Page 144

Section 9-1

Periodic Inspection

9-1

Periodic Inspection SYSMAC LINK Units must be inspected on a regular basis to ensure correct operation. SYSMAC LINK Units are built primarily of solid-state components and contain almost no parts subject to wear. Nevertheless, the life span of some solid-state components can be shortened as a result of adverse environmental conditions. We recommend that the following points be checked at least once every 6 to 12 months as part of a standard inspection program. Ambient conditions should be checked more frequently. If any of these items deviate from the prescribed standards, take appropriate action to correct the condition. Item

Description

Ambient conditions

Temperature: 0° to 55°C Humidity: 10% to 90% (no condensation) Dust-free

Installation

SYSMAC LINK Units securely attached? Cable connectors tight? Screws tightened on terminal blocks for external wiring? Cabling used for external wiring intact (no breaks)?

We recommend that users have backup Units available to make repairs and minimize down-time if a problem occurs in a SYSMAC LINK Unit. Handling Precautions when Replacing Units

Please observe the following precautions in the event of a problem: • Always turn the power off when replacing a SYSMAC LINK Unit. • After replacing a Unit, always make the required settings before restarting operation. • If a SYSMAC LINK Unit fails, replace it with a new one and immediately verify that the new Unit is working properly. • When returning a malfunctioning SYSMAC LINK Unit for repair, please attach a detailed description of the problem to the Unit and return it to the sales office nearest you (see listing at the end of this manual). • If you suspect that a poor connection is the cause of a malfunction, clean the connectors using a clean, soft cloth and industrial-grade alcohol. Remove any lint or threads left from the cloth, and re-mount the SYSMAC LINK Unit.

Interchanging C200HS-SLK12/22 and C200HW-SLK13/14/23/24 SYSMAC LINK Units

The C200HW-SLK13/14/23/24 SYSMAC LINK Units’ functions are equal to or superior to those of the C200HS-SLK12/22 Units, so C200HS-SLK12/22 Units can be replaced with C200HW-SLK13/14/23/24 Units. Do not replace C200HWSLK13/14/23/24 Units with C200HS-SLK12/22 Units.

Tools and Equipment Needed for Inspection

The following tools and equipment will be needed to perform inspection and adjustments. • Assorted flat-blade and Phillips screwdrivers • Circuit tester or digital VOM • Industrial-grade alcohol and clean cotton cloth • Synchroscope • Pen-chart recording oscilloscope • Thermometer, hygrometer

130

Page 145

Replacing SYSMAC LINK Units

9-2

Section 9-2

Replacing SYSMAC LINK Units Note

1. Data link tables and network parameters are stored in the EEPROM in the SYSMAC LINK Unit. Be extremely careful when removing this component from the old SYSMAC LINK Unit and inserting it in the new Unit. 2. Always turn off the power supply to the PC before attempting to replace a Unit.

Manually Set Data Link

If data links have been established manually, the data link table must be re-set after mounting the new Unit and before activating data links. If data link areas are set automatically, this re-set operation is unnecessary as long as SW1 and SW2 are set correctly.

Network Parameters

To use network parameters other than default values, use the following procedure after mounting the new Unit.

1, 2, 3...

1. Set SW1 pin 8 to ON (polling unit setting*). 2. After initializing the SYSMAC LINK Unit, confirm that it has correctly joined the Network by checking the indicators (INS LED lit, and ERC and ERH LEDs not lit indicate normal operation). 3. Set SW1 pin 8 to OFF (polled unit setting*). 4. After initializing the SYSMAC LINK Unit, confirm that it has correctly joined the Network by checking the indicators (INS LED lit, and ERC and ERH LEDs not lit indicate normal operation).

Note *Refer to 4-5 Polling Unit Setting for more information on the polling unit.

131

Page 146

This page is a scan with no text; see it in the PDF.

Page 147

Appendix A Standard Models

SYSMAC LINK Units Name SYSMAC LINK Unit

Specifications Use optical fiber cable. Refer to the tables below for accessories.

Model C200HW-SLK13 C200HW-SLK14 C1000H-SLK11 C200HW-SLK23 C200HW-SLK24 C1000H-SLK21-V1

Includes to secures the optical fiber cables to the Unit. Use coaxial cable. Refer to the tables below for accessories.

Accessories The required number of each of the following is included with the SYSMAC LINK Units. Replacement parts can be ordered using the following model numbers. • Optical-type Units Name Optical Fiber Cable Mounting Bracket

Specifications Secures the optical fiber cables to the Unit and includes the following: Mounting Bracket M3 hexagonal nuts (2) Cable Retainer

Pan-head Phillips screws (M3 x 6) (2)

Terminal screws (2)

Binding Phillips screw (M3 x 10)

• Coaxial Units Name F Adapter F Adapter cover

Specifications One of each is included with the C200HW-SLK23/24 and C1000H-SLK21-V1.

