For the Omron C200HW-SLK24

Page 24

Section 2-1

C1000H-SLK11/SLK21-V1 Components

2-1

C1000H-SLK11/SLK21-V1 Components

Front C1000H-SLK11

C1000H-SLK21-V1

SLK11

SLK21-V1

RUN ERC

P/S ERH

INS

M/S

SD

RD

TS

LNK

RUN ERC

Indicators Indicate operational status.

ERH

INS

M/S

SD

RD

TS

LNK

Node number switches Used to set the node number. Reset switch Used to reinitialize the SYSMAC LINK Unit. DIP switch 1 Remove this cover to gain access to DIP switch 1. The switch is used to set a variety of operating parameters. Power supply connector Connect to the Auxiliary Power Supply Unit.

Optical fiber connectors Used to connect optical fiber cables.

Coaxial connector Used to connect coaxial cable.

Note Do not push the Reset Switch on SYSMAC LINK Units when the RUN indicator is not lit (watchdog timer error).

10

Page 25

Section 2-1

C1000H-SLK11/SLK21-V1 Components Back

The backs of the C1000H-SLK11 and C1000H-SLK21-V1 are identical. Mounting screw Secures Unit to Backplane

Connector Used to connect the SYSMAC LINK Unit to the Rack.

Mounting screw Secures Unit to Backplane

11

Page 26

Section 2-2

C200HW-SLK13/14/23/24 Components

2-2

C200HW-SLK13/14/23/24 Components

Front C200HW-SLK13/14

C200HW-SLK23/24 SLK24

SLK14 RUN ERC INS SD

P/S ERH M/S RD

TS LNK

Indicators Indicate operational status.

RUN ERC INS SD

ERH M/S RD

TS LNK

Node number switches Used to set node number. DIP switch 1 Remove this cover to gain access to DIP switch 1. The switch is used to set a variety of operating parameters. SYSMAC LINK Unit Connector Used to connect the SYSMAC LINK Unit to the CPU Unit.

Power supply connector Connect to the Auxiliary Power Supply Unit. Coaxial connector Used to connect coaxial cable. Optical fiber connectors Used to connect optical fiber cables.

Back

The backs of the C200HW-SLK13/14 and C200HW-SLK23/24 are identical.

DIP switch 2 Used to set a variety of operating parameters.

Connector Used to connect the SYSMAC LINK Unit to the Rack.

12

Page 27

Section 2-3

Indicators

2-3

Indicators The status of the SYSMAC LINK Unit is indicated by the indicators shown below. The Units that use coaxial cables (C1000H-SLK21-V1 and C200HW-SLK23/24) are not equipped with the P/S indicator. C1000H-SLK11 C1000H-SLK21-V1

C200HW-SLK13/14

C200HW-SLK23/24

RUN ERC

P/S ERH

RUN ERC

ERH

INS

M/S

INS

M/S

RUN ERC INS SD

RUN ERC INS SD

SD

RD

SD

RD

TS

LNK

TS

LNK

Name

Indicator Color

RUN

Green

P/S (power supply on, optical units only)

Green

ERC (communications error)

Red

ERH (PC error)

Red

INS (Network inclusion) M/S (polling unit) SD (transfer) RD (receive) TS (test)

LNK (data link)

Orange

Orange Orange Orange Orange

Orange

P/S ERH M/S RD

TS LNK

ERH M/S RD

TS LNK

Meaning Condition Lit

Unit is operating normally.

Not lit

Watchdog timer error has occurred.

Lit

Power is being supplied from the Auxiliary Power Supply Unit.

Not lit

Power is not being supplied from the Auxiliary Power Supply Unit.

Lit

Communications error has occurred, node number setting is incorrect, or same node number has been set twice.

Not lit

None of the above errors has occurred.

Lit Not lit

PC CPU, PC model, PC version, PC interface, or EEPROM error has occurred. None of the above errors has occurred.

Lit

Unit is part of Network.

Not lit

Unit is not part of Network.

