The text of a manual · part 15 of 19
C-series SYSMAC LINK System Manual, pages 134 to 143
Pages 134 to 143 of 174
The original document is the PDF (983 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200HW-SLK24
Page 134
Section 8-1
Troubleshooting Main code 01: Local node error
Subcode 01 02 03
02: Destination node error
03: Communications controller error
Add to Network.
Token time-out, node number too high. Number of transmit retries exceeded.
Set the local node’s node number below the maximum node number. Check communications with internode echo test. If the test fails, check network. Either check the execution of events in the network and reduce the number of events occurring in one cycle, or increase the maximum number of frames. Make sure the node number is within specified range and that there are no duplicate node numbers.
05
Node number setting error (range).
06
Node number duplication error.
01
Destination node not part of Network.
Make sure that there are no duplicate node numbers. Add to Network.
02 03
No node with the specified node number. Third node not part of Network.
Check the destination node’s node number. Check the third node’s node number.
04
Busy error, destination node busy.
05
Response time-out, message packet was corrupted by noise.
Increase the number of transmit retry attempts or re-evaluate the system so that the destination node is not so busy receiving data. Increase the number of transmit retry attempts. Perform an internode echo test to check noise level.
Response time-out, response watchdog timer interval too short. Error occurred in the communications controller, ERC indicator is lit.
Increase the value for the response watchdog timer interval. Take corrective action, referring to communications controller errors and remedies table at end of this section.
CPU Unit error occurred in the PC at the destination node. Node number setting error.
Clear the error in the CPU Unit (refer to the PC’s Operating Manual) Make sure the node number is within specified range and that there are no duplicate node numbers.
An undefined command has been used. Cannot process command because the specified unit model or version is wrong.
Check the command code.
02
Destination node number is not set in the routing table. Routing table isn’t registered.
03
Routing table error.
Set the destination node number in the routing table. Set the source nodes, destination nodes, and relay nodes in the routing table. Set the routing table correctly.
04
The maximum number of relay nodes (2) was exceeded in the command.
01
01 02
120
Local node not part of Network.
Maximum number of frames exceeded.
04
05: Routing error
Remedy
04
02
04: Not executable
Probable cause
01
Check the unit model and version.
Redesign the network or reconsider the routing table to reduce the number of relay nodes in the command.
Page 135
Section 8-1
Troubleshooting Main code 10: Command format error
Subcode 01
Probable cause
Remedy
The command is longer than the max. permissible length. The command is shorter than min. permissible length. The designated number of data items differs from the actual number. An incorrect command format has been used.
Check the command format of the command and set it correctly. Check the command format of the command and set it correctly. Check the number of items and the data, and make sure that they agree. Check the command format of the command and set it correctly.
05
An incorrect header has been used. (The local node’s relay table or relay node’s local network table is wrong.)
Set the routing table correctly.
01
A correct memory area code has not Check the command’s memory area code been used or Expansion Data Memory and set the appropriate code. is not available.
02
The access size specified in the command is wrong, or the first address is an odd number.
Set the correct access size for the command.
03
The first address is in an inaccessible area. The end of specified word range exceeds the acceptable range.
Set a first address that is in an accessible area. Check the acceptable limits of the data area and set the word range within the limits.
A non-existent program no. has been specified. The sizes of data items in the command block are wrong. The response block is longer than the max. permissible length. An incorrect parameter code has been specified.
Check the program number and be sure that it is set correctly. Check the command data and be sure that the sixes of the data items are correct. Check the command format and set the number of items correctly. Check the command data and reenter it correctly.
02
The program area is protected.
Execute the instruction again after issuing the PROGRAM AREA PROTECT CLEAR command.
03
The registered table does not exist or is incorrect.
Set or reset the registered table.
01
The specified area is read-only or is write-protected.
If the specified area is read-only, the write cannot be performed. If it is write-protected, turn off the write-protect switch and execute the instruction again.
02
The program area is protected.
Execute the instruction again after issuing the PROGRAM AREA PROTECT CLEAR command.
01
The mode is wrong (being executed).
Check the operating mode.
02
The mode is wrong (stopped).
Check the operating mode.
03
The PC is in the PROGRAM mode.
Check the PC’s mode.
04
The PC is in the DEBUG mode.
Check the PC’s mode.
05
The PC is in the MONITOR mode.
Check the PC’s mode.
06
The PC is in the RUN mode.
Check the PC’s mode.
07
Check which node is the control node.
