The text of a manual · part 11 of 19
C-series SYSMAC LINK System Manual, pages 94 to 103
Pages 94 to 103 of 174
The original document is the PDF (983 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200HW-SLK24
Page 94
Section 6-2
NETWORK READ/WRITE Instructions
6-2-6 Network Instruction Status Flags SEND(90) and RECV(98) are based on command/response processing. That is, the transmission is not complete until the sending node receives and acknowledges a response from the destination node. Operation without a response is also possible for SEND(90), if desired. The SEND(90)/RECV(98) Enable Flag is not turned ON until the first END(01) after the transmission is completed. If multiple SEND(90)/RECV(98) operations are used, the following flags must be used to ensure that any previous operation is completed before attempting another. Because the C200H/C200HS provides separate flags for each operating level, it is possible to control these independently and have operations going on in both levels simultaneously. With the C1000H/C2000H, only one SEND(90)/RECV(98) operation should be performed in the network at a time, regardless of the number of operating levels. C200HX/C200HG/C200HE/ C200HS/C200H Enable Flag Level 0: SR 25201 Level 1: SR 25204 Error Flag Level 0: SR 25200 Level 1: SR 25203
C1000H/C2000H
Functions
Enable Flag All levels SR 25204
OFF during SEND(90)/RECV(98) execution (including command response processing). Do not start a SEND(90)/RECV(98) operation unless this flag is ON.
Error Flag All levels: SR 25203
OFF following normal completion of SEND/RECV (i.e., after reception of response signal) ON after an unsuccessful SEND(90)/RECV(98) attempt. Error status is maintained until the next SEND(90)/RECV(98) operation. Error types: Time-out error (command/response time greater than 1 second) Transmission data errors
Timing
The following diagram shows the status of the Enable Flag, Error Flag, and response code while two network instructions are issued in the C1000H PC. An error occurs during execution of first instruction. 1
Enable Flag
0 1
Error Flag
0 Response code
Previous response code
00
Instruction #1 received
Instruction #1 00 response code
Instruction #1 completed
Instruction #2 received
Instruction #2 response code
Instruction #2 completed
Data Processing for SEND(90)/RECV(98)
Data is transmitted for SEND(90) and RECV(98) for the C1000H/C2000H when SEND(90)/RECV(98) is executed and for the C200H/C200Hj when END(01) is executed. Final processing for transmissions/receptions is performed when END(01) is executed for all PCs.
Programming Example: Multiple SEND(90)/RECV(98)
To ensure successful SEND(90)/RECV(98) operations, the program must use the SEND(90)/RECV(98) Enable Flag and SEND(90)/RECV(98) Error Flags to confirm that execution is possible. The following program shows one way to do this:
80
Page 95
Section 6-2
NETWORK READ/WRITE Instructions 00000
25204
12802 S
KEEP(11) 12800
(Enable Flag) 12801
12800 prevents execution of SEND(90) until RECV(98) (below) is completed. IR 00000 is turned ON to start transmission.
R
12800
@MOV(21) #000A DM 0000 @MOV(21)
Data is placed into control data words to specify the 10 words to be transmitted to node 3 in operating level 0.
#8000 DM 0001 @MOV(21)
DM 000 DM 001 DM 002
00 80 00
0A 00 03
10 words Node 3 (a PC)
#0003 DM 0002 XFER(70) #0010
Transfers the 10 words beginning at IR 000 to the 10 words beginning at DM 0010.
000 DM 0010 @SEND(90) DM 0010 DM 0020 DM 0000 12800
25204 DIFU(13)
12800
25203
12801
SEND(90)/RECV(98) Error Flag 00200
00001
25204
12800 S
KEEP(11) 12802
Turns ON to indicate transmission error. 12802 prevents execution of RECV(98) when SEND(90) above has not completed. IR 00001 is turned ON to start transmission.
12803 R 12802 @MOV(21) #0010 DM 0003 @MOV(21) #8000
Data moved into control data words to specify the 16 words to be transmitted from node 4 in operating level 0.
DM 0004 @MOV(21) #0004 DM 0005
DM 003 DM 004 DM 005
00 80 00
10 00 04
16 words Node 4 (a PC)
@RECV(98) HR 10 LR 10 DM 0003 12802
25204 DIFU(13)
12802
12802
25203
25204
12801
SEND(90)/RECV(98) Error Flag 00201
Turns ON to indicate reception error.
#0016
Transmitted data moved into words beginning at DM 0030 for storage.
12800 XFER(70)
LR 10 DM 0030
81
Page 96
Section 6-2
NETWORK READ/WRITE Instructions Indirect Addressing of Beginning Words for C200H/C200Hj PCs 00000
25204
12802 S
KEEP(11) 12800
(Enable Flag) 12801 R
12800
The transmission program is started when IR 00000 goes ON, provided that the SEND(90)/RECV(98) Enable Flag is ON (indicating RECV(98) isn’t being executed). IR 12800 is ON while SEND(90) is being executed.