Lit

Unit is polling unit.

Not lit

Unit is not part of Network or is polled unit.

Lit

Unit is sending data.

Not lit

Unit is not sending data.

Lit

Unit is receiving data.

Not lit

Unit is not receiving data

Lit

Test is being executed.

Flashing

Test setting error has occurred.

Not lit

Test is not being executed.

Lit

Unit is part of active data link.

Flashing

Data link error has occurred.

Not lit

Unit is not part of active data link.

13

Page 28

Section 2-4

Switches

2-4

Switches

2-4-1 C1000H-SLK11/SLK21-V1 DIP switch 1 can be accessed by removing the cover from the front of the Unit with a standard screwdriver.

NODE NO. x101 x100

Node number switches Used to set node number.

RESET

8 7 6 5

SW

DIP switch 1

4 3 2 1

Standard screwdriver

2-4-2 C200HW-SLK13/14/23/24 The node number switches and DIP switch 1 are located on the front of the Unit, and DIP switch 2 is located on the back. Front

NODE NO. x101 x100

Node number switches Used to set node number.

4

SW

3 2 1

14

DIP switch 1

Page 29

Section 2-5

Setting Switches Back

4 3 2

DIP switch 2

1

2-5

Setting Switches Switch settings determine how the SYSMAC LINK Units will work together in a Network. Be sure to turn the power off to the PC before setting the switches. Errors in switch settings, which may not always be detected by the System, can cause faulty data communications. Set and check all switch settings carefully.

2-5-1 Node Number Switches Turn off the power to the PC before setting the node number switches. Node number switches determine the node number. The left switch sets the tens digit; the right switch sets the ones digit. The node number must be between 01 and 62. Each SYSMAC LINK Unit in a Network must have a unique node number. Use a small flat-blade screwdriver to set node number switches, being careful not to damage them. Note Units in the same network must have unique node numbers.

15

Page 30

Section 2-5

Setting Switches

2-5-2 C1000H-SLK11/SLK21-V1 DIP Switch 1 Turn off the power to the PC before setting the DIP switch. DIP switch 1 is used to control the communications test, data link activation, operating level, PC operating mode when power is applied, network parameter initialization, and polling/polled unit operation. Refer to the pages indicated in the table for more details on these settings. Pin

Function When ON

Note

Page When OFF

1

Test activated.

Test stopped.

111

2

Data link activated.

Data link stopped.

58

3

Operating level 0

Operating level 1

38

41

For maintenance use only. Leave this switch set to OFF.

---

5

38

61

PC enters MONITOR mode at PC enters usual mode at start-up. start-up. Not used. Leave this switch set to OFF.

72

Network Parameters initialized.

40

82

Polled unit

Network Parameters not initialized. Polling unit

---

39

1. Pins 4 and 6 should always be OFF. 2. Pins 7 and 8 are normally OFF.

2-5-3 C200HW-SLK13/14/23/24 DIP Switches 1 and 2 Turn off the power to the PC before setting the DIP switches. DIP switch 1 is used to control the communications test, data link activation, and operating level. DIP switch 2 is used to control network parameter initialization and polling/polled unit operation Refer to the pages indicated in the tables for more details on these settings. DIP Switch 1 (Front of the Unit)

Pin

Function When ON

Page When OFF

1

Test activated.

Test stopped.

111

2

Data link activated.

Data link stopped.

58

3

Operating level 0

Operating level 1

38

4*

For maintenance use only. Leave this switch set to OFF.

---

Note *Pin 4 should always be OFF. DIP Switch 2 (Back of the Unit)

Pin

Function When ON

Note

When OFF

11

Not used. Leave this switch set to OFF.

---

21

Not used. Leave this switch set to OFF.

---

32

Network Parameters initialized.

