Page 124

Section 6-6

CV-mode Commands for SYSMAC LINK Units response differs from that transmitted in the command, an error occurred in the internode echo test.

6-6-9 BROADCAST TEST RESULTS READ Reads the results (number of receptions for each node) of the broadcast tests carried out using the BROADCAST TEST DATA SEND command. Refer to 6-6-10 BROADCAST TEST DATA SEND for details on that command. Command Block 08

02

Command code

Response Block 08

02

Command code

Parameters

Response code

Number of receptions

Number of receptions (response): The number of times that the BROADCAST TEST DATA SEND command has been executed since the last BROADCAST TEST RESULTS READ command was executed. When this command is executed, the number of receptions data stored in the destination nodes is cleared. If the number of receptions does not equal the number of times that the BROADCAST TEST DATA SEND command has been executed since the last BROADCAST TEST RESULTS READ command was executed, an error has occurred.

6-6-10 BROADCAST TEST DATA SEND Sends the test data in the command to all nodes in the specified network. No response will be returned when this command is executed, but reception of the test data can be verified by executing the BROADCAST TEST RESULTS READ command. Refer to 6-6-9 BROADCAST TEST RESULTS READ for details. Command Block 08

03

Command code

512 bytes max.

Test data

Note Make the following control data settings when executing this command: a) Destination node number:

FF (broadcast transmission)

b) Destination node unit number:

FE (to SYSMAC LINK Units)

c) Response Flag (bit 13 of C+1): ON (response not returned)

110

Page 125

SECTION 7 Special Services Information on remote programming and monitoring and RAS functions is provided in this section. 7-1 7-2

Remote Programming and Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RAS Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2-1 Internode Echo Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2-2 Broadcast Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2-3 Polling Unit Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2-4 Failed Node Bypass (Optical Networks Only) . . . . . . . . . . . . . . . . . . . . . . . . . . .

112 113 113 115 115 116

111

Page 126

Section 7-1

Remote Programming and Monitoring

7-1

Remote Programming and Monitoring Any C200HX, C200HG, C200HE, C200HS, C200H, C1000H, or C2000H (simplex) PC on a SYSMAC LINK Network can be remotely programmed and monitored using a SSS/CVSS connected to any other PC on the network. C2000H Duplex PCs cannot be remotely programmed and monitored through the SYSMAC LINK Network. Remote programming or monitoring of the CVM1 and CV-series PCs is not possible.

Peripheral Device Connection

The SSS is connected to C-series PCs via a C500-IP004 or C200H-IP006/007 Peripheral Interface Unit and can provide remote programming and monitoring capability for PCs in the same Network. In addition, the CVSS (CV Support Software, see note following diagram) running on an IBM-PC/AT or compatible can be used. The abbreviations in the diagram below indicate the following OMRON products: SLK: SYSMAC LINK Unit NSB: SYSMAC LINK Network Service Board IP: Peripheral Interface Unit or Conversion Cable

IP

PC

PC

PC

SLK

SLK

SLK

SLK

NSB

PC

Computer

SSS

Note When the C- and CV-series PCs are in the same system configuration, CVSS on an IBM-PC/AT or compatible can be used. Remote Communications Limits

112

The SSS can provide remote programming and monitoring capability for all PCs in the same Network. If the SSS is connected to a PC that is part of two Networks, i.e., one that has two SYSMAC LINK Units mounted to it, then remote programming and monitoring are possible for any PC in either Network.

Page 127

Section 7-2

RAS Functions

The SSS can only access PCs within the Network of which the PC it is connected to is a part. In the following diagram SSS A is attached to PC 1 and can remotely program and monitor PCs 1, 2, 3, 4, 5, 6, 7, and 8. SSS B is attached to PC 2 and can program and monitor only PCs 1, 2, 3, and 4.

SSS A

PC (1)

PC (2)

PC (3)

SLK

SLK

SLK

SLK PC (4)

SSS B

SLK

7-2

SLK

SLK

SLK

PC (5)

PC (6)

PC (7)

RAS Functions RAS is an acronym for Reliability, Availability, and Serviceability, and the RAS functions are intended to promote these three elements in the SYSMAC LINK Network.

7-2-1 Internode Echo Test The internode echo test involves transmitting data to a specific node and requesting the node to send back the data that was sent. The results of the test are stored in the IR area. The internode echo test can also be executed with a CV-mode command. Refer to 6-6-8 INTERNODE ECHO TEST for details. Internode Test Functions

1, 2, 3...

Data Preparations

Internode Testing functions in the following manner: 1. Test data is transmitted to a specified node. 2. The specified node returns the test data unaltered. 3. The original test data is compared to the data which was echoed back. If there is any discrepancy, an error code is generated. Using the Programming Console, set the node number of the destination PC in IR 23200 to IR 23207 for the C1000H/C2000H, IR 04000 to IR 04007 for the C200H, and IR 50000 to IR 50007 for the C200HS, C200HX, C200HG, or C200HE. The node number must be between 1 and 62 ($01 to $3E) and can be changed during the test. Do not set the node number to the local node’s node number or $00 (broadcast mode).