@MOV(21) #000A DM 0000
Data is placed into control data words to specify the 10 words to be transmitted to node 3 in operating level 0.
@MOV(21) #8000 DM 0001
DM 000 DM 001 DM 002
00 80 00
0A 00 03
10 words Node 3 (a PC)
@MOV(21) #0003 DM 0002 @MOV(21) #0500
Indirectly addressed beginning destination word. Beginning destination word in destination node = DM 4000.
DM 0020 @MOV(21) #4000
DM 020 DM 021
05 40
00 00
DM 0021 XFER(70) #0010
Transfers the 10 words beginning at IR 000 to the 10 words beginning at DM 0010.
000 DM 0010 @SEND(90) DM 0010 DM 0020 DM 0000 12800
25204 DIFU(13)
12800
25203
12801
SEND(90)/RECV(98) Error Flag 00200
00001
25204
12800 S
KEEP(11) 12802
12803 R
(Continued on the next page)
82
Turns ON to indicate transmission error. 12802 prevents execution of RECV(98) when SEND(90) above has not completed. IR 00001 is turned ON to start transmission.
Page 97
Section 6-2
NETWORK READ/WRITE Instructions (Continued from previous page) 12802 @MOV(21) #0010
Data moved into control data words to specify the 16 words to be transmitted from node 4 in operating level 0.
DM 0003 @MOV(21) #8000 DM 0004
DM 003 DM 004 DM 005
00 80 00
10 00 04
16 words Node 4 (a PC)
@MOV(21) #0004 DM 0005 @MOV(21) #0500
Indirectly addressed beginning destination word. Beginning destination word in destination node = DM 5000.
HR 10
HR 10 HR 11
@MOV(21)
05 50
00 00
#5000 HR 11 @RECV(98) HR 10 LR 10 DM 0003 12802
25204 DIFU(13)
12802
12802
25203
25204
12801
SEND(90)/RECV(98) Error Flag 00201
Turns ON to indicate reception error.
#0016
Transmitted data moved into words beginning at DM 0030 for storage.
12800 XFER(70)
LR 10 DM 0030
83
Page 98
Section 6-2
NETWORK READ/WRITE Instructions
6-2-7 Delay Times The two charts which follow indicate the sequence of processing which will enable users to calculate the maximum delay time to be expected between the time SEND(90) or RECV(98) is executed and the time the data is stored in the remote or local node’s memory area, ready for use by other instructions in the program. SEND(90)
The following diagram indicates the data flow which will yield the maximum delay time from the time SEND(90) is executed by the user program to the time the SYSMAC LINK Unit stores the data in the destination Unit’s memory. Note Be sure to take into account the time required for data links and program execution, which are not included in the following example.
SEND(90) executed
SYSMAC LINK Unit servicing (source node) Transmission processing
Communications cycle Reception processing
SYSMAC LINK Unit servicing (destination node)
Max. transmission delay Data stored
Max. transmission delay = LINK Unit servicing interval (source node) + Transmission processing + Communications cycle time + Reception processing + LINK Unit servicing interval (destination node). SYSMAC LINK Unit servicing is performed once per PC scan. Delay cause Transmission/reception processing Communications Coaxial cycle time1 Optical
Note
Delay (ms) No. of words transferred × 0.013 ms + 5 ms Max. node no. × 0.01 ms + no. of nodes × 0.075 ms + no. of polled units × 0.75 ms + 1.322 ms Max. node no. × 0.01 ms + no. of nodes × 0.133 ms + no. of polled units × 0.75 ms + 1.322 ms
1. When the data link is halted. Refer to 5-10-1 Data Link Communications Cycle Time for details on the communications cycle time when the data link is operating. 2. The I/O response time might increase due to noise or restrictions on the number of frames that can be transmitted while the data link is operating.
84
Page 99
Section 6-2
NETWORK READ/WRITE Instructions Example
In this example, the maximum transmission delay is calculated for an instruction sending 256 words of data in a system with 32 nodes. Network specifics are detailed below: Max. node number: 32 Number of nodes: 32 Number of polled units: 4 Number of words: 256 Communications: coaxial cable Data link: halted Delay cause
Maximum delay (ms)
LINK Unit servicing
PC scan time
Transmission processing
8.328 ms
Communications cycle time
7.042 ms
Reception processing
8.328 ms
The maximum transmission delay is thus: (PC scan time × 2) + 23.698 ms. The following indicates the data flow which will yield the maximum transfer interval from the time the RECV(98) instruction is executed by the user program to the time the SYSMAC LINK Unit stores the data in the local Unit’s memory area.