40

42

Polled unit

Network Parameters not initialized. Polling unit

1. Pins 1 and 2 should always be OFF. 2. Pins 3 and 4 are normally OFF.

16

Page

39

Page 31

SECTION 3 Installation This section explains how to install SYSMAC LINK Systems. 3-1

3-2

3-3 3-4

3-5

Mounting Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-1 C1000H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-2 C2000H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-3 C200H/C200HS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-4 C200HX/C200HG/C200HE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Supply Unit Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2-1 Specifications and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2-2 Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bus Connector (C200HX/HG/HE/HS/H only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-1 Coaxial Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-2 Optical Fiber Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

18 18 18 18 19 20 20 22 25 26 26 28 33

17

Page 32

Section 3-1

Mounting Position

3-1

Mounting Position Note

1. Turn off power to the PC before mounting Units to the Backplane. 2. Tighten Backplane mounting screws firmly.

3-1-1 C1000H The C1000H-SLK11/SLK21-V1 can be mounted in one of the first three slots to the left of (i.e., next to) the CPU Unit when using the 3G2A5-BC081/051 Backplane, and in one of the first five slots to the left of the CPU Unit when using a C500-BC082/052 Backplane.

3G2A5-BC081/051 Backplane: Mount only in one of the three slots immediately to the left of the CPU Unit. CPU Rack

I/O Control Unit

CPU Unit

Power Supply Unit

C500-BC082/052 Backplane: Mount only in one of the five slots immediately to the left of the CPU Unit.

3-1-2 C2000H C1000H-SLK11/SLK21-V1 can be mounted in any slot in 3G2C5-BC061 Backplanes.

CPU Rack

I/O Control Unit

CPU Unit

Power Supply Unit

3G2C5-BC061 Any slot

3-1-3 C200H/C200HS The C200HW-SLK13/14/23/24 must be mounted in one of the two slots immediately to the left of the CPU Unit when using the C200H-BC081-V2 or C200H-BC051-V2 Backplane.

18

Page 33

Section 3-1

Mounting Position

If only one Unit is mounted, it must in the slot immediately to the left of the CPU Unit. If two SYSMAC LINK Units, or one together with a SYSMAC NET Link Unit, are mounted, the SYSMAC LINK Unit can be mounted in either of the two slots immediately to the left of the CPU Unit. CPU Rack

CPU Unit

C200H-BC081-V2/BC051-V2 Backplane The two slots to left of CPU Unit if two Units are mounted. CPU Rack

CPU Unit

C200H-BC081-V2/BC051-V2 Backplane The slot to left of CPU Unit if only one Unit is mounted.

Note Refer to 1-4-2 Compatibility with other Link Units for details on using a C200HWSLK13/14/23/24 SYSMAC LINK Unit with a SYSMAC NET Link Unit.

3-1-4 C200HX/C200HG/C200HE The C200HW-SLK13/14/23/24 must be mounted in one of the two slots immediately to the left of the CPU Unit when using a C200HWBC101/081/051/031 Backplane. If only one Unit is mounted, it must be in the slot immediately to the left of the CPU Unit. If two SYSMAC LINK Units, or one together with a SYSMAC NET Link Unit, are mounted, the SYSMAC LINK Unit can be mounted in either of the two slots immediately to the left of the CPU Unit. If one SYSMAC LINK Unit and one PC Card Unit are mounted, the SYSMAC LINK Unit must be in the slot immediately to the left of the CPU Unit. CPU Rack

CPU Rack

CPU Unit

C200HW-BC101/081/051/031 Backplane Two slots to left of CPU Unit if two Units are mounted.

CPU Unit

C200HW-BC101/081/051/031 Backplane Slot to left of CPU Unit if only one Unit is mounted.

CPU Rack

CPU Unit

PC Card Unit

C200HW-BC101/081/051/031 Backplane Two slots to left of CPU Unit if the SYSMAC LINK Unit and PC Card Unit are mounted.

SYSMAC LINK Unit

Note

1. Refer to 1-4-2 Compatibility with other Link Units for details on using a C200HW-SLK13/14/23/24 SYSMAC LINK Unit with a SYSMAC NET Link Unit.

19