Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 3 of 19

C-series SYSMAC LINK System Manual, pages 14 to 23

Pages 14 to 23 of 174

The original document is the PDF (983 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200HW-SLK24

Page 14

5

Application Precautions

• Always use the power supply voltages specified in this manual. An incorrect voltage may result in malfunction or burning. • Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction. • Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning. • Do not apply voltages to the Input Units in excess of the rated input voltage. Excess voltages may result in burning. • Do not apply voltages or connect loads to the Output Units in excess of the maximum switching capacity. Excess voltage or loads may result in burning. • Disconnect the functional ground terminal when performing withstand voltage tests. Not disconnecting the functional ground terminal may result in burning. • Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in this manual. Incorrect tightening torque may result in malfunction. • Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit. • Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction. • Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning. • Wire correctly. Incorrect wiring may result in burning. • Mount Units only after checking terminal blocks and connectors completely. • Be sure that the terminal blocks, Memory Units, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction. • Check the user program for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation. • Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation. • Changing the operating mode of the PC. • Force-setting/force-resetting any bit in memory. • Changing the present value of any word or any set value in memory. • Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming operation. Not doing so may result in an unexpected operation. • Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may break the cables. • Do not place objects on top of the cables or other wiring lines. Doing so may break the cables. • Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning. • When replacing parts, be sure to confirm that the rating of a new part is correct. Not doing so may result in malfunction or burning. • Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any static built-up. Not doing so may result in malfunction or damage.

xiv

Page 15

SECTION 1 Introduction This section introduces the features and operations of the SYSMAC LINK Units. It also describes the possible system configurations and compatibility with PCs and other Link Units. 1-1 1-2 1-3

1-4

1-5

OMRON Network Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SYSMAC LINK System Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-1 Single-level Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-2 Multilevel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-1 Compatibility with PCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-2 Compatibility with Other Link Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 3 4 4 5 6 6 6 8

1

Page 16

Section 1-1

OMRON Network Systems

1-1

OMRON Network Systems As production processes become more complex and diversified, it is necessary to develop networks that link control components such as PCs to more powerful host computers in LANs that control entire production processes. OMRON provides 3 types of network systems for large, medium, and smallscale networks.

SYSMAC NET Link System

The SYSMAC NET Link System is a high-speed, high-capacity LAN. It can be used as a gateway to a general LAN composed of different kinds of computers or to an Ethernet to create a large-scale network.

SYSMAC LINK System

The SYSMAC LINK System provides high-speed, high-capacity communications between any nodes (PCs, or IBM-PC/AT or compatible running SSS) in the network, as well as remote monitoring and programming functions and automatic data transfer via data links.

SYSMAC BUS System

The SYSMAC BUS Remote I/O System is used to link a single PC to remote racks called Slave Racks and/or components (e.g., I/O Terminals or Programmable Terminals) to form a small, decentralized control network. Depending on the size and complexity of the production process, these systems can be used alone or in combination as shown below.

Host computer

PC

Bridge

SYSMAC NET Link System

PC

SYSMAC NET Link System

PC

SYSMAC LINK System PC

PC

PC

Host computer

SYSMAC BUS Remote I/O System

Expansion I/O Rack

2

Expansion I/O Rack

I/O Terminal

Expansion I/O Rack

Page 17

SYSMAC LINK System Features

1-2

Section 1-2

SYSMAC LINK System Features SYSMAC LINK Units are equipped with a variety of special features.

High Speed, Reliability, and Flexibility

The specialized communications LSIs used in all SYSMAC LINK Units deliver high speed, reliability, and flexibility in an advanced data link system, while optical fiber cable systems provide high-speed communications with unparalleled immunity to noise. In the event of an error or failure in the polling unit, another node automatically takes over management of the SYSMAC LINK System without stopping the entire network. SSS or CVSS running on an IBM-PC/AT or compatible can monitor and/or program PCs anywhere in the network via the SYSMAC LINK System.

Distributed Control with Data Links

The data link function transfers data to and from other nodes automatically, establishing simple but powerful peer-to-peer links between nodes. Data links can be generated automatically between 2, 4, 8, or 16 nodes by changing the value of just one byte in the AR Area of the start-up node. Or the user can use the flexibility of manually generating data links to eliminate unused link words, improve data link I/O response time, and to even create several data link groups in one network. The data link communications cycle time can be fixed at a constant value, so even simultaneous remote programming/monitoring and NETWORK READ/ WRITE instruction (RECV(98)/SEND(90)) execution have no effect on the data link I/O response time.

Active PC Transmission

1, 2, 3...

PCs can communicate actively with other PCs in the network. The four functions listed below can be performed from the PC’s program using the SEND(90) and RECV(98) instructions (SEND(192), RECV(193), and CMND(194) in the CVseries). 1. Broadcast transmission 2. Response monitoring time setting (response time-out setting) 3. Transmit retry setting 4. Enabling/disabling response

RAS Functions

SYSMAC LINK Units are equipped with three RAS functions (RAS is an acronym for reliability, availability, and serviceability). The Polling Unit Backup and Failed Node Bypass (optical systems only) functions prevent the network from failing when one Unit fails. The Internode Echo Test function aids in communications troubleshooting. Remote monitoring of the network’s operating status also aids in troubleshooting and quick correction of communications problems.