RECV(98) Instruction Maximum Delay Time
Note Be sure to take into account the time required for data links and program execution, which are not included in the following example. RECV(98) executed
Data stored Max. transmission delay SYSMAC LINK Unit servicing (source node) Transmission processing (command)
Reception processing (response) Communications cycle
Reception processing (command)
Transmission processing (response) SYSMAC LINK Unit servicing (destination node)
Max. transmission delay = LINK Unit servicing interval (source node) + Transmission processing (command) + Communications cycle + Reception processing (command) + LINK Unit servicing interval (destination node) + Transmission processing (response) + Communications cycle + Reception processing (response) + LINK Unit servicing interval (source node). SYSMAC LINK Unit servicing is performed once per PC scan. Delay cause Transmission/reception processing (command) Transmission/reception processing (response) Communications Coaxial cycle time1 Optical
Delay (ms) 5 ms No. of words transferred × 0.013 ms + 5 ms Max. node no. × 0.01 ms + no. of nodes × 0.075 ms + no. of polled units × 0.75 ms + 1.322 ms Max. node no. × 0.01 ms + no. of nodes × 0.133 ms + no. of polled units × 0.75 ms + 1.322 ms
85
Page 100
Section 6-3
CV-mode Command/Response Format Note
1. When the data link is halted. Refer to 5-10-1 Data Link Communications Cycle Time for details on the communications cycle time when the data link is operating. 2. The I/O response time might increase due to noise or restrictions on the number of frames that can be transmitted while the data link is operating.
Example
In this example, the maximum transmission delay is calculated for an instruction receiving 256 words of data in a system with 32 nodes. Network specifics are detailed below: Max. node number: 32 Number of nodes: 32 Number of polled units: 4 Number of words: 256 Communications: coaxial cable Data link: halted Delay cause
Maximum delay (ms)
LINK Unit servicing
PC scan time
Transmission processing (command)
5 ms
Reception processing (command)
5 ms
Communications cycle time (× 2)
7.042 ms (× 2)
Transmission processing (response)
8.328 ms
Reception processing (response)
8.328 ms
The maximum transmission delay is thus: (PC scan time × 3) + 40.74 ms.
6-3
CV-mode Command/Response Format This section describes the format of commands that can be received from computers or CV-series PCs and the responses that are returned. C-series SYSMAC LINK Units (except models C1000H-SLK21 and C200H-SLK21) can receive CV-mode (FINS) commands, but cannot transmit commands in this command/response format because they are not equipped with a COMMAND instruction (CMND(194) in CV-series PCs). Unless another format is specifically indicated, all commands and responses are in hexadecimal. Commands that are sent to the PC CPU Unit differ from those that are sent to the SYSMAC LINK Unit.
Command Format
Response Format
Commands have the following format: 2 bytes
540 bytes max.
Command code
Data
Responses have the following format: 2 bytes 01
538 bytes max.
Response code
Data
01
Command code
86
2 bytes
Page 101
Section 6-3
CV-mode Command/Response Format
6-3-1 List of CV-mode Commands for PCs Command
Name code 01
PC mode RUN
Page
MONITOR
PROGRAM
01
MEMORY AREA READ
Valid
Valid
Valid
90
02
MEMORY AREA WRITE
Valid
Valid
Valid
90
04
MULTIPLE MEMORY AREA READ
Valid
Valid
Valid
91
02
02
PARAMETER AREA WRITE
Not valid
Not valid
Valid
92
03
06
PROGRAM AREA READ
Valid
Valid
Valid
92
07
PROGRAM AREA WRITE
Not valid
Not valid
Valid
93
01*
RUN
Valid
Valid
Valid
94
04
02*
STOP
Valid
Valid
Valid
94
05
01*
CONTROLLER DATA READ
Valid
Valid
Valid
95
06
01*
CONTROLLER STATUS READ
Valid
Valid
Valid
95
07
01
CLOCK READ (C200H/C200Hj only)
Valid
Valid
Valid
97
02
CLOCK WRITE (C200H/C200Hj only)
Not valid
Valid
Valid
97
21
01
ERROR CLEAR
Valid
Valid
Valid
98
22
0F
Valid
Valid
Valid
98
Valid
Valid
Valid
99
Not valid
Valid
Valid
100
01
FILE MEMORY INDEX READ (C1000H/C2000H only) FILE MEMORY BLOCK READ (C1000H/C2000H only) FILE MEMORY BLOCK WRITE (C1000H/C2000H only) FORCED SET/RESET
Not valid
Valid
Valid
101
02
FORCED SET/RESET CANCEL
Not valid
Valid
Valid
102
0A
FORCED STATUS READ (C200H/C200j only)
Valid
Valid
Valid
102
10 11 23
Note *These command codes are also used for CV-mode commands sent to SYSMAC LINK Units.