F Adapter Attachment Stirrup

One is included with the C200HW-SLK23/24 only.

Model C1000H-CE001 C1000H-COV01 C200H-TL001

Related Items The following items might be required depending on the SYSMAC LINK Unit and system configuration. Name Bus Connector (For C200HX/HG/HE)

Bus Connector (For C200H/HS) Communications Board Terminator

Specifications Required to connect SYSMAC LINK Unit(s) to a Connects one Unit C200HX/HG/HE. Connects two Units Required to connect one SYSMAC LINK Unit Connects two Units and one PC Card Unit to a C200HX/HG/HE. Required to connect SYSMAC LINK Unit(s) to a Connects one Unit C200H/HS. Connects two Units Required to connect SYSMAC LINK Unit(s) to a C200HX/HG/HE. Two required for each Network connected with coaxial cable.

Model C200HW-CE001 C200HW-CE002 C200HW-CE012 C200H-CE001 C200H-CE002 C200HW-COM01 C200HW-COM04-EV1 C1000H-TER01

Auxiliary Power Supply Units Name Auxiliary Power Supply Unit

Specifications For use with the C1000H-SLK11. For use with the C200HW-SLK13/14.

Model C1000H-APS01 C200H-APS03

133

Page 148

Appendix A

Standard Models

Accessories The required number of each of the following is included with the Auxiliary Power Supply Units. Replacement parts can be ordered using the following model numbers. Name

Specifications

Power Supply Cable (Supplies one Unit.)

Model

One is included with the C1000H-APS01.

C1000H-CN111

One is included with the C200H-APS03.

C200H-CN111

Related Items The following items will be required when connecting two Units to one Power Supply Unit. Name Power Supply Cable

Specifications Connects to one Unit. Order one more cable (one is included with the Power Supply Unit) when connecting two C1000H-SLK11 Units. Connects to two Units. Order one when connecting two C200HWSLK13/14 Units.

Model C1000H-CN111 C200H-CN211

Applicable CPU Units The following table shows which CPU Units are compatible with which SYSMAC LINK Units. The SYSMAC LINK Units cannot be used with other CPU Units or with a C2000H Duplex System (even one set for Simplex operation.) A Communications Board equipped with a Link Interface (C200HW-COM01/04-EV1) is required when mounting a SYSMAC LINK Unit to a C200HX/HG/HE PC. SYSMAC LINK Unit

Specifications

C1000H-SLK21-V1 C1000H-SLK11 C200HW-SLK23/24

Coaxial-type Optical-type Coaxial-type

C200HW-SLK13/14

Optical-type

Applicable CPU Unit(s) C1000H-CPU01-EV1 C2000H-CPU01-EV1 C200H-CPU11-E C200H-CPU31-E C200HS-CPU31-E C200HS-CPU33-E C200HX-CPU34-E C200HX-CPU44-E C200HX-CPU54-E C200HX-CPU64-E C200HG-CPU33-E C200HG-CPU43-E C200HG-CPU53-E C200HG-CPU63-E C200HE-CPU32-E C200HE-CPU42-E

Connectors and Related Items The following tables list the optical and coaxial connectors as well as tools used to attach the connectors and test connections.

Optical-type Name Optical Connector

Optical Connector Assembly Tools Optical Power Tester Master Fiber

Specifications

Model

Connects the optical fiber cable to the C1000H-SLK11. (See note 1.) Two are required for each node. Connects the optical fiber cable to the C200HW-SLK13/14. Two are required for each node. (Can be used with the C1000H-SLK11 too.) This inline adapter splices optical fiber cable. One is required for each break in the cable. For use with the S3200-COCF2071/COCF2571 Optical Connector. (Optical fiber cable cutters are included) For use with the S3200-COCF2071/COCF2571 Optical Connector. (Head Unit model number: S3200-CAT2702) For use with the S3200-COCF2071/COCF2571 Optical Connector.

S3200-COCF2071 S3200-COCF2571 S3200-COIA2000 CAK-0057 (See note 2.) S3200-CAT2700 S3200-CAT2001H

Note 1. Never use the S3200-COCF2011 Optical Connector with C200HW-SLK13/14 SYSMAC LINK Units. The connector might become stuck in the Unit if inserted.

134

Page 149

Appendix A

Standard Models

2. The S3200-COCF2071/2571 Connectors can be assembled using the S3200-CAK1062 by adding the JRFK-57PWS (made by Sumitomo Electric Industries, Ltd.).

Coaxial-type Units Name

Specifications

Model

BNC Connector

Crimp-on connector.

BNC-P-5C-CR10-B

Crimping Tool

Attaches the connector.