Improvements on the C200HS-SLK12/SLK22 (C200HW-SLK13/SLK14/ SLK23/SLK24)

Up to 2,966 words can be linked using the data link function with the C200HWSLK14/SLK24. The input interrupt response time is 1 ms maximum when the new SYSMAC LINK Units are mounted to a C200HX, C200HG, or C200HE PC.

3

Page 18

Section 1-3

System Configuration

1-3

System Configuration Up to 62 nodes (including all PCs and, in coaxial systems, computers) can be connected in a SYSMAC LINK Network via SYSMAC LINK Units or Network Service Boards. One of the Units in the network will function as the polling unit and the remainder will be polled units. The polling unit manages the System communications during and after configuration.

1-3-1 Single-level Systems The following diagrams show the general configuration of Single-level SYSMAC LINK Systems connected with coaxial and optical fiber cables. The Systems are considered single-level because each PC has only one SYSMAC LINK Units mounted to it. The SSS/CVSS connection is not a required part of the System. It is shown here because of its usefulness in monitoring and controlling not only the operation of the SYSMAC LINK System itself, but the general operation of all the PCs connected in the System. Coaxial System

The abbreviation NSB indicates a SYSMAC LINK Network Service Board. CPU Rack

CPU Rack

CPU Rack

SYSMAC LINK Unit

SYSMAC LINK Unit

SYSMAC LINK Unit

CPU Unit

CPU Unit

CPU Unit

Computer

NSB

SSS/ CVSS

Note Terminators must be connected to the Units on the ends of the network. Optical System

The abbreviation APS indicates an Auxiliary Power Supply Unit.

CPU Rack

CPU Rack

CPU Rack

APS

APS

APS

APS

SYSMAC LINK Unit

SYSMAC LINK Unit

SYSMAC LINK Unit

SYSMAC LINK Unit

CPU Unit

CPU Unit

CPU Unit

CPU Unit

Backup Power Supply

4

CPU Rack

SSS/ CVSS

Page 19

Section 1-3

System Configuration

1-3-2 Multilevel System Each PC can have up to two SYSMAC LINK Units mounted. Each SYSMAC LINK Unit will connect it to a SYSMAC LINK Network, i.e., if a PC has two SYSMAC LINK Units mounted, it is part of two SYSMAC LINK Networks and the overall system is considered a Multilevel SYSMAC LINK System. Operating levels, which are described later in this manual, are used to differentiate between the two Networks to which one PC might belong. The SSS/CVSS connection is not a required part of the System. It is shown here because of its usefulness in monitoring and controlling not only the operation of the SYSMAC LINK System itself, but the general operation of all the PCs connected in the same Network(s) as the PC to which the SSS/ CVSS is connected. The abbreviation SLK indicates a SYSMAC LINK Unit.

Subsystem 1 operating level 1

CPU Rack

CPU Rack

CPU Rack

CPU Rack

SYSMAC LINK Unit

SYSMAC LINK Unit

SYSMAC LINK Unit

CPU Unit

CPU Unit

CPU Unit

SSS/ CVSS

SYSMAC LINK Unit SYSMAC LINK Unit

CPU Unit Subsystem 3 operating level 1 CPU Rack

CPU Rack

CPU Rack

SYSMAC LINK Unit

Subsystem 2 operating level 0

SSS/ CVSS

SYSMAC LINK Unit

SYSMAC LINK Unit

SYSMAC LINK Unit

CPU Unit

CPU Unit

CPU Unit

Note Terminators must be connected to the Units on the ends of networks connected by coaxial cable.

5

Page 20

Section 1-4

Unit Compatibility

1-4

Unit Compatibility There are some restrictions regarding the models and versions of PCs to which SYSMAC LINK Units can be mounted. There are also limitations in using SYSMAC LINK Units together with other Link Units. These limitations are described in this section.

1-4-1 Compatibility with PCs The following table shows which CPU Units are compatible with which SYSMAC LINK Units. The SYSMAC LINK Units cannot be used with other CPU Units or with a C2000H Duplex System (even one set for Simplex operation.) A Communications Board equipped with a Link Interface (C200HWCOM01/04-EV1) is required to mount a SYSMAC LINK Unit to a C200HX, C200HG, or C200HE PC. SYSMAC LINK Unit

Cable

C1000H-SLK21-V1 C1000H-SLK11

Coaxial Optical fiber

C200HW-SLK23 C200HW-SLK24

Coaxial

C200HW-SLK13 C200HW-SLK14

Optical fiber

Applicable CPU Unit(s) C1000H-CPU01-EV1 or C2000H-CPU01-EV1 C200H-CPU11-E C200H-CPU31-E C200HS-CPU31-E C200HS-CPU33-E C200HE-CPU32-E C200HE-CPU42-E C200HG-CPU33-E C200HG-CPU43-E C200HG-CPU53-E C200HG-CPU63-E C200HX-CPU34-E C200HX-CPU44-E C200HX-CPU54-E C200HX-CPU64-E

1-4-2 Compatibility with Other Link Units C1000H-SLK11 and C1000H-SLK21-V1 The following combinations of Units can be mounted on a single C1000H or C2000H PC.

