimal without decimal point, i.e., 00hex to FFhex) Note: The response time will be 2 seconds if the limit is set to 0hex. There will be no time limit if the time limit is set to FFhex.
C+2
Note
Bits 08 to 15
Destination node number (1 to 62 in 2-digit hexadecimal, i.e., 01hex to 3Ehex)2
Bits 08 to 11: No. of retries (0 to 15 in hexadecimal, i.e., 0hex to Fhex) Bit 12: Indirectly addressed beginning reception flag ON: Indirect addressing OFF: No indirect addressing Bit 13 ON: Response not returned. OFF: Response returned.1 Bit 14 ON: Operating level 0 OFF: Operating level 1 Bit 15: Set to 1. (SYSMAC LINK flag) Bits 08 to 12: Destination node unit number (0 to 4)3 Bits 13 to 15: Set to 0.
1. If the instruction is set for broadcast transmission, no response will be returned even if bit 13 is OFF. 2. The node number of the PC executing the send cannot be set. 3. Set the destination node unit number to 00 when sending data to a PC. Settings 01 to 04 specify computer applications 1 to 4.
76
Page 91
Section 6-2
NETWORK READ/WRITE Instructions
4. Indirectly Addressed Beginning Reception Flag: The CV-series PC has a larger data area than the C-series PC. Therefore, the beginning reception word of the destination node cannot be always designated by the operand of the SEND(90). If the beginning reception word cannot be designated, set the indirectly addressed beginning reception flag to 1 (ON: indirect addressing), in which case the second operand (D) will be the indirect beginning reception word, and it will be possible to designate the beginning reception word (rightmost word) of the destination node in BCD with the word designated by the second operand (D). Bit
15
14
12
11
10
9
8
Data area code
D+0 D+1
13
Word no. (fourth digit)
Word no. (third digit)
7
6
5
4
3
0
0
0
0
Word no. (fifth digit)
2
1
0
Word no. (second digit)
Word no. (first digit)
This operation is possible with a C200HW-SLK13/14/23/24 SYSMAC LINK Unit mounted in a C200HX, C200HG, C200HE, C200HS, or C200H PC only. Refer to the following table to designate the data area. Destination node (C-series PC) Area
Destination node (CV-series PC)
I/O (IR)
Data area code 00
Area Core I/O (CIO)
Data area code 00
Link Relay (LR)
06
CPU Bus Link (G)
01
Holding Relay (HR)
07
Auxiliary (A)
02
Auxiliary Relay (AR)
08
Timer (T)
03
Timer/Counter (T/C)
03
Counter (C)
04
Data Memory (DM)
05
Data Memory (D) Extended Banks 0 to 7 Data Current bank Memory (E)
05 10 to 17 18
6-2-4 NETWORK READ - RECV(98) The ladder diagram programming symbols, operand names, and allowable data areas for RECV(98) are shown below. Operand Data Areas
Ladder Symbols
S: Source beginning word RECV(98)
@RECV(98)
S
S
D
D
C
C
IR, SR, AR, DM, HR, TC, LR D: Destination beginning word IR, AR, DM, HR, TC, LR C: First control data word IR, AR, DM, HR, TC, LR
Limitations
C through C+2 must be within the same data area and must be within the values specified below.
Description
When executed with an ON execution condition, RECV(88) transfers data beginning at S from a node on the SYSMAC LINK System to words beginning at D. The control words, beginning with C, provide the number of words to be received, the source node, and other transfer parameters.
77
Page 92
Section 6-2
NETWORK READ/WRITE Instructions
Bit 15 of C+1 determines whether the instruction is for a SYSMAC NET Link System or a SYSMAC LINK System. Word
Bits 08 to 15
C
Number of words (0 to 256 in 4-digit hexadecimal, i.e., 0000hex to 0100hex)
C+1
Response time limit (0.1 and 25.4 seconds in 2-digit hexadecimal without decimal point, i.e., 00hex to FFhex)
C+2
Note
Bits 00 to 07
Note: The response time will be 2 seconds if the limit is set to 0hex. There will be no time limit if the time limit is set to FFhex.