CR-H-1130

Cables Optical Fiber Cable The following table lists the Hard Plastic-clad Optical Fiber Cables that can be used with the C200HW-SLK13/14 and C1000H-SLK11. Name Optical Fiber Cable

Specifications

Model

Black, 10 m long

S3200-HCCB101

Black, 50 m long

S3200-HCCB501

Black, 100 m long

S3200-HCCB102

Black, 500 m long

S3200-HCCB502

Black, 1000 m long

S3200-HCCB103

Orange, 10 m long

S3200-HCCO102

Orange, 50 m long

S3200-HCCO501

Orange, 100 m long

S3200-HCCO102

Orange, 500 m long

S3200-HCCO502

Orange, 1000 m long

S3200-HCCO103

The following table shows the code used the last 6 or 7 characters (after S3200-H) of the Optical Fiber Cable model numbers. Character

Possible characters

Meaning

First

C or B

C indicates cord, and B indicates cable.

Second

C or L

C indicates no power cable, and L indicates power cable attached.

Third

B or O

B indicates black, and O indicates orange.

Fourth Fifth

A = 1 to 9 Always 0

Cable length in scientific notation. L = A : 10B.

Sixth

B = 1 to 3

Seventh

N or blank

N indicates no tension wires are attached.

Coaxial Cable Use a high quality 5C-2V coaxial cable with the C200HW-SLK23/24 and C1000H-SLK21-V1.

Peripheral Devices Name

Specifications

Model

SSS

IBM PC/AT or compatible, 3.5” disks

CVSS

IBM PC/AT or compatible, 3.5” disks

C500-ZL3AT1-E V1.1 CV500-ZS3AT1-EV2

Programming Console

Vertical, w/backlight

3G2A5-PRO13-E

Horizontal, w/backlight

3G2A6-PRO15-E

Hand-Held, w/backlight Except for C200H and C20, the Programming C200H-PRO27-E Console Adapter AP003 and connecting cable CN222/CN422 are necessary. They are sold separately.

135

Page 150

This page is a scan with no text; see it in the PDF.

Page 151

Appendix B Specifications Communications Specifications Item

Specification

Communications method

C200HW-SLK23/SLK24 and C1000H-SLK21-V1 Token ring (N:N)

Transmission method

Manchester encoding, baseband

Data transmission rate

2 Mbps

Media

Coaxial cable (5C-2V)

Hard-plastic-clad quartz optical fiber cable

Transmission path

Bus

Daisy chain

No. of nodes

62 max.

Distance between nodes

Total: 1 km

Message length

512 bytes max. (not including header)

Connectors

BNC (F Adaptor)

Link functions

Data link, data read/write service

Data link words

2,966 words max. in LR and DM Areas combined (918 words max. with only C200HWSLK13/SLK23 in data link) (see note 2)

Send/receive buffer capacity

Buffers for 13 messages (1-message send buffer +2-message receive buffer+10-message send/receive buffer)

RAS functions

Automatic polling unit backup, self-diagnostics (internode echo tests), failed node bypass (optical systems only), watchdog timer, error (CRC-CCITT) detection = X16 + X12 + X5 + 1 C200HW-SLK23/SLK24: 0.4 kg max. C200HW-SLK13/SLK14: 0.5 kg max. C1000H-SLK21-V1: 0.6 kg max. C1000H-SLK11: 0.7 kg max.

Weight

C200HW-SLK13/SLK14 and C1000H-SLK11

Total: 10 km (800 m max. between nodes if press-fit; 1 km if polished and connected) (see note 1) Full, half-lock press-in connector

Note 1. A press-fit type connector, which ensures a transmission distance of 800 m, can be made by the user. A cable with connectors is a polished-connection type, and ensures a transmission distance of 1 km. 2. There are some usage restrictions in systems that incorporates the C200HW-SLK14/SLK24 or C1000H-SLK11/SLK21-V1 with the in the same system. Refer to 5-6-1 Combining the C200HWSLK13/SLK23 with other SYSMAC LINK Units for details.

SR and AR Bits Refer to your PC’s Operation Manual for tables of all SR and AR bits that can be used in relation to SYSMAC LINK Units.

137

Page 152

This page is a scan with no text; see it in the PDF.

Page 153

Appendix C Internal Configuration The diagrams below show the configuration of the internal components of SYSMAC LINK Units.

Optical Units CPU

CPU bus connector

Communications controller

System ROM

Buffer memory

C200H or C1000H Interface

RAM

EEPROM*

Optical interface

Optical module

Optical module

Note *Network parameters and data link tables are backed up in EEPROM.

Coaxial-cable Units CPU

CPU bus connector

Communications controller

System ROM

Buffer memory

C200H or C1000H Interface

RAM

EEPROM*

Driver/ receiver

BNC connector

Note *Network parameters and data link tables are backed up in EEPROM.

139