113

Page 128

Section 7-2

RAS Functions Internode Test Execution

The test is initiated by moving the node number of the destination PC to IR 232 (IR 040 in the C200H and IR 500 in the C200HS, C200HX, C200HG, or C200HE) and then turning ON pin 1 of DIP switch 1. The overall procedure is listed below. The PC that is initiating the test must be in PROGRAM mode. The PC receiving the transmission may be set in any mode. The overall procedure for the test is as follows:

1, 2, 3...

Test Results

1. Set the PC to PROGRAM mode. 2. Input the node number of the destination PC. 3. Turn ON pin 1 of DIP switch 1. 4. Check test results via indicators and/or returned data. 5. To test another node, change the destination node number and check results for the new node. 6. Turn OFF pin 1 of DIP switch 1. Test results are indicated both on the Unit indicators and stored in the IR area. The TS indicator displays the results of the test for each node. Lit: . . . . . . . . . . Testing in progress Flashing: . . . . . Testing error Not lit: . . . . . . . Test halted The table below shows the results of the tests which will be stored in the IR area of the PC which initiated the test.

IR 500

IR 040

C1000H/ C2000H IR 232

IR 501

IR 041

IR 233

Number of test cycles

IR 502

IR 042

IR 234

Number of errors

IR 503

IR 043

IR 235

Number of times not able to transmit Test status

IR 504

IR 044

IR 236

Number of no responses

Number of busy responses

IR 505

IR 045

IR 237

Number of no-token time-outs

Number of data mismatches

C200Hj

C200H

Bits 00 to 07 Destination node number

Bits 08 to 15 * (07)

Set to zero.

* Bit 07 will be turned ON when the destination node number designation is incorrect. Number of test cycles is the total number of data packets sent and echoes received. Number of errors is the total number of errors. Test status is as follows. 15

14

13

12

11

10

09

08

Normal completion (0), Error (1) Destination node not part of Network (1) Token time-out (1) Data mismatch (1) Local node not part of Network* (1) No response (1) Destination node busy (1) Not able to transmit (1)

Note *This error will occur when the communications chip is faulty, there is a node number setting error, or node number duplication error.

114

Page 129

Section 7-2

RAS Functions

Number of times not able to transmit is the number of times transmission was impossible because the destination node or the local node were not part of the Network, or node did not have the right to transmit. Number of busy responses is number of times the node was unable to transmit because destination node was busy. Number of no responses is the number of times the destination node did not respond. Number of data conflicts is number of times test data did not match data echoed back. Number of token time-outs is the number of times transmission was impossible because the node did not receive the token giving it polling unit status. Note

1. Responses are monitored for two seconds. 2. When the destination node number is changed in IR 232 (IR 040 in the C200H and IR 500 in the C200HX, C200HG, C200HE, or C200HS), the test results in IR 233 to IR 237 (IR 041 to IR 045 in the C200H and IR 505 in the C200HX, C200HG, C200HE, or C200HS) will be initialized.

7-2-2 Broadcast Test The broadcast test transmits data to all nodes in the network simultaneously and then reads the results (number of receptions for each node) of the test. The broadcast test can also be executed with CV-mode commands. Refer to 6-6-10 BROADCAST TEST DATA SEND for details. Broadcast Test Execution

The test can be executed with a SSS/CVSS. Refer to the Peripheral Device’s Operation Manual for details. The test proceeds as follows:

1, 2, 3...

1. The test data is transmitted to all nodes the specified number of times. 2. The number of receptions at each node is read out. 3. The test results (the number of transmissions and successful receptions) are displayed.

7-2-3 Polling Unit Backup SYSMAC LINK Units provide an automatic backup function. In case of a failure or error in the SYSMAC LINK Unit which is currently the polling unit, the Network is automatically restructured. The lowest numbered functional node within the Network becomes the new polling unit, and the Network continues to function. While the Network is restructuring itself, all data transmission stops. If the data link was operational when the polling unit failed, data is saved in the state it was just prior to the failure and data link operations will continue. The time required to restructure the Network in the event of an error or failure may be calculated using the following formula: Restructuring time = (new polling unit node number + 1) x 20 ms + highest node number x 1 ms

115

Page 130

Section 7-2

RAS Functions

7-2-4 Failed Node Bypass (Optical Networks Only) SYSMAC LINK Networks using optical fiber cable and equipped with a back-up power supply and Power Supply Units have an automatic bypass function. If a failure or error occurs in a node of the network, that node will be bypassed, and the rest of the network will continue functioning. In the example shown below, node 3 fails, but communications continue by bypassing node 3. The abbreviations in the diagram below indicate the following OMRON products: SLK: APS:

SYSMAC LINK Unit (optical type) Auxiliary Power Supply Unit

Optical transmission path

SLK (node #1)

SLK (node #2)

SLK (node #3)

SLK (node #4)

APS

APS

APS

APS

PC

PC

PC

PC

Node #3 fails Backup power supply

The following table shows which Auxiliary Power Supply Units can be used with the SYSMAC LINK Units. SYSMAC LINK Unit

! Caution

116

Auxiliary Power Supply Unit

C1000H-SLK11

C1000H-APS01

C200HW-SLK13/14

C200H-APS03

In an optical network, power supplied from the Power Supply Unit that is connected to each node will have precedence over power supplied from the back-up Power Supply Unit of the system. Be sure to turn on the Power Supply Units and the PCs simultaneously, or turn on the Power Supply Units first and then turn on the PCs. If the Power Supply Units are turned on or off, a transmission data error will result.