1, 2, 3...

1. Two SYSMAC LINK Units 2. One SYSMAC LINK Unit and one SYSMAC NET Link Unit 3. One SYSMAC LINK Unit and one Rack-mounting Host Link Unit In addition to the Units in the above combinations you may also mount one CPU Unit-mounting Host Unit or up to two PC Link Units. Only one PC Link Unit can be mounted on the C500-BC081 and C500-BC051 Backplanes, because these Backplanes have only 3 linkable slots.

6

Page 21

Section 1-4

Unit Compatibility

When combining Units as shown above, use the following models. Name

Model

SYSMAC LINK Unit

C1000H-SLK11

Optical type

C1000H-SLK21-V1

Coaxial type

SYSMAC NET Link Unit

C500-SNT31-V4

Rack-mounting Host Link Units

C500-LK103 C500-LK103-P C500-LK203

Other versions cannot be used. Other versions cannot be used.

CPU Unit-mounting Host Link Units

3G2A6-LK101-EV1 3G2A6-LK101-PEV1 3G2A6-LK201-EV1 3G2A6-LK202-EV1 C500-LK009-V1 C500-LK009

PC Link Units

! Caution

Remarks

---

---

Be sure to set a unique operating level for each system when combining SYSMAC LINK Units, SYSMAC NET Link Units, and/or Host Link Units (SYSMAC WAY) on the same PC.

C200HW-SLK13, C200HW-SLK14, C200HW-SLK23, and C200HW-SLK24 The following combinations of Units can be mounted on a single PC. Some power supplies might not have sufficient capacity for all system configurations; be sure to check power supply requirements and capacities carefully.

1, 2, 3...

1. Two SYSMAC LINK Units 2. One SYSMAC LINK Unit and one SYSMAC NET Link Unit In addition to the Units in the above combinations you may also mount one CPU Unit-mounting Host Link Unit, up to two rack-mounting Host Link Units, or up to two PC Link Units. For the C200HX, C200HG, or C200HE PC, one SYSMAC LINK Unit and one PC Card Unit may be mounted. When combining Units as shown above, use the following models. Name SYSMAC LINK Unit

Model

Remarks Optical type

SYSMAC NET Link Unit

C200HW-SLK13 C200HW-SLK14 C200HW-SLK23 C200HW-SLK24 C200HS-SNT32

PC Card Unit

C200HW-PCU01

Can be used only with with the C200HX, C200HG, or C200HE.

Rack-mounting Host Link Units

C200H-LK101 (-PV1) C200H-LK201-V1 C200H-LK202-V1

---

CPU Unit-mounting Host Link Units

3G2A6-LK101-EV1 3G2A6-LK101-PEV1 3G2A6-LK201-EV1 3G2A6-LK202-EV1 C200H-LK401

Cannot be used with the C200HS, C200HX, C200HG, or C200HE.

PC Link Units

Coaxial type ---

---

Note Be sure to set a unique operating level for each system when combining SYSMAC LINK Systems, SYSMAC NET Link Systems, and the PC Card Unit on the same PC.

7

Page 22

Precautions

1-5

Section 1-5

Precautions • A Bus Connector is required to mount the C200HW-SLK13, C200HW-SLK14, C200HW-SLK23, or C200HW-SLK24. Refer to Section 3 Installation for details. • Be sure to set different operating levels when mounting a SYSMAC LINK Unit on the same PC with a SYSMAC NET Link Unit, Host Link Unit (Rack-mounting type), or PC Card Unit. Refer to Section 2 Unit Components and Switch Settings for details. • The input interrupt response speed is 1 ms max. for the C200HW-SLK13, C200HW-SLK14, C200HW-SLK23, or C200HW-SLK24 when mounted to the C200HX/HG/HE and 10 ms max. when mounted to the C200H or C200HS. • The C200HW-SLK13, C200HW-SLK14, C200HW-SLK23, or C200HWSLK24 are totally upwardly compatible from the C200HS-SLK12 and C200HS-SLK22. • The power supply capacity depends on the CPU Unit that is being used. Refer to you PC’s Installation Guide for details and do not run over the power supply capacity.

8

Page 23

SECTION 2 Unit Components and Switch Settings The names and functions of the SYSMAC LINK Units’ components and switch settings are described in this section. 2-1 2-2 2-3 2-4

2-5

C1000H-SLK11/SLK21-V1 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C200HW-SLK13/14/23/24 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-1 C1000H-SLK11/SLK21-V1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4-2 C200HW-SLK13/14/23/24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-1 Node Number Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-2 C1000H-SLK11/SLK21-V1 DIP Switch 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5-3 C200HW-SLK13/14/23/24 DIP Switches 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . .

10 12 13 14 14 14 15 15 16 16

9