Page 104

Section 6-5

CV-mode Commands for PCs

6-5

CV-mode Commands for PCs

6-5-1 MEMORY AREA READ Reads the contents of the specified number of consecutive memory area words starting from the specified word. All words must be in the same memory area (here, all memory areas with the same memory area code are considered as one area). Command Block 01

00

01

Command First word code Memory area code

No. of items

Response Block 01

01

Command code

Parameters

Response code

Data

Memory area code (command): The data area to read. First word (command): The address of the first word to read from memory. Set the third byte of the First word to 00. No. of items (command): The number of items to be read. The number of items must be 0000 to 0100 (0 to 256 decimal). A normal completion response will be returned even if the number of items is set to 00. Data (response): The data from the specified words is returned in sequence starting from the first word. Timer/counter PVs are returned in BCD. The total number of bytes is calculated as follows: Bytes/item x No. of items Memory Areas The following data can be read (refer to 6-4 Memory Area Designations for PC word/bit address designations): Memory area

Data

IR, SR, LR, HR, and AR

Word contents

Memory area Bytes/ code item 80 2

Timer/Counter

Completion Flag status

01

1

PV

81

2

DM

Word contents

82

2

EM

Word contents

90 to 98

2

6-5-2 MEMORY AREA WRITE Writes data to the specified number of consecutive words starting from the specified word. All words must be in the same memory area (here, all memory areas with the the same memory area code are considered as one area). Note

90

1. The MEMORY AREA WRITE command can be executed regardless of the PC’s operating mode. It is the user’s responsibility to program steps to prohibit this command from being executed when the PC is in RUN mode if such protection is necessary. Execute the CONTROLLER STATUS READ command (refer to 6-5-10 CONTROLLER STATUS READ) to read the PC’s mode.

Page 105

Section 6-5

CV-mode Commands for PCs

2. When data is written to the Timer/Counter PV Area, the Completion Flags will be turned OFF (0). Command Block 01

00

02

Command First word code Memory area code

No. of items

Data

Response Block 01

02

Command code

Parameters

Response code

Memory area code (command): The data area to write. First word (command): The first word to write. Set the third byte of the first word to 00. No. of items (command): The number of items to be written. The number of items must be 0000 to 0100 (0 to 256 decimal). A normal completion response will be returned even if the number of items is set to 00. Data (command): The data to be written. Timer/counter PVs are returned in BCD. The total number of bytes is calculated as follows: Bytes/item x No. of items The following data can be written (refer 6-4 Memory Area Designations for the word/bit address designations): Memory area

Data

IR, SR, LR, HR, and AR

Word contents

Memory area Bytes/ code item 80 2

Timer/Counter

PV

81

2

DM

Word contents

82

2

EM

Word contents

90 to 98

2

6-5-3 MULTIPLE MEMORY AREA READ Reads the contents of the specified non-consecutive memory area bytes or words. Bytes or words can be read from up to 128 locations. Note

1. If there is an error in even one memory area code or address, no data will be read. 2. If EM is specified in the memory area code, the maximum number of locations from which bytes or words can be read will be 100.

Command Block Up to 128 addresses

01

04

Command Address code Memory area code

Address Memory area code

91

Page 106

Section 6-5

CV-mode Commands for PCs Response Block 01

04

Command code

Parameters

Response Data code Memory area code

Data Memory area code

Memory area code (command): The data area to read. Address (command): The addresses of the words/bits/flags to read. Data (response): The response returns the memory area code(s) paired with the data from the specified memory area(s). There will be either one or two bytes of data per memory area code depending on the access size specified in the memory area code. Refer to 6-4-2 Memory Area Code for details on access size. Memory Areas The following data can be read (refer to 6-4 Memory Area Designations for memory area designations): Memory area

Data Bit status

Memory area Bytes/ code item 00 1

Word contents

80

2

Completion Flag status

01

1

PV

81

2

DM

Word contents

82

2

EM

Word contents

90 to 98

2

IR, SR, LR, HR, and AR Timer/Counter

6-5-4 PARAMETER AREA WRITE Writes data to the parameter area to designate the DM (data memory) size. Note This command is available only on the SYSMAC C1000HF. Command Block 02

02

Command code

80

10

Parameter code

00

00

First word

80

01

No. of items

Data

Response Block 02

02

Command code

Parameters

Response code

Parameter code (command): 8010 (designate to change the DM size) First word (command): 0000 No. of items (command): 8001 Data (command): Input 00 to designate a DM size of 4,095 words. If 00 is not input, a DM size of 10,000 words will be designated.

6-5-5 PROGRAM AREA READ Reads the contents of the specified number of consecutive program area words starting from the specified word. The data is read in machine language (object code level). A maximum of 512 bytes can be read with each command. To read larger amounts of data, use multiple commands and specify the beginning word and number of words for each.

92

Page 107

Section 6-5

CV-mode Commands for PCs Command Block 03

06

Command code

00

00

Program no.

First word

No. of bytes

Response Block 03

06

Command code

00 Response code

Parameters

00

Program no.