Page 131

SECTION 8 Error Processing Information to help identify and correct errors that might occur is provided in this section. 8-1 8-2

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Network Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

118 124

117

Page 132

Section 8-1

Troubleshooting

8-1

Troubleshooting

Error Indications

The table below lists error conditions, their probable cause, and possible remedies.

Error indicator RUN indicator not lit

ERC indicator lit

Probable cause

Remedy

SYSMAC LINK Unit faulty.

Replace Unit.

PC not connected to power supply.

Connect to power supply (check connectors).

PC’s power supply voltage too low.

Adjust voltage to within recommended range.

SYSMAC LINK Unit mounting screws are loose.

Tighten screws.

SYSMAC LINK Unit mounted in wrong slot.

Move Unit to correct slot.

PC faulty.

Replace PC.

Node address setting is incorrect.

Not between 1 and 62 Duplicated setting

Communications Controller is faulty.

Hardware problem in the communications part of the Unit. Power supply Power Supply selection Unit is faulty. circuit is Power supply unstable. section of the Unit is faulty. Connectors are broken or have poor contact. External power supply has dropped.

ERH indicator lit

INS indicator not lit

Set the node address to between 1 and 62. Set the node addresses again so that each address is used only once and then restart. Replace the SYSMAC LINK Unit.

Replace the Power Supply Unit. Replace the SYSMAC LINK Unit.

Check connectors and replace them if necessary.

Check the primary side of the Power Supply Unit.

Unit mounted to faulty PC.

Replace PC.

Unit mounted to incompatible PC.

Replace PC.

EEPROM error.

Re-initialize network parameters and data link tables or replace Unit.

Watchdog timer error in PC.

Replace PC.

Terminator connection faulty.

Connect Terminator correctly.

Cable connection faulty.

Connect cables correctly.

Local node’s node number greater than the maximum node number set in the polling unit’s network parameters.

Increase the maximum node number or decrease the local node number.

LNK indicator flash- Data link table error on local node. ing

Re-create data link table.

Error when reading EEPROM.

Re-create data link table or replace PC.

Data link table of currently operating node and data link table of the local node don’t match.

Stop data link and modify the data link table of either the currently operating node or the local node so they match.

Local node has no data link table.

Create a data link table.

Note Node numbers cannot be modified with the power on. To change node numbers, first turn off the power, then change the settings, making sure not to duplicate any node numbers.

118

Page 133

Section 8-1

Troubleshooting Send (90)/RECV(98) Errors

Response code 00: Normal completion 01: Parameter error 02: Unable to transmit

03: Destination node not in Network

The table below lists response codes returned after execution of the SEND(90) and RECV(98) instructions, the probable cause of errors, and recommended remedies.

Item to check

Probable cause

Remedy

---

---

---

---

Local node parameter is outside of specified range. Local node not part of Network.

Set the parameter correctly.

Local node SYSMAC LINK Unit was initialized during instruction execution.

Execute the instruction again.

Destination node not part of Network.

Add to Network.

Destination node SYSMAC LINK Unit was initialized during instruction execution.

Execute the instruction again.

Increase the number of transmit retry attempts or re-evaluate the system so that the destination node is not so busy receiving data. Increase the number of transmit retry attempts. Perform an internode echo test to check noise level.

Network status of local node

Network status of destination node

Add to Network.

04: Busy error

---

Destination node is engaged in receiving data.

05: Response Time-out

---

Message packet was corrupted by noise.

Control data

Response watchdog timer interval too short. DM Area overrun because of DM Area size mismatch between PCs.

Increase the value for the response watchdog timer interval. Check the first word of the data transfer area at the destination node and reset if necessary.

06: Response Error

Destination node parameters

07: Communications controller error

AR 1114 (level 0) or AR 1514 (level 1)

An error has occurred in the local node communications controller.

Take corrective action, referring to communications controller errors and remedies table at end of this section.

08: Setting error

Node number

Check node number of local node.

09: PC error

Destination node indicators

A CPU Unit error at the destination node has occurred.

Set the node number correctly. Make sure the node number is within specified range and that there are no duplicate node numbers. Clear the error in the CPU Unit (refer to the PC’s Operating Manual).

CV-mode Command Errors

Main code 00: Normal completion

The table below lists response codes (main and sub-codes) returned after execution of the CV-mode commands, the probable cause of errors, and recommended remedies. Upon receipt of some commands, the destination node will issue a request to another node; the other node is referred to as the third node.

Subcode 00

Probable cause

Remedy

---

---

01

Service was interrupted.

Check the contents of the destination transmission area of third node.

119