The text of a manual · part 5 of 19

C-series SYSMAC LINK System Manual, pages 34 to 43

Pages 34 to 43 of 174

The original document is the PDF (983 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200HW-SLK24

Page 34

Section 3-2

Power Supply Unit Connection

2. A Communications Board equipped with a Link Interface (C200HWCOM01/04-EV1) is required when mounting a SYSMAC LINK Unit to a C200HX, C200HG, or C200HE PC.

3-2

Power Supply Unit Connection SYSMAC LINK Units that are connected with optical fiber cable (the C1000H-SLK11 and C200HW-SLK13/14) can be connected to an Auxiliary Power Supply Unit to provide backup power. By connecting the Unit to an Auxiliary Power Supply Unit, the entire system won’t go down if the Unit fails for some reason. The table below shows which Power Supply Units can be connected to the SYSMAC LINK Units. SYSMAC LINK Unit

Corresponding Power Supply

C1000H-SLK11

C1000H-APS01

C200HW-SLK13/14

C200H-APS03

3-2-1 Specifications and Components Specifications The following specifications apply to both the C1000H-APS01 and C200H-APS03. Item

20

Specification

Power supply voltage

100 to 120 VAC or 200 to 240 VAC (switchable)

Acceptable voltage range

85 to 132 VAC or 170 to 264 VAC

Power consumption

40 VA max.

Weight

0.5 kg max.

Other

Conform to C-series specifications

Page 35

Section 3-2

Power Supply Unit Connection Auxiliary Power Supply Unit Components C1000H-APS01

The diagram below shows the components of the C1000H-APS01 Auxiliary Power Supply Unit and their functions.

APS01 P/S

Indicators Indicate operational status.

Power supply connector 1 Supplies backup power to a SYSMAC LINK Unit.

P/S1

Power supply connector 2 Supplies backup power to a SYSMAC LINK Unit.

P/S2

L1 100240 VAC

Power supply terminals Backup AC power is supplied through these terminals.

L2/N LG

Ground Connect LG to a separate 100 W max. ground to prevent electrical shock. Connect GR to a separate 100 W max. ground to reduce noise and prevent electrical shock.

GR

C200H-APS03

The diagram below shows the components of the C200H-APS03 Auxiliary Power Supply Unit and their functions.

APS03 P/S

CN (OUT)

L1 100240 VAC L2/N

Indicators Indicate operational status.

Power supply connector Supplies backup power to a SYSMAC LINK Unit.

Power supply terminals Backup AC power is supplied through these terminals.

LG GR

Ground Connect LG to a separate 100 W max. ground to prevent electrical shock. Connect GR to a separate 100 W max. ground to reduce noise and prevent electrical shock.

21

Page 36

Section 3-2

Power Supply Unit Connection Power Cables

The following table shows which power cables are included with the C1000H-APS01 and C200H-APS03 as accessories. Unit

Power cable

C1000H-APS01

C1000H-CN111

1 cable provided

Notes

C200H-APS03

C200H-CN111

1 cable provided (for 1 SYSMAC LINK Unit)

When connecting 2 SYSMAC LINK Units to an Auxiliary Power Supply Unit, order the following cables separately as required. Unit

Power cable

C1000H-APS01

C1000H-CN111

Same as the one provided with the Unit.

Notes

C200H-APS03

C200H-CN211

For connection to 2 SYSMAC LINK Units

Indicators Name

Indicator Color Condition

P/S

Green

Meaning

Lit

Power is being supplied to the SYSMAC LINK Unit.

Not lit

Power is not being supplied to the SYSMAC LINK Unit.