First word

No. of bytes

Data (512 bytes max.)

Program no. (command and response): Set to 0000. First word (command and response): The program area begins at 00000000. The first word must be an even number and will be returned as is in the response. No. of bytes (command and response): The number of bytes in an even number up to 0100 (512 decimal). Bit 15 will be ON (1) in the response block when the last word of data from the program area is in the data returned. In the response, the no. of bytes is the actual number of bytes read. Bit 15 OFF (0): Without last word data Bit 15 ON (1): With last word data Bits 0 to 14: No. of bytes read Bits 0 to 7 (second byte) Bits 8 to 15 (first byte)

If the no. of bytes specified in the command exceeds the number of bytes remaining in the program area, data will be read up to the last word in the program area and an 11 04 or 11 0B parameter error response code will be returned. Data (response): The data in the specified program area will be returned in sequence starting from the beginning word.

6-5-6 PROGRAM AREA WRITE Writes data to the specified number of consecutive program area words starting from the specified word. The data is written in machine language (object code level). A maximum of 512 bytes can be written with each command. To write larger amounts of data, use multiple commands and specify the beginning word and number of words for each. Note The PC will generate an index when bit 15 of the no. of bytes is ON, so bit 15 must be ON when data is written through the last word in the program area. If the no. of bytes is set to 8000, the PC will just generate an index. Command Block 03

07

Command code

00

00

Program no.

First word

No. of bytes

Data (512 bytes max.)

Response Block 03

07

Command code

00 Response code

00

Program no.

First word

No. of bytes

93

Page 108

Section 6-5

CV-mode Commands for PCs Parameters

Program no. (command and response): Set to 0000. First word (command and response): The program area begins at 00000000. The first word must be an even number and will be returned as is in the response. No. of bytes (command and response): The number of bytes in an even number up to 0200 (512 decimal). Bit 15 must be ON (1) when data is written to the last word in the program area. In the response, the no. of bytes is the actual number of bytes read. Bit 15 OFF (0): Without last word data Bit 15 ON (1): With last word data Bits 0 to 14: No. of bytes written Bits 0 to 7 (second byte) Bits 8 to 15 (first byte)

Data (command): The data to be written.

6-5-7 RUN Changes the PC to MONITOR or RUN mode, enabling the PC to execute its program. Command Block 04

01

Command code

Program no.

Mode

Response Block 04

01

Command code

Parameters

Response code

Program no. (command): Set to 0000. Mode (command): As follows: 0002:

MONITOR mode

0004:

RUN mode

Note If the mode is not specified, the PC will go to MONITOR mode.

6-5-8 STOP Changes the PC to PROGRAM mode, stopping program execution. Command Block 04

02

Command code

Response Block 04

02

Command code

94

Response code

Page 109

Section 6-5

CV-mode Commands for PCs

6-5-9 CONTROLLER DATA READ Reads the following data: • PC model and version • Area data • PC status Command Block 05

01

Command code

Response Block 05

01

Command code

Parameters

Response code

20 bytes

20 bytes

16 bytes

10 bytes

65 bytes

PC model

PC version

All zeroes

Area data

All zeroes PC status

PC model and version (response): Both are read in ASCII codes (20 bytes (i.e. 20 ASCII characters) max. each). If the model or version requires less than 20 characters, the remaining bytes will be filled with spaces (ASCII code 20). For the C1000H and C2000H, the version is returned for the MPU1 first followed by the version for the MPU2. If a version does not required 20 characters, the remaining bytes will be filled with spaces (ASCII code 20) for each. All zeroes (response): These bytes contain zeroes. Area data (response): As follows: 1st byte

10th byte 00

00

00

No. of DM words Program area size

Item

EM bank number

File memory size Kind of file memory

Meaning

Unit

Program area size

The size of PC Setup and program area

K words (1K words = 1,024 words)

No. of DM words

Total words in the DM area

Words

EM bank number

Extended Data Memory (EM) Area bank number

Bank

Kind of file memory

00: No file memory 01: SPRAM 04: First half RAM, second half ROM

---

File memory size

0000: 0 (no file memory) 0001: 1000 0002: 2000

Blocks

PC status (response): The value of the byte returned indicates whether or not a Peripheral Device is connected. 00: No Peripheral Device connected. 80: Peripheral Device connected.

6-5-10 CONTROLLER STATUS READ Reads the status of the PC.

95

Page 110

Section 6-5

CV-mode Commands for PCs Command Block 06

01

Command code

Response Block 06

16 bytes

01

Command code

Response code

Fatal error data

Non-fatal error data

FAL no.