02
The specified node is not the control node. The specified memory does not exist.
03
No clock exists.
01
The data link table either hasn’t been created or is incorrect.
02 03 04
11: Parameter error
04
06 09 0B 0C 20: Read not possible
21: Write not possible
22: Not executable in current mode
23: No Unit
24: Start/halt not possible
Check the specifications of the installed file memory. Check the model number. Set the data link table correctly.
121
Page 136
Section 8-1
Troubleshooting Main code 25: Unit error
Subcode 12
26: Command error
05
The service is being executed.
07
Service cannot be executed from local node because the local node is not part of the data link.
0B
Cannot clear error because the cause of the error still exists.
Data Link Status Errors Data link status PC Error ON
Communications error ON
Node not in data link
Probable cause
Remedy
Execute the command again after the service has been completed or aborted. Execute the service from a node that is part of the data link. Eliminate the cause of the error and execute the ERROR CLEAR command.
The following table lists data link status errors, their probable cause, and possible remedies. Check all nodes in question.
Point to check
Probable cause
Remedy
PC Error Flag (bit 01, 05, 09, or 13 in the data link status flags)
A fatal error has caused the CPU Unit to halt (FALS instruction generated, etc.) CPU Unit error.
Clear the error in the CPU Unit, referring to the Unit’s Operating Manual and Installation Guide.
Connected to an incompatible PC. Error resulting from noise.
Connect only to compatible PCs.
Unit in question is not part of the Network. Communications cycle time too short. Node in question is not part of the data link.
Add the Unit to the Network.
Communications Error Flag (bit 02, 06, 10, or 14 in the data link status flags)
Data Link Member Flag (bit 03, 07, 11, or 15 in the data link status flags)
Data Link Table Error Messages
Run an internode echo test; if the results are not OK, re-check the operating environment.
Increase communications cycle time. Add the node in question to the data link.
The following tables list data link table errors, their probable cause, and possible remedies for the SSS/CVSS.
SSS/CVSS Error Write not possible
Probable Cause and Remedy The number of LR Area data link words is greater than 64 words. The maximum number of LR Area data link words is 64 words in C-series PCs. The total number of data link words is greater than 2966 words (918 words when C200HW-SLK13/23 SYSMAC LINK Units are included). Make sure that the total number of data link words is 2966 words or less (918 words or less when C200HW-SLK13/23 SYSMAC LINK Units are included). The node number of a C200HW-SLK13/23 SYSMAC LINK Unit has been set incorrectly when the total number of data link words exceeds 918. Refer to 5-8 Data Link Precautions for more details on node number settings. The refresh parameter’s beginning DM or LR word setting is incorrect. When setting the beginning LR word for C-series SYSMAC LINK Units, LR words LR 00 to LR 63 correspond to CV-series addresses CIO 1000 to CIO 1063. Refer to page 44 for details on data link areas for different PC models. The refresh parameter’s beginning DM or LR word setting is incorrect and the regions specified by the beginning DM or LR words cannot be used as a data link area. The data area regions that can be used as a data link area vary from PC to PC. Refer to page 44 for details on data link areas for different PC models. (Also, C-series addresses LR 00 to LR 63 correspond to CV-series addresses CIO 1000 to CIO 1063.) The refresh parameter’s beginning status word setting is incorrect. Make sure that the beginning status word specifies a region that can be used for the data link status area (16 words). Refer to 5-8 Data Link Precautions for more details. The refresh parameter’s PC model setting is set to “CV-series.” Set the PC model to “Other” when the setting is for a C-series SYSMAC LINK Unit.
Other Errors
122
The table below lists other errors not covered above. Probable causes and remedies are also provided.
Page 137
Section 8-1
Troubleshooting Error
Point to check
Communications Controller error
AR 1114 for operating level 0
Noise or environmental influences.
AR 1514 for operating level 1
Consider replacing communications-reReinitialize the SYSMAC LINK Unit lated hardware if one of the following If the problem recurs, replace the errors occurs: Unit. · Communications Controller watchdog timer error · Communications Controller memory error · Communications Controller chip bad · Transmitter portion of Communications Controller bad · Local node internode echo test error
ERC indicator
Communications Controller error
AR 1114 for operating level 0 AR 1514 for operating level 1
Probable cause
Hardware problem in the communications section of the Unit.
• Communications Controller memory error.
Remedy Run an internode echo test; if an error occurs, recheck the operating environment.
Replace the SYSMAC LINK Unit.