Precautions The backup function will be disabled when the PC’s power is off, so connect the power supply terminals to an AC power supply other than the one connected to the PC. Always supply power to the Power Supply Unit before supplying power to the PC. Note

1. Turn off the power supply to the PC before mounting the Power Supply Unit. 2. Firmly tighten the Backplane mounting screws for the Power Supply Unit. 3. Leave the protective sticker in place on the Unit when wiring to prevent clippings and other foreign matter from entering the Unit during the wiring procedure. 4. Remove the protective sticker after completion of wiring before turning on power to the Unit. If Unit is operated with the protective sticker in place, the Unit may overheat, causing operational errors. 5. Do not pull on the cable. Pulling on the cable could break wires inside. 6. Do not bend the cable past the minimum radius. Bending the cable too far could break wires inside.

3-2-2 Installation and Wiring C1000H/C2000H Mounting Position

The C1000H-APS01 can be mounted in any slot, but the power cables are relatively short, so the Power Supply Unit cannot be more than 2 slots from the SYSMAC LINK Unit. One Power Supply Unit can supply backup power to two SYSMAC LINK Units, as shown below.

APS SLK SLK

22

CPU PS

Page 37

Section 3-2

Power Supply Unit Connection

In the following diagram, a Power Supply Unit is connected to just one SYSMAC LINK Unit.

APS SLK

Wiring

CPU PS

The Power Supply Unit and SYSMAC LINK Unit are connected by a power supply cable, as shown below. The cable can be plugged into either power supply connector on the Power Supply Unit. Power cable

Power Supply Unit or SYSMAC LINK Unit power supply connector The tab should be on the left.

Note

1. Turn off the power supply to the PC before mounting the Power Supply Unit. 2. Firmly tighten the Backplane mounting screws for the Power Supply Unit. 3. Leave the protective sticker in place on the Unit when wiring to prevent clippings and other foreign matter from entering the Unit during the wiring procedure. 4. Remove the protective sticker after completion of wiring before turning on power to the Unit. If Unit is operated with the protective sticker in place, the Unit may overheat, causing operational errors. 5. Do not pull on the cable. Pulling on the cable could break wires inside. 6. Do not bend the cable past the minimum radius. Bending the cable too far could break wires inside.

C200H/C200HS Mounting Position

The C200H-APS03 can be mounted in any slot, but the power cable included with the Unit will only reach to the next slot, so the Power Supply Unit must be mounted next to the SYSMAC LINK Unit. In the following diagram, a Power Supply Unit is connected to just one SYSMAC LINK Unit.

APS SLK

CPU

23

Page 38

Section 3-2

Power Supply Unit Connection

One Power Supply Unit can supply backup power to two SYSMAC LINK Units. In this case an optional power cable that will supply the two SYSMAC LINK Units must be purchased separately. One branch of the cable will reach two slots from the Power Supply Unit, as shown below.

APS SLK SLK

CPU

Note Connect the C200H-APS01 Power Supply Unit (for single-unit power supply) or the C200H-APS02 Power Supply Unit (for double-unit power supply) to the SYSMAC NET Link Unit. The C200H-APS03 Power Supply Unit cannot be connected to the SYSMAC NET Link Unit. If the SYSMAC Link Unit is used in combination with the SYSMAC NET Link Unit, be sure to mount them and the Power Supply Unit in the correct positions. Wiring

The Power Supply Unit and SYSMAC LINK Unit are connected by a power supply cable, as shown below. The tab on the connector should be on the right.

Power cable

The tab should be on the right.

Note

1. Turn off the power supply to the PC before mounting the Power Supply Unit. 2. Leave the protective sticker in place on the Unit when wiring to prevent clippings and other foreign matter from entering the Unit during the wiring procedure. 3. Remove the protective sticker after completion of wiring before turning on power to the Unit. If Unit is operated with the protective sticker in place, the Unit may overheat, causing operational errors. 4. Do not pull on the cable. Pulling on the cable could break wires inside. 5. Do not bend the cable past the minimum radius. Bending the cable too far could break wires inside.