6-3-2 List of CV-mode Commands for SYSMAC LINK Units Command
Name code 04
Data link mode Operating
Page
Halted
01*
START DATA LINK
Not valid
Valid
103
02*
HALT DATA LINK
Valid
Not valid
103
03
RESET
Valid
Valid
104
05
01*
CONTROLLER DATA READ
Valid
Valid
104
06
01*
CONTROLLER STATUS READ
Valid
Valid
105
02
NETWORK STATUS READ
Valid
Valid
107
03
DATA LINK STATUS READ
Valid
Valid
108
01*
INTERNODE ECHO TEST
Valid
Valid
109
02
BROADCAST TEST RESULTS READ
Valid
Valid
110
03
BROADCAST TEST DATA SEND
Valid
Valid
110
08
Note *These command codes are also used for CV-mode commands addressed to PCs.
87
Page 102
Section 6-4
Memory Area Designations
6-3-3 CV-mode Response Codes A 2-byte response code is returned with all responses. The first byte contains the main code indicating the general category of the response, and the second byte contains the sub-code giving more specific information. The table below shows the main codes. Refer to 8-1 Troubleshooting for details on sub-codes. Main code
6-4
Description
00
Normal completion
01
Source node error
02
Destination node error
03
Controller error
04
Not executable
05
Routing error
10
Command format error
11
Parameter error
20
Read not possible
21
Write not possible
22
Not executable in current PC mode
23
No Unit
24
Start/stop not possible
25
Unit error
26
Command error
30
Access right error
Memory Area Designations The following table gives the addresses that can be used when reading or writing PC data. The Data area address column gives the data area addresses normally used in the PC program. The Address used in communications column are the PC memory addresses used in CV-mode commands and responses. These addresses are combined with the memory area codes to specify PC memory locations. These addresses are not the same as the actual memory addresses of the data. The Bytes/item column specifies the smallest increment of data that can be read or written for that area. The increment will be either words (2 bytes) or bytes (1 byte).
Memory area Bit status
00000 to 25515
Address used in communications 000000 to 00FF0F
Word contents
000 to 255
000000 to 00FF00
80
2
Bit status
LR 0000 to LR 6315
03E800 to 04270F
00
1
Word contents
LR 00 to LR 63
03E800 to 042700
80
2
Bit status
HR 0000 to HR 9915
042800 to 048B0F
00
1
Word contents
HR 00 to HR 99
042800 to 048B00
80
2
Bit status
AR 0000 to AR 2715
048C00 to 04A70F
00
1
Word contents
AR 00 to AR 27
048C00 to 04A700
80
2
Completion Flag status
TC 000 to TC 511
000000 to 01FF00
01
1
PV
TC 000 to TC 511
000000 to 01FF00
81
2
DM Area
Word contents
DM 0000 to DM 9999
000000 to 270F00
82
2
EM Area
Word contents
EM 0000 to EM 6143
000000 to 17FF00
90 to 98
2
IR and SR Link Relay Holding Relay Auxiliary Relay Timer/Counter
Data
Note
88
Data area address
Memory area code 00
Bytes/ item 1
1. The actual size of memory areas depends on the PC model being used. Refer to the PC Operation Manual for details on memory area ranges.
Page 103
Section 6-4
Memory Area Designations
2. The memory area codes for the EM Area are as follows: codes 90 through 97 specify banks 0 through 7 and code 98 specifies the current bank.
6-4-1 Word/Bit Addresses Each word/bit address specifies a specific bit or word. The rightmost two digits of the address specify bit 00 to 15 (or 00 if not required), and leftmost four digits specify the word address.
Specify the bit between 00 and 0F (00 to 15). Set to 00 to specify word or flag data. Specify the address of the word or flag.
To obtain the corresponding address of the desired word or bit, add the data area word address (hexadecimal) to the first address of the range of addresses used for that data area in communications. For example, the address for word AR 13 is computed as follows: First address for AR Area; 048C + 0D (13 in BCD);
048C 0499
The word address for AR 13 would thus be 049900 (the memory area code would specify this as a word) and the address of bit 12 in AR 13 would be 04990C.
6-4-2 Memory Area Code The memory area code specifies the data area being accessed and whether a bit or word is being accessed, as shown below. Bit:
07
06
05
04
03
Access size 00: Bit 10: Word
02
01
00
Memory area designator 00: IR, SR, LR, HR, or AR 01: Timer/counter 02: Data Memory (DM)
If the access size indicates a bit is being accessed, one byte of data will be read or written. If the access size indicates a word is being accessed, two bytes of data (one word) will be read or written.
6-4-3 Data Configuration The configuration of the types of data that can be read or written is shown below. The number of bytes required for each type of data is also given. Flag or Bit Status (One Byte) 00: Bit is OFF (0) 01: Bit is ON (1) Word Contents, PV (Two Bytes)
Bits 0 to 7 (second byte) Bits 8 to 15 (first byte)
89