• Communications Controller chip bad. • Transmission section of the Communications Controller bad. • Local node loopback test error.
Power supply selection circuit is unstable.
EEPROM error
• Communications Controller watchdog timer error. Power Supply Unit Replace the Power Supply Unit. may be faulty. Power supply Replace the SYSMAC LINK Unit. section of the Unit is faulty. Connectors are broken or have poor contact.
Check connectors and replace them if necessary.
External power supply on the primary side of the Power Supply Unit has dropped.
Check the primary side of the Power Supply Unit.
AR 1115 for operating level 0
Network parameters backed up in the EEPROM or data link table corrupted.
AR 1515 for operating level 1
Network parameters or data link table (1) Reset the network parameters destroyed when backing up in EEPROM. and data link tables using the SSS/ CVSS. When a network parameters mismatch
ERH indicator occurs, the parameters have been destroyed. When the LNK indicator flashes, it indicates that the data link table has been destroyed.
Network Parameters mismatch
AR 2406 for operating level 1 AR 2407 for operating level 0
Network parameters being used in the currently operating Network do not match the network parameters set in the Unit in question.
Reset the network parameters and data link tables in the node in question.
(2) Initialize the Unit by toggling DIP switch 1, pin 7 (C1000H-SLK11 or C1000H-SLK21) or DIP switch 2, pin 3 (C200HW-SLK13/14/23/24). a)If an EEPROM error continues to occur even after performing the reset actions above, the EEPROM has failed. Replace the Unit. Use the SSS/CVSS to check the network parameters and reset them if necessary.
123
Page 138
Section 8-2
Network Troubleshooting
8-2
Network Troubleshooting Use the headings in this section to troubleshoot problems that occur in the Network and find a list of the probable causes of the problem.
Unable to operate network Check indicators on the entire Network. RUN indicator not lit • Check whether power is being supplied to the PC at adequate voltage. • Check whether mounting screws on Unit are tight. • Check whether the Unit is mounted in a permissible slot on the Rack. • Check whether the Unit operates normally when mounted on another PC. • If none of the actions above solve the problem, replace suspect SYSMAC LINK Units. INS indicator not lit • Check whether local node number is greater than the maximum node number setting. If it is, lower local node number or increase maximum node number. • Check whether the same node number has been assigned twice. • In coaxial cable systems, check whether the Terminators are connected properly. • Check whether all cables are connected properly. • Check whether the cables transmit properly.
Unable to add local node to network A local node cannot be added to the Network. (Check indicators on the node which cannot be added.) RUN indicator not lit • Check whether power is being supplied to the PC at adequate voltage. • Check whether mounting screws on Unit are tight. • Check whether the Unit is mounted in a permissible slot on the Rack. • Check whether the Unit operates normally when mounted on another PC. • If none of the actions above solve the problem, replace suspect SYSMAC LINK Units. ERC indicator lit • Check the PC’s Communications Controller Error Flags. If ON, replace the SYSMAC LINK Unit. • Check whether node number is within the range of 1 to 62. If not, reset to a unique node number from 1 to 62 (duplicate node numbers not permitted). • Check for duplicate node numbers. Make sure each node number is assigned to only one unit. ERH indicator lit • Check whether the Unit is mounted to an incompatible model or version or PC. Replace PC if necessary. • Check for CPU Unit error in the PC. Switch power off and turn on again. If problem occurs again, replace PC. • Check for EEPROM error. INS indicator not lit • Check whether local node number is greater than the maximum node number setting. If it is, lower local node number or increase maximum node number. • Check whether the same node number has been assigned twice.
124
Page 139
Section 8-2
Network Troubleshooting
• In coaxial cable systems, check whether the Terminators are connected properly. • Check whether all cables are connected properly. • Check whether the cables transmit properly.