24

Page 39

Section 3-3

Bus Connector (C200HX/HG/HE/HS/H only)

3-3

Bus Connector (C200HX/HG/HE/HS/H only) A Bus Connector is required to connect a C200HW-SLK13/14/23/24 SYSMAC LINK Unit to the CPU Unit of a C200HX, C200HG, C200HE, C200HS, or C200H PC. There are three models of Bus Connector available. One is used when a single SYSMAC LINK Unit is being mounted on the CPU Rack, one is used when two Units are being mounted (either two SYSMAC LINK Units or a SYSMAC LINK Unit and a SYSMAC NET Link Unit), and one is used when a single SYSMAC LINK Unit and a single PC Card Unit are mounted (C200HX/ HG/HE CPU Units only).

CPU Unit C200HX, C200HG, C200HE

C200H, C200HS

Communications Board C200HW-COM01 or C200HW-COM04-EV1

---

Bus Bar Connection

Bus Connector

Function

C200HW-CE001 Used when mounting just one SYSMAC LINK Unit. C200HW-CE002 Used when mounting two SYSMAC LINK Units or a SYSMAC LINK Unit and a SYSMAC NET Link Unit. C200HW-CE012 Used when mounting one SYSMAC LINK Unit and one PC Card Unit. C200H-CE001 Used when mounting just one SYSMAC LINK Unit. C200H-CE002 Used when mounting two SYSMAC LINK Units or a SYSMAC LINK Unit and a SYSMAC NET Link Unit.

Connect the Bus Connector as described below after turning off the PC.

1, 2, 3...

1. When using the C200HS or C200H PC, align the Bus Connector so it fits into the connectors on both the SYSMAC LINK Unit and PC CPU Unit, and then press it into the connectors. or When using the C200HX, C200HG, or C200HE PC, mount the Communications Board on the CPU Unit, align the Bus Connector so it fits into the connectors on both the SYSMAC LINK Unit and Communications Board, and then press it into the connectors. 2. Tighten the two screws on the Bus Connector to secure it. C200HS, C200H

C200HX, C200HG, C200HE

Communications Board C200HW-COM01 or C200HW-COM04-EV1

Note

1. Turn off the power supply to the PC before connecting the Bus Connector. 2. Firmly tighten the mounting screws of the Bus Connector.

25

Page 40

Section 3-4

Cable Connection

3-4

Cable Connection SYSMAC LINK Units can be connected with either coaxial cable or optical fiber cable. This section describes the procedures required to connect both types of cable.

3-4-1 Coaxial Cable The diagram below shows a SYSMAC LINK System connected by coaxial cables.

F Adapter Terminator Connector Terminator

5C-2V coaxial cable

Required Components 1, 2, 3...

1. Coaxial cable and connectors: Use 5C-2V coaxial cable designed for indoor use. Install connectors on each end of the cable. Cables must be continuous lengths only. No intervening cable connectors or breaks are permitted. 2. F Adapters (C1000H-CE001): Coaxial cables are connected to the SYSMAC LINK Units via F Adapters. One F Adapter is included as an accessory with SYSMAC LINK Units that use coaxial cables (C1000H-SLK21-V1 and C200HW-SLK23/24). An Attachment Stirrup (C200H-TL001) is also included with the C200HWSLK23/24. 3. Terminator (C1000H-TER01): Two Terminators (sold separately) are required for the F Adapters at the ends of the network.

Connection Procedure The connection procedure is described briefly below.

26

Note

1. Turn off the power supply to the PC before connecting the cables. 2. Leave the protective sticker in place on the Unit when wiring to prevent wire clippings and other foreign matter from entering the Unit during the wiring procedure. 3. Remove the protective sticker after completion of wiring before turning on power to the Unit. If Unit is operated with the protective sticker in place, the Unit may overheat, causing operational errors.

1, 2, 3...

1. Install connectors on each end of the cables. 2. Connect the Terminators to the F Adapters at the ends of the network (i.e., to the unused connectors at the last Unit on each end). Hold the connector in one hand and press the resistor into it firmly with the other.

Page 41

Section 3-4

Cable Connection

3. Connect the F Adaptors to the SYSMAC LINK Units by firmly pushing the adapter onto the coax connector on the Unit and turning the locking ring to the right until it locks. Start at one end of the network and connect the F Adapters to the other end in order.