Bits 08 to 11: No. of retries (0 to 15 in hexadecimal, i.e., 0hex to Fhex) Bit 12: Indirectly addressed beginning destination flag ON: Indirect addressing OFF: No indirect addressing Bit 13: Set to 0. Bit 14 ON: Operating level 0 OFF: Operating level 1 Bit 15: Set to 1. (SYSMAC LINK flag)
Source node number (1 to 62 in 2-digit hexadecimal, i.e., 01hex to 3Ehex)1
Bits 08 to 11: Source node unit number (0 to 4)2 Bits 13 to 15: Set to 0.
1. The node number of the PC executing RECV(98) cannot be set. 2. Set the source node unit number to 00 when sending data to a PC. Settings 01 to 04 specify computer applications 1 to 4. 3. Indirectly Addressed Beginning Destination Flag: The CV-series PC has a larger data area than the C-series PC. Therefore, the beginning destination word of the destination node cannot be always designated by the operand of the RECV instruction. If the beginning destination word cannot be designated, set the indirectly addressed beginning destination flag to 1 (ON: indirect addressing), in which case the first operand (S) will be the indirect beginning destination word, and it will be possible to designate the beginning destination word (rightmost word) of the destination node in BCD with the word designated by the first operand (S). Bit
15
14
S+0 S+1
13
12
11
10
9
8
Data area code Word no. (fourth digit)
Word no. (third digit)
7
6
5
4
3
0
0
0
0
Word no. (fifth digit)
2
1
0
Word no. (second digit)
Word no. (first digit)
This operation is possible with a C200HW-SLK13/14/23/24 SYSMAC LINK Unit mounted in a C200HX, C200HG, C200HE, C200HS, or C200H PC only. Refer to the following table to designate the data area. Destination node (C-series PC) Area
78
Destination node (CV-series PC)
I/O (IR)
Data area code 00
Area Core I/O (CIO)
Data area code 00
Link Relay (LR)
06
CPU Bus Link (G)
01
Holding Relay (HR)
07
Auxiliary (A)
02
Auxiliary Relay (AR)
08
Timer (T)
03
Timer/Counter (T/C)
03
Counter (C)
04
Data Memory (DM)
05
Data Memory (D) Extended Banks 0 to 7 Data Current bank Memory (E)
05 10 to 17 18
Page 93
Section 6-2
NETWORK READ/WRITE Instructions
6-2-5 Response Codes When SEND(90) or RECV(98) is used in a SYSMAC LINK System, a response code is returned to indicate that the data transfer was completed successfully or identify the nature of the error when communications are not completed successfully. The most recent response code will be retained until another SEND(90) or RECV(98) instruction is executed. The output bits and the error codes are as follows: PC C200HX, C200HG, C200HE, C200HS, C200H C1000H/C2000H Response code
Name
Bits1
Operating level Level 0 Level 1 Levels 0 and 12
SR 23700 to SR 23707 SR 23708 to SR 23715 SR 23700 to SR 23707
Meaning
00
Normal end3
Data transfer was completed successfully.
01
Parameter error
SEND(90)/RECV(98) instruction operands are not within specified ranges.
02
Transmission impossible
The System was reset during execution of the instruction or the destination node is not in the System.
03
Destination not in System
The destination node is not in the System.
04
Busy error
The destination node is busy and cannot receive the transfer.
05
Response timeout
A response was not received within the time limit.
06
Response error
The response received from the destination node was incorrect.
07
Communications controller An error occurred in the communications controller. error
08
Setting error
The node number was set incorrectly.
09
CPU Unit error
A CPU Unit error occurred in the PC of the destination node.
Note
1. The response codes listed here occupy only one byte, unlike the command/ response response codes which occupy two bytes. 2. Only the most recent response code, from either level, is retained. 3. The response code will also be 00 while the instruction is being executed.
79