Data link cannot be started Data link does not operate properly. Check indicators on the data link nodes. LNK indicator is not lit and RUN indicator not lit • Check whether power is being supplied to the PC at adequate voltage. • Check whether mounting screws on Unit are tight. • Check whether the Unit is mounted in a permissible slot on the Rack. • Check whether the Unit operates normally when mounted on another PC. • If none of the actions above solve the problem, replace SYSMAC LINK Units. ERC indicator lit • Check the PC’s Communications Controller Error Flags. If ON, replace the SYSMAC LINK Unit. • Check whether node number is within the range of 1 to 62. If not, reset to a unique node number from 1 to 62 (duplicate node numbers not permitted). • Check for duplicate node numbers. Make sure each node number is assigned to only one unit. ERH indicator lit • Check whether the Unit is mounted to an incompatible model or version or PC. Replace PC if necessary. • Check for CPU Unit error in the PC. Switch power off and turn on again. If problem occurs again, replace PC. • Check for EEPROM error. INS indicator not lit • Check whether local node number is greater than the maximum node number setting. If it is, lower local node number or increase maximum node number. • Check whether the same node number has been assigned twice. • In coaxial cable systems, check whether the Terminators are connected properly. • Check whether all cables are connected properly. • Check whether the cables transmit properly. LNK indicator flashing • Check whether a data link table has been created. If not, generate one. • Check whether an EEPROM error has occurred. If so, investigate EEPROM error causes and remedies as outlined on page 123 • If a data link is already operating on the same Network, bring that data link to a halt, and start the data link that has the problem. • If the LNK indicator flashing on other nodes, stop the data links in those nodes.
Data link cannot be stopped Data link does not operate properly. Check indicator indicators on the data link nodes. LNK indicator is not lit and RUN indicator not lit • Check whether power is being supplied to the PC at adequate voltage. • Check whether mounting screws on Unit are tight.
125
Page 140
Section 8-2
Network Troubleshooting
• Check whether the Unit is mounted in a permissible slot on the Rack. • Check whether the Unit operates normally when mounted on another PC. • If none of the actions above solve the problem, replace suspect SYSMAC LINK Units. ERC indicator lit • Check the PC’s Communications Controller Error Flags. If ON, replace the SYSMAC LINK Unit. • Check whether node number is within the range of 1 to 62. If not, reset to a unique node number from 1 to 62 (duplicate node numbers not permitted). • Check for duplicate node numbers. Make sure each node number is assigned to only one unit. ERH indicator lit • Check whether the Unit is mounted to an incompatible model or version or PC. Replace PC if necessary. • Check for CPU Unit error in the PC. Switch power off and turn on again. If problem occurs again, replace PC. • Check for EEPROM error. INS indicator not lit • Check whether local node number is greater than the maximum node number setting. If it is, lower local node number or increase maximum node number. • Check whether the same node number has been assigned twice. • In coaxial cable systems, check whether the Terminators are connected properly. • Check whether all cables are connected properly. • Check whether the cables transmit properly.
Node cannot join data link Node cannot be entered into the data link. Check indicators on the node which you want to add to data link. LNK indicator is not lit and RUN indicator not lit • Check whether power is being supplied to the PC at adequate voltage. • Check whether mounting screws on Unit are tight. • Check whether the Unit is mounted in a permissible slot on the Rack. • Check whether the Unit operates normally when mounted on another PC. • If none of the actions above solve the problem, replace suspect SYSMAC LINK Units. ERC indicator lit • Check the PC’s Communications Controller Error Flags. If ON, replace the SYSMAC LINK Unit. • Check whether node number is within the range of 1 to 62. If not, reset to a unique node number from 1 to 62 (duplicate node numbers not permitted). • Check for duplicate node numbers. Make sure each node number is assigned to only one unit. ERH indicator lit • Check whether the Unit is mounted to an incompatible model or version or PC. Replace PC if necessary. • Check for CPU Unit error in the PC. Switch power off and turn on again. If problem occurs again, replace PC. • Check for EEPROM error.
126
Page 141
Network Troubleshooting
Section 8-2
INS indicator not lit • Check whether local node number is greater than the maximum node number setting. If it is, lower local node number or increase maximum node number. • Check whether the same node number has been assigned twice. • In coaxial cable systems, check whether the Terminators are connected properly. • Check whether all cables are connected properly. • Check whether the cables transmit properly. LNK indicator flashing • Confirm that a data link table has been created. If not, do so. • Check whether the data link tables of nodes which are currently in the data link match that of the local node. If not, stop data link operations and modify the data link table either in the local node or the nodes which are currently linked. • If the data link tables do match, check whether an EEPROM error has occurred. If so, investigate EEPROM error causes and remedies. LNK indicator still not lit • When the data link tables have been generated automatically, confirm that the node number of the local node is within the range of node numbers set automatically. If not, either lower the node number of the local node so that it is within the range, or change the automatic settings in AR 07 to include the local node. • Check whether the node number of the local node is included in the common link parameters in the data link tables of those nodes currently in the data link. If not, stop data link operations and modify the data link tables of either the active nodes or of the local node.