Turn locking ring to the right.

With the C200H, C200HS, C200HX, C200HG, or C200HE, secure the F Adapter to the coaxial connector with an attachment stirrup.

C200H-TL001 Attachment Stirrup

4. Place an insulation cover over the F Adapter.

Insulation cover

27

Page 42

Section 3-4

Cable Connection

5. Any bends in the coaxial cable must be 45 mm in radius or greater (six times the outer diameter of the cable). When laying the cable, make wider bends of 110 mm in radius or greater (15 times the outer diameter of the cable).

Radius

> 45 mm

Note

1. Check to be sure that the coaxial cable if firmly locked into place after connecting it. 2. Do not pull on the cable. Pulling on the cable could break wires inside. 3. Do not bend the cable past the minimum radius. Bending the cable too far could break wires inside. 4. Do not place heavy objects on the cable or connectors. Heavy objects could break wires inside.

3-4-2 Optical Fiber Cable Required Components 1, 2, 3...

1. Optical fiber cable: Use Hard Plastic-clad Optical Fiber Cable (H-PCF). Refer to Appendix A Standard Models for details on available lengths and colors. 2. Optical Connectors: There are two types of Optical Connector available, as shown below. Use the cable splicing connector to splice cable. Function

Model number

Number required

Node-cable connection

S3200-COCF2071

2 for each node

Cable splicing

S3200-COIAT2000 (inline adapter)

1 for each break in the cable

Note Using an inline adapter to splice the cable will reduce the maximum transmission distance because of loss at the junction. Refer to your hard plastic-clad optical fiber cable (H-PCF) installation manual for details. 3. Optical Connector Assembly Tools: These tools are required to attach the Optical Fiber Cable to the Optical Connector. Optical Connector Assembly Tool Set S3200-CAK1062

Applicable Connectors S3200-COCF2071 (C1000H) S3200-COCF2571 (C200HS)

Note Optical fiber cable cutters are included. 4. Optical Fiber Tester (Optical Power Tester):

28

Tester Set

Head Unit

S3200-CAT2700

S3200-CAT2702

Applicable Connectors S3200-COCF2071 (C1000H) S3200-COCF2571 (C200HS)

Page 43

Section 3-4

Cable Connection 5. Master Fiber: Master Fiber S3200-CAT2001H

Applicable Connectors S3200-COCF2071 (C1000H) S3200-COCF2571 (C200HS)

Discontinued Products: Name

Optical Connector

Model number

Recommended replacement models

Manufacturer

S3200-COCF2011 S3200-COCF2071 OMRON S3200-COCF2511 S3200-COCF2571 OMRON

Optical Connector Assembly Follow the instructions provided with the S3200-CAK1062 Optical Connector Assembly Tool Set.

Connection Procedure The connection procedure is described briefly below. Begin with the highest node in the network and connect the lower nodes in order. Note

1. Turn off the power supply to the PC before connecting the cables. 2. Leave the protective sticker in place on the Unit when wiring to prevent clippings and other foreign matter from entering the Unit during the wiring procedure. 3. Remove the protective sticker after completion of wiring before turning on power to the Unit. If Unit is operated with the protective sticker in place, the Unit may overheat, causing operational errors. 4. Do not pull on the cable. Pulling on the cable could break fibers inside. 5. Do not bend the cable past the minimum radius. Bending the cable too far could break fibers inside. 6. Do not place heavy objects on the cable or connectors. Heavy objects could break fibers inside.

1, 2, 3...

1. Insert the terminals into the mounting bracket so that the tension wire holes are vertical, and then secure the terminals by tightening the nuts on the other side. 2. Insert the bushings into the mounting bracket and secure the bracket to the Unit with the Philips head screws provided. 3. If the cable has tension wires, thread them through the terminals and tighten the terminal screws to secure them. 4. Place the cables behind the clamp and secure them by tightening the Philips head screw provided. Secure both cables at once.

C1000H-SLK11

29