Error message

Status Mode

Parameters

Status (response): The operating status of the PC as follows: 00: Stop (program not being executed) 01: Run (program being executed) 80: CPU Unit on standby (the start switch is OFF or the CPU Unit is waiting for a Slave Rack to turn ON). Mode (response): One of the following PC modes: 00: PROGRAM 02: MONITOR 04: RUN Fatal error data (response): The information contained in the fatal error data is shown below. Refer to the PC’s Operation Manual for details on fatal errors. Bit

15

14

13

12

0

0

11

10

9

8

7

0

0

0

6

5

4

3

2

1

0

0

0

0

0

0

0

1: FALS error 1: I/O setting error 1: I/O point overflow 1: I/O bus error 1: Memory error

Non-fatal error data (response): The information contained in the non-fatal error data is shown below. Refer to the PC’s Operation Manual for details on non-fatal errors. Bit

15

14

13

12

11

10

0

0

0

0

0

9

8

7

6

0

0

5

4

3

2

0

0

1

0

1: PC Link error 1: Host Link error 1: Battery error 1: Remote I/O error 1: Special I/O Unit error 1: I/O verification error 1: FAL error

FAL no. (response): The second byte contains the FAL or FALS number of the highest priority error that has occurred in BCD. The first byte contains 00. The FAL no. range is therefore 00 to 99. If neither an FAL nor an FALS error has occurred, the FAL no. will be 0000. Error message (response): The error message of the present FAL number. The error message will be up to 16 ASCII characters. If there is no error message, the response will be shortened.

96

Page 111

Section 6-5

CV-mode Commands for PCs

6-5-11 CLOCK READ Reads the clock. This command can be used with the C200H, C200HS, C200HX, C200HG, and C200HE PCs only. Command Block 07

01

Command code

Response Block 07

01

Command code

Parameters

Response code

Year Month Date Hour Minute Second Day

Year, month, date, hour, minute, second, day (response): Each value is expressed in BCD. Year: The rightmost two digits of the year. Hour: 00 to 23. Day: As follows: Value Day

00

01

02

03

04

Sun

Mon

Tues

Wed

Thur

05 Fri

06 Sat

6-5-12 CLOCK WRITE Sets the clock. This command can be used with the C200H, C200HS, C200HX, C200HG, and C200HE PCs only. Command Block 07

02

Command Year Month Date Hour Minute Second Day code

Response Block 07

02

Command code

Parameters

Response code

Year, month, date, hour, minute, second, day (command): Each specified value is expressed in BCD. Year: The rightmost two digits of the year. Hour: Specify 00 to 23. Day: As follows: Value Day

00

01

02

03

04

Sun

Mon

Tues

Wed

Thur

05 Fri

06 Sat

97

Page 112

Section 6-5

CV-mode Commands for PCs

6-5-13 ERROR CLEAR Clears errors from the PC. Command Block 21

01

Command code

FF

FF

Error reset

Response Block 21

01

Command Response code code

Parameters

Error reset (command): The code must be FFFF.

6-5-14 FILE MEMORY INDEX READ Reads out the indices of a specified number of blocks stored in file memory. This command can be used with the C1000H and C2000H only. Command Block 22

0F

Command code

Beginning block no.

No. of blocks

Response Block

22

Index for last block

Kind of data No. of comments

Kind of data No. of comments

0F

Command Response Remaining Total no. code code no. of blocks of blocks Kind of file memory

Parameters

Index for first block

Beginning block no. (command): The first block to be read. The beginning block no. must be between 0000 and 03E7 (0 to 999 decimal) for 1000 block file memory, or 0000 and 07CF (0 to 1999 decimal) for 2000 block file memory. No. of blocks (command): The number of blocks to be read. The no. of blocks must be between 01 and 80 (0 to 128 decimal). Remaining no. of blocks (response): The number of blocks remaining after the read. The remaining no. of blocks will be between 0000 and 07CF (0 to 1999 decimal). Total no. of blocks (response): The number of blocks in the file memory. The total no. of blocks will be between 0000 (0), 03E8 (1000), or 07D0 (2000). Kind of file memory (response): The kind of file memory installed, as follows: 00: All RAM 01: First half RAM, second half ROM

98

Page 113

Section 6-5

CV-mode Commands for PCs

Kind of data (response): The kind of data in this block, as follows: Bit

7

6

5

4

3

0

0

0

2

1

0

Kind of data (see table below) 1: Protected 1: Block contains END(01) (program data only)

Kind of data Bits 0 to 2 indicate the kind of data, as shown in the following table. Bit status 2 1 0

Kind of data

0

0

0

None

0

0

1

I/O data

0

1

0

Program

0

1

1

Comments

No. of comments (response): If the block contains comments data, this byte indicates the number of comments.

6-5-15 FILE MEMORY BLOCK READ Reads the contents of the indicated block of file memory. This command can be used with the C1000H and C2000H only. Command Block 22

10

Command code

Block no.

Response Block 22

256 bytes

10

Command Response Kind of code code data No. of comments

Parameters

Block data

Block no. (command): The block number of the block to be read. The block no. must be between 0000 and 03E7 (0 to 999 decimal) for 1000 block file memory, or 0000 and 07CF (0 to 1999 decimal) for 2000 block file memory. Kind of data (response): The kind of data in the block, as follows: Bit

7

6

5

4

3

0

0

0

2

1

0

Kind of data (see table below) 1: Protected 1: Block contains END(01) (